N.J. Admin. Code § 5:21-5.3 - System design and placement
(a) System design
and placement shall comply with the following construction specifications,
incorporated herein by reference: all applicable NJ Department of Environmental
Protection (NJDEP) rules, the American Water Works Association (AWWA)
standards, and in the Pinelands Area, the Standards of the Pinelands
Comprehensive Management Plan, with the strictest standards
governing.
(b) Distribution mains
of the overall system shall be connected into loops so that the supply may be
brought to the consumer from more than one direction. In balancing loops in a
design, the Hardy-Cross, or an equivalent, method shall be used (see subchapter
Appendix incorporated herein by reference). Manning roughness coefficients
listed in Table 7.2 in
N.J.A.C.
5:21-7.3 may be used in these calculations.
Dead-end lines shall be permitted within the design of a looped system provided
that there are no more than 20 dwelling units permanently, or no more than 50
dwelling units temporarily, on a dead-end line. When dead-end lines are used,
they shall be provided with a hydrant or blow off at the terminus as a means of
flushing.
(c) Valves, except on a
permitted dead end, shall be located on distribution mains so that no more than
one hydrant would be out of service as a result of a single water main break.
They shall be located in all small branches off larger mains; and where
eight-inch or larger mains lines intersect, a valve shall be located in each
branch. At street intersections, valves shall be located near pipe
intersections for ease in finding in the event of a water main break.
(d) In addition to the above requirements,
water mains shall be valved so that not more than one-fifth of a mile would be
affected by a single water main break. Geared valves on 16-inch mains or larger
shall be furnished when required by the municipality.
(e) Gate valves shall be cast-iron body with
double-disc gates, bronze mounted conforming to AWWA C500 or resilient-seated
wedge, non-rising stem mechanical joint conforming to AWWA C509. Butterfly
valves shall conform to AWWA C504. The type of valve to be used shall be as
specified by the municipality or utility authority. Valve interior openings
shall be full size, and valves on 16-inch mains or larger shall be geared and
have suitable bypasses. Valve boxes shall be of the adjustable type with the
cover marked "water" and direction of valve operation indicated.
(f) No pipe shall be placed on private
property unless the owner of the land is to own or operate the pipe, or an
easement deeded to the municipality or utility authority is obtained. All
easements shall be a minimum of 20-feet wide unless depth of pipe, soil
conditions, or additional utilities require wider. Where the easement is
located adjacent to a right of way, the municipality or authority may approve a
narrower easement.
(g) A building
service connection shall be comprised of a corporation stop at the main, a curb
stop, and a water meter. When the meter is located outside a building, an
additional shut-off valve shall be installed on the discharge side of the
meter. When the meter is located inside a building, valving shall be in
accordance with the Plumbing Subcode of the Uniform Construction Code
(N.J.A.C.
5:23-3.15). Curb stops and water meters shall
be located as specified by the public or private water supplier.
1. Common water service connections shall be
permitted where allowed by the Plumbing Subcode of the Uniform Construction
Code (N.J.A.C. 5:23-3.15).
(h) Where water system extensions
are constructed by developers and meter fees are not paid by the developer, the
water meter(s) shall be furnished by the developer and shall be of a
manufacture and type approved by the municipality or utility authority. The
meter(s) shall read in volume units as determined by the municipality or
utility authority. Where meter fees are paid by the developer, the meter(s)
shall be furnished by the municipality or utility authority.
(i) Pipe size shall comply with the following
requirements:
1. Water mains shall be a
minimum diameter of eight inches except at the end of a permanent cul-de-sac,
unless another size is required for fire flow and other criteria. A six-inch
main may be used when it serves not more than 20 dwelling units and only one
fire hydrant.
2. Building service
connection pipe shall be a minimum diameter of three-quarter inch.
3. Design capacity of water mains shall be
such as to maintain a minimum pressure of 20 pounds per square inch (psi) at
street level under all flow conditions.
(j) Pipe materials used in the construction
of water mains shall be cement-lined ductile iron, prestressed concrete
cylinder pipe, reinforced concrete pressure pipe, or PVC pipe. All pipe and
appurtenances shall comply with the applicable AWWA standards in effect at the
time of application. All standards referenced in this section are incorporated
herein by reference.
1. Ductile iron pipe,
appurtenances, and fittings shall comply with ANSI/AWWA C110/A21.10 (fittings),
C111/A21.11 (gasket joints), C115/A21.15 (flanged joints), and C151/A21.51
(pipe). Thickness shall be designed in accordance with ANSI/AWWA C150/A21.50.
It shall be cement-mortar lined in accordance with ANSI/AWWA C104/A21.4. Joints
shall be gasketed push-on joints or mechanical joints in conformance with
ANSI/AWWA C111/A21.11. The exterior of the ductile iron pipe shall be covered
with an asphaltic epoxy-type coating. In aggressive soils, ductile iron pipe
wrapped in polyethylene in accordance with ANSI/AWWA C105/A21.5 shall be
used.
2. Prestressed concrete
cylinder pipe with rubber and steel joints shall conform to ANSI/AWWA C301;
reinforced concrete pressure pipe (steel cylinder type) shall meet ANSI/AWWA
C300; concrete pressure pipe (bar wrapped steel cylinder type) shall meet
ANSI/AWWA C303.
3. PVC pipe,
appurtenances, and fittings shall conform to ANSI/AWWA C900 or AWWA C909 for
pipe sizes four inches to 12 inches and shall conform to AWWA C905 for sizes 14
inches through 36 inches. Joints shall be elastomeric-gasket couplings of a
corresponding size. Laboratory performance requirements, as specified in ASTM
D3139, shall be met. Solvent-cement couplings shall not be permitted. PVC pipe
installations shall be provided with a metallic locator tape.
4. Where transitions to flanged fittings are
made, adapters approved by the municipality or water purveyor shall be
used.
5. Building service
connection pipe shall be type K copper or polyethylene (PE) pressure pipe that
complies with ANSI/AWWA C901.
(k) Pipe bedding and backfill shall be
installed in accordance with the pipe manufacturer's recommendations.
1. The municipality or the authority may
require the developer to provide an opinion of a professional engineer relative
to the suitability of the on-site material to be used as backfill. The
municipality or authority shall rely on this opinion.
2. Where the on-site material is deemed
suitable, the opinion shall specify the appropriate installation methods for
the material. Where the on-site material is deemed not suitable, the opinion
shall specify modification or replacement of the material and the appropriate
installation for the specified material.
Notes
See: 31 N.J.R. 477(a), 31 N.J.R. 3259(a).
Inserted a new (e); recodified former (e) through (j) as (f) through (k); in the new (f), added a third sentence; in the new (h), substituted a reference to volume in units for a reference to gallons and cubic feet; and rewrote the new (j).
Amended by R.2000 d.480, effective
See: 32 N.J.R. 2670(b), 32 N.J.R. 4277(a).
In (d), substituted "one-fifth" for "one-quarter" in the first sentence and added "when required by the municipality" in the second sentence; in (g), rewrote 1 and deleted 2; and in (j)3 inserted reference to AWWA C909.
Amended by R.2005 d.56, effective
See: 36 N.J.R. 4025(a), 37 N.J.R. 481(c).
In (b), amended the table and N.J.A.C. references.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.