N.H. Admin. Code § Saf-C 6904.01 - Fire Watch Required
(a) The state fire marshal shall require an
approved fire watch when potentially hazardous conditions or a reduction in a
life safety feature exists due to the following factors, which shall include:
(1) Type of performance, display, exhibit,
contest or activity;
(2) Impairment
to a fire protection feature; and
(3) Number of persons present.
(b) The owner, agent or lessee
shall employ one or more qualified persons as standby fire personnel, to be on
duty at a required event, as determined by the authority having jurisdiction.
Prior to the start of the performance or event, the standby fire personnel
shall inspect the fire equipment or appliances provided, to ensure that they
are in the proper place and in good working order.
(c) Standby fire personnel shall keep
diligent watch for any fire(s) during the period of time the location is open
to the public and during the performance and take appropriate measures for the
extinguishment of any fire(s) that may occur.
(d) Standby fire personnel shall be subject
to any orders of the authority having jurisdiction at all times and shall be
identifiable and on duty during the following periods of time:
(1) When the location is open to the
public;
(2) While the performance
or event is being conducted; and
(3) Until normal operating conditions have
been resumed, as determined by the authority having jurisdiction.
(e) All standby fire personnel
shall have a means of communicating or transmitting an alarm in the event of a
fire or other emergency.
(f) The
operator shall provide the fire watch with the following equipment:
(1) At least 2 multipurpose dry chemical fire
extinguishers with a minimum 10-A 60 B:C rating; and
(2) Two pressurized water fire
extinguishers.
(g) Events
utilizing a singe stage shall be required to have a minimum of 3 qualified
standby fire personnel assigned to the display in the following manner:
(1) One standby fire fighter assigned stage
"left";
(2) One standby fire
fighter assigned stage "right"; and
(3) One standby fire fighter, familiar with
the particular pyrotechnic display, assigned to the operator.
(h) Events utilizing more than one
stage shall be required to have a minimum of 2 additional standby fire
personnel assigned to each additional stage. Portable fire extinguishers, as
set forth in (f) above, shall be provided for each additional stage.
(i) The premises where pyrotechnic effect or
flame effect materials or devices are handled, used or stored shall be
maintained in a neat and orderly condition and shall be free of any condition
that might create a fire hazard.
(j)
Immediately after each performance and prior to the removal of any property
related to the performance, the standby fire personnel shall verify with the
operator that all devices have been fired. Any unfired pyrotechnic effect or
flame effect materials or devices shall be disposed of in accordance with the
manufacturer's recommendations.
(k)
Notwithstanding any other rule to the contrary, the state fire marshal shall
have the right to increase or reduce the number of standby fire personnel for
any event utilizing pyrotechnic effects or flame effects before a proximate
audience, performers or support personnel, if after reviewing the application,
he/she determines that such an increase or reduction of standby fire personnel
is in the best interest of public safety.
(l) The operator shall contact the local fire
official and the state fire marshal's office at least 10 business days prior to
the event to confirm what fire or life safety measures are
required.