N.J. Admin. Code § 7:10-10.3 - Approved physical connection installation requirements
(a) An approved
physical connection installation shall be either a double check valve assembly
or a reduced pressure zone backflow preventer assembly, as defined at
N.J.A.C.
7:10-1.3, designed and constructed in
accordance with the requirements of this subchapter.
(b) The approved physical connection
installation shall be a reduced pressure zone backflow preventer assembly when
the unapproved water supply is a non-potable water source or a source in which
contaminant levels measured pursuant to the State primary drinking water
regulations at N.J.A.C. 7:10-5 exceed the maximum contaminant levels specified
therein.
(c) The requirements of
(b) above shall not apply to any physical connection installation operated
under a current physical connection permit issued before November 18, 1996
until such time as the existing physical connection is replaced or
modified.
(d) Each backflow
prevention device used in an approved physical connection installation shall be
constructed as follows:
1. For devices up to
and including two inches in diameter, the double check valve assembly or the
reduced pressure zone backflow preventer assembly shall be of durable,
non-toxic plastic, or of all stainless steel, all bronze, or all brass
construction;
2. For devices larger
than two inches in diameter, the double check valve assembly or the reduced
pressure zone backflow preventer assembly shall be constructed as described in
(d)1 above or shall be constructed of cast iron or steel, lined with brass,
bronze, epoxy resin, stainless steel, or other durable nontoxic, non-corrodible
material acceptable to the Department;
3. The clappers, discs or poppets, hinges,
bushings, and seatings of the check valve assemblies in any device used for an
approved physical connection installation shall be constructed of brass,
bronze, stainless steel or non-toxic plastic, and shall be so designed and
installed as to be readily replaceable;
4. Facing rings of the clappers, poppets or
discs, or differential relief valves shall be composed of durable molded
natural rubber, synthetic rubber or neoprene, shall be of even thickness,
smoothfaced, water-absorption resistant and shall provide a positive seal
against the backflow of water through the device;
5. Every double check valve assembly and
reduced pressure zone backflow preventer assembly shall have test cocks
installed to facilitate the pressure testing required pursuant to
N.J.A.C.
7:10-10.6;
6. Every backflow prevention device up to two
inches in diameter shall be installed with full port ball type shutoff valves.
For backflow prevention devices that are larger than two inches in diameter,
shutoff valves of the ball valve type are recommended; and
6. Every backflow prevention device up to two
inches in diameter shall be installed with full port ball type shutoff valves.
For backflow prevention devices that are larger than two inches in diameter,
shutoff valves of the ball valve type are recommended. Strainers installed
upstream of the leading shutoff valve are recommended for all backflow
prevention devices regardless of sizes; and
7. The pipe conveying water from the
differential relief port of a reduced pressure zone backflow preventer assembly
shall allow an air gap between the assembly and the drain pipe, and the pipe
shall be of the same diameter as, or larger than, the relief
port.
(e) All approved
physical connection installations shall meet the following operating
conditions:
1. The turbulence in the backflow
prevention device shall not be excessive for flow rates up to the rated flow so
as not to interfere with proper operation of the device;
2. All moving parts shall be designed to
operate up to the rated flow in a positive manner without chatter;
3. The backflow prevention device shall not
cause water hammer, nor be adversely affected by water hammer arising from an
outside condition; and
4. The
backflow prevention device shall not permit leakage in a direction reverse to
normal water flow.
(f)
In addition to the operating conditions set forth at (e) above, all double
check valve assemblies shall, under normal flow conditions, operate so that the
independently operating check valves remain closed until there is a demand for
water. Each of the check valves in series must maintain a minimum of one psi
pressure differential in the direction of flow. If, at any time, pressure
downstream of the device increases to within one psi of supply pressure, both
check valves must close to prevent backflow.
(g) In addition to the operating conditions
set forth at (e) above, all reduced pressure zone backflow preventer assemblies
shall, under normal flow conditions, operate so that both check valves are open
and the pressure area between the check valves, called the zone, is at least
five psi lower than the supply pressure. The relief valve, within the zone, is
held shut by supply pressure acting through an internal sensing passage on the
relief valve diaphragm. The first check valve in the line of flow must maintain
a minimum pressure differential of five psi and the second check valve in the
line of flow must maintain a minimum pressure differential of one psi. If the
first or second check valve becomes fouled, the pressure in the zone will
increase causing the relief valve in the zone to open automatically and
discharge to the atmosphere in order to maintain a pressure in the zone which
is at least two psi lower than the supply pressure, thus preventing
backflow.
Notes
See: 31 N.J.R. 2717(b), 32 N.J.R. 3106(a).
Rewrote (b); and in (d)6, added a third sentence.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.