N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 45-4.3 - Special requirements
(a)
Exits. At least two exits remote from each other shall be provided from each
floor, tier, room or balcony in a building or structure to which this Subpart
applies. No exit shall be less than 18 inches wide.
(b) Exit signs.
(1) Location. Low level exit signs visible
from the approach to the exits, shall be provided at each exit doorway from the
building or structure. The bottom of the low level exit signs shall not be less
than six inches nor more than eight inches above the floor.
(2) Illumination. Such signs shall be
illuminated either externally or internally by artificial light and shall be
kept illuminated at all times when the building is occupied.
(3) Legend requirements. Each low level exit
sign shall be worded in plainly legible block letters, at least six inches high
with three-quarter inch strokes, with the word EXIT.
(c) Exit directional signs and exit path
marking.
(1) Location. Exit directional signs
shall be provided at locations in hallways, passageways, corridors, aisles and
at all other locations from which exit doorways are not readily discernible.
Low level exit path marking shall be allowed in lieu of exit directional
signs.
(2) Illumination. Such signs
or exit path marking shall not normally be illuminated; however, in the event
of activation of the emergency lighting system required by subdivision (d) of
this section, these signs or exit path marking shall be illuminated by this
system.
(3) Legend requirements.
Exit directional signs shall be worded as in paragraph (b)(3) of this section
with a suitable pointer or arrow indicating the direction of exit.
(4) Low level exit path marking placement.
The low level exit path marking shall be located at floor level or no more than
eight inches above the floor level on or near the exit path.
(d) Emergency lighting. Each
building or structure shall be equipped with an emergency lighting system
conforming to the requirements of Part 1032, of Title 9 NYCRR "Emergency Power
and Lighting," of the New York State Uniform Fire Prevention and Building Code,
effective January 1, 1984. In addition, the emergency lighting system shall be
automatically activated by the operation of the fire and smoke detection system
required under subdivision (e) of this section.
(e) Fire and smoke detection system. Each
building or structure shall be equipped with a fire and smoke detecting system
conforming to the requirements of section 1060.3, Part 1060, Title 9 NYCRR
"Fire- and Smoke-Detecting Systems," of the New York State Uniform Fire
Prevention and Building Code, effective November 15, 1985. In addition, this
system shall have the capability of activating the emergency lighting system
required by subdivision (d) of this section.
(f) Fire prevention and protection. Each
building or structure shall conform to the provisions of section
45-2.23 of this Part.
(g) Smoking prohibited. The carrying of
lighted cigars, cigarettes or pipes shall be prohibited in any building or
structure subject to the provisions of this Subpart. NO SMOKING signs shall be
posted at all entrances to such building or structure.
(h) Evacuation procedures. The owner shall
develop emergency evacuation procedures for each building or structure. Such
procedures shall be in writing and shall be available on site for review by the
commissioner or his authorized representative and any personnel assigned to the
operation of the building or structure. The owners shall also insure that all
personnel assigned to the operation of the building or structure are thoroughly
trained in the implementation of these evacuation procedures.