N.Y. Comp. Codes R. & Regs. Tit. 12 § 38.25 - Radiation symbol, signs, labels and control devices
(a) Standard radiation symbol. Unless
otherwise authorized by this Part (rule) or by the commissioner, the symbol
prescribed by this section shall use the colors magenta, purple, or black on
yellow background. The symbol prescribed is the three-bladed design and shall
be as illustrated below:
Image
(1) Cross-hatched area is to be magenta,
purple, or black.
(2) The
background is to be yellow.
(3)
Exception to color requirements for standard radiation symbol. Notwithstanding
the requirements of this subdivision, licensees or registrants are authorized
to label sources, source holders, or device components containing sources of
radiation, and which are subjected to high temperatures, with conspicuously
etched or stamped radiation caution symbols and without a color
requirement.
(4) Additional
information on signs and labels. In addition to the contents of signs and
labels prescribed in this Part, the licensee or registrant shall provide, on or
near the required signs and labels, additional information, as appropriate, to
make individuals aware of potential radiation exposures and to minimize the
exposures.
(b)
(1) Posting requirements.
(i) Posting of radiation areas. The licensee
or registrant shall post each radiation area with a conspicuous sign or signs
bearing the radiation symbol and the words "CAUTION, RADIATION AREA".
(ii) Posting of high radiation areas. The
licensee or registrant shall post each high radiation area with a conspicuous
sign or signs bearing the radiation symbol and the words " CAUTION, HIGH
RADIATION AREA" or "DANGER, HIGH RADIATION AREA".
(iii) Posting of very high radiation areas.
The licensee or registrant shall post each very high radiation area with a
conspicuous sign or signs bearing the radiation symbol and words "GRAVE DANGER,
VERY HIGH RADIATION AREA".
(iv)
Posting of airborne radioactivity areas. The licensee or registrant shall post
each airborne radioactivity area with a conspicuous sign or signs bearing the
radiation symbol and the words "CAUTION, AIRBORNE RADIOACTIVITY AREA" or
"DANGER, AIRBORNE RADIOACTIVITY AREA".
(v) Posting of areas or rooms in which
licensed or registered material is used or stored. The licensee or registrant
shall post each area or room in which there is used or stored an amount of
licensed or registered material exceeding 10 times the quantity of such
material specified in Table 4 of section
38.41 of this Part (rule) with a
conspicuous sign or signs bearing the radiation symbol and the words "CAUTION,
RADIOACTIVE MATERIAL(S)" or "DANGER, RADIOACTIVE MATERIAL(S)".
(2) Exceptions to posting
requirements.
(i) A licensee or registrant is
not required to post caution signs in areas or rooms containing sources of
radiation for periods of less than eight hours, if each of the following
conditions is met:
(a) the sources of
radiation are constantly attended during these periods by an individual who
takes the precautions necessary to prevent the exposure of individuals to
sources of radiation in excess of the limits established in this Part (rule);
and
(b) the area or room is subject
to the licensee's or registrant's control.
(ii) A room or area is not required to be
posted with a caution sign because of the presence of a sealed source provided
the radiation level at 30 centimeters from the surface of the sealed source
container or housing does not exceed 0.05 mSv (0.005 rem) per hour.
(c) Labeling containers
and radiation machines.
(1) The licensee or
registrant shall ensure that each container of licensed or registered material
bears a durable, clearly visible label bearing the radiation symbol and the
words "CAUTION, RADIOACTIVE MATERIAL"or "DANGER, RADIOACTIVE MATERIAL". The
label shall also provide information, such as the radionuclides present, an
estimate of the quantity of radioactivity, the date for which the activity is
estimated, radiation levels, kinds of materials, and mass enrichment,
sufficient to permit individuals handling or using containers, or working in
the vicinity of the containers, to take precautions to avoid or minimize
exposures.
(2) Each licensee shall,
prior to removal or disposal of empty uncontaminated containers to unrestricted
areas, remove or deface the radioactive material label or otherwise clearly
indicate that the container no longer contains radioactive materials.
(3) Each registrant shall ensure that each
radiation machine is labeled in a conspicuous manner which cautions individuals
that radiation is produced when it is energized.
(4) Exceptions to labeling requirements. A
licensee or registrant is not required to label:
(i) containers holding licensed material in
quantities less than the quantities listed in Table 4 of section
38.41 of this Part
(rule);
(ii) containers holding
licensed material in concentrations less than those specified in Appendix A-13,
Table III of section
38.41 of this Part
(rule);
(iii) for laboratory
containers, such as beakers, flasks, and test tubes, used transiently in
laboratory procedures (i.e. for a period of a few hours) in the presence of an
authorized user;
(iv) containers
holding licensed material when they are in transport and packaged and labeled
in accordance with the regulations of the U.S. Department of Transportation for
radioactive material;
(v)
containers that are accessible only to individuals authorized to handle or use
them, or to work in the vicinity of the containers, if the contents are
identified to these individuals by a readily available written record. Examples
of containers of this type are containers in locations such as water-filled
canals, storage vaults, or hotcells. The record shall be retained as long as
the containers are in use for the purpose indicated on the record; or
(vi) installed manufacturing or process
equipment, such as chemical process equipment, piping, and tanks.
(d) Control of access
to high radiation areas.
(1) The licensee or
registrant shall ensure that each entrance or access point to a high radiation
area has one or more of the following features:
(i) a control device that, upon entry into
the area, causes the level of radiation to be reduced below that level at which
an individual might receive a deep dose equivalent of 1 mSv (0.1 rem) in one
hour at 30 centimeters from the source of radiation or from any surface that
the radiation penetrates;
(ii) a
control device that energizes a conspicuous visible or audible alarm signal so
that the individual entering the high radiation area, and the supervisor of the
activity, are made aware of the entry; or
(iii) entryways that are locked, except
during periods when access to the areas is required, with positive control over
each individual entry.
(2) In place of the controls required by
paragraph (1) of this subdivision, the licensee or registrant may substitute
continuous direct or electronic surveillance that is capable of preventing
unauthorized entry.
(3) The
licensee or registrant may use alternative methods for controlling access to
high radiation areas if they are approved by the commissioner as effective at
accomplishing such control.
(4) The
licensee or registrant shall establish the controls required by paragraphs (1)
and (3) of this subdivision in a way that does not prevent individuals from
leaving a high radiation area.
(5)
The licensee or registrant is not required to control each entrance or access
point to a room or other area that is a high radiation area solely because of
the presence of radioactive materials prepared for transport and packaged and
labeled in accordance with the regulations of the U.S. Department of
Transportation for radioactive material, provided that:
(i) the packages do not remain in the area
longer than three days; and
(ii)
the dose rate at one meter from the external surface of any package does not
exceed 0.1 mSv (0.01 rem) per hour.
(e) Control of access to very high radiation
areas. In addition to the requirements in subdivision (d) of this section, the
licensee or registrant shall institute additional measures to ensure that an
individual is not able to gain unauthorized or inadvertent access to areas in
which radiation levels could be encountered at 5 Gy (500 rad) or more in one
hour at one meter from a source of radiation or any surface through which the
radiation penetrates. This requirement does not apply to radiation sources
subject to subdivision (f) of this section.
(f) Control of access to very high radiation
areas--irradiators.
(1) This subdivision
applies to licensees or registrants with sources of radiation in
non-self-shielded irradiators. This subdivision does not apply to sources of
radiation that are used in industrial radiography, or in completely
self-shielded irradiators in which the source of radiation is both stored and
operated within the same shielding radiation barrier and, in the designed
configuration of the irradiator, is always physically inaccessible to any
individual and cannot create a radiation level of 5 Gy (500 rad) or more in one
hour at one meter in an area that is accessible to any individual.
(2) Each area in which there may exist
radiation levels in excess of 5 Gy (500 rad) in one hour at one meter from a
source of radiation that is used to irradiate materials shall meet the
following requirements:
(i) Each entrance or
access point shall be equipped with entry control devices which:
(a) function automatically to prevent any
individual from inadvertently entering a very high radiation area;
(b) permit deliberate entry into the area
only after a control device is actuated that causes the radiation level within
the area, from the source of radiation, to be reduced below that at which it
would be possible for an individual to receive a deep dose equivalent in excess
of 1 mSv (0.1 rem) in one hour; and
(c) when actuated, prevent operation of the
source of radiation if it would produce radiation levels in the area that could
result in a deep dose equivalent to an individual in excess of 1 mSv (0.1 rem)
in one hour.
(ii)
Additional control devices shall be provided so that, upon failure of the entry
control devices to function as required by subparagraph (i) of this paragraph:
(a) the radiation level within the area, from
the source of radiation, is reduced below that at which it would be possible
for an individual to receive a deep dose equivalent in excess of 1 mSv (0.1
rem) in one hour; and
(b)
conspicuous visible and audible alarm signals are generated to make an
individual attempting to enter the area aware of the hazard as well as at least
one other authorized individual, who is physically present, familiar with the
activity and prepared to render or summon assistance, aware of the failure of
the entry control devices.
(iii) The licensee or registrant shall
provide control devices so that, upon failure or removal of physical radiation
barriers other than the sealed source's shielded storage container:
(a) the radiation level from the source of
radiation is reduced below that at which it would be possible for an individual
to receive a deep dose equivalent in excess of 1 mSv (0.1 rem) in one hour;
and
(b) conspicuous visible and
audible alarm signals are generated to make potentially affected individuals
aware of the hazard; as well as to make the licensee or registrant or at least
one other individual, who is familiar with the activity and prepared to render
or summon assistance, aware of the failure or removal of the physical
barrier.
(iv) When the
shield for stored sealed sources is a liquid, the licensee or registrant shall
provide means to monitor the integrity of the shield and to signal,
automatically, loss of shielding to a level at which it would be possible for
an individual to receive a deep dose equivalent in excess of 1 mSv (0.1 rem) in
one hour.
(v) Physical radiation
barriers that comprise permanent structural components, such as walls, that
have no credible probability of failure or removal in ordinary circumstances
need not meet the requirements of subparagraphs (iii) and (iv) of this
paragraph.
(vi) Each area shall be
equipped with devices that will automatically generate conspicuous visible and
audible alarm signals to alert personnel in the area before the source of
radiation can be put into operation, and in time for any individual in the area
to operate a clearly identified control device which must be installed in the
area, and which will prevent the source of radiation from being put into
operation.
(vii) Each area shall be
controlled by use of such procedures and devices as are necessary to ensure
that the area is cleared of personnel prior to each use of the source of
radiation.
(viii) Prior to the
first individual's entry into each very high radiation area after any use of
the source of radiation, the area shall be checked by a radiation measurement.
The area may not be used unless the radiation level from the source of
radiation in the area is below that at which it would be possible for an
individual to receive a deep dose equivalent in excess of 1 mSv (0.1 rem) in
one hour.
(ix) The entry control
devices required in subparagraph (i) of this paragraph shall have been tested
for proper functioning as follows:
(a)
testing shall be conducted prior to initial operation with the source of
radiation on any day, unless operations were continued uninterrupted from the
previous day;
(b) testing shall be
conducted prior to resumption of operation of the source of radiation after any
unintentional interruption; and
(c)
the licensee or registrant shall submit and adhere to a schedule for periodic
tests of the entry control and warning systems.
(x) The licensee or registrant shall not
conduct operations, other than those necessary to place the source of radiation
in safe condition or to effect repairs on controls, unless control devices are
functioning properly.
(xi) Entry
and exit portals that are used in transporting materials to and from the
irradiation area, and that are not intended for use by individuals, shall be
controlled by such procedures and devices as are necessary to physically
protect and warn against inadvertent entry by any individual through these
portals. Exit portals for irradiated materials shall be equipped to detect and
signal the presence of any loose radioactive material that is carried toward
such an exit and to automatically prevent loose radioactive material from being
carried out of the area.
(3) Licensees, registrants, or applicants for
licenses or registrations for sources of radiation within the purview of this
subdivision which will be used in a variety of positions or in locations, such
as open fields or forests, that make it impracticable to comply with certain
requirements of paragraph (2) of this subdivision, such as those for the
automatic control of radiation levels, may apply to the commissioner for
approval of alternative safety measures. Alternative safety measures shall
provide personnel protection at least equivalent to those specified in
paragraph (2) of this subdivision. At least one of the alternative measures
shall include an entry-preventing interlock control based on a measurement of
the radiation present that ensures the absence of high radiation levels before
an individual can gain access to the area where such sources of radiation are
used.
(4) The entry control devices
required by paragraphs (2) and (3) of this subdivision shall be established in
such a way that no individual will be prevented from leaving the
area.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.