N.Y. Comp. Codes R. & Regs. Tit. 21 § 1950.7 - Water meters
(a) Water shall
be furnished to all users through metered services only, except as otherwise
provided in this Part.
(b) The
supply of water through separate service must be recorded by one meter only. If
additional meters are desired for recording the subdivision of such supply,
they must be furnished and set by the owners or users at their own expense.
Furthermore, the water board shall not be required to read such meters nor to
subdivide water bills in view of the existence of such subdividing
meters.
(c) All water meters
installed after August 1, 1988, including remote reading devices, shall be
purchased by the water board and shall remain the property of the water board.
All costs of inspection, testing and installation, where applicable, shall be
borne by the water board and shall be recovered through the establishment of
equitable rates and charges for water service.
(d) Water meters shall not be removed from
one service to another except by the water board. The water board reserves the
right to remove and replace any meter at the director's determination. Meters
shall be tested and repaired as necessary by the water board.
(e) Water meters less than two inches in size
shall be placed inside the basement wall or indoors whenever possible. When it
is necessary to install a water meter in any other location, a water control
structure of such size and construction as is approved by the director must be
provided and paid for by the owner of the property served thereby.
(f) Water meters less than two inches in size
shall be installed by the water board only, and the cost of such installation
shall be borne by the water board. A place must be provided by the owner where
such meters and remote reading devices will be protected from frost and other
damage and in readily accessible locations for reading, examination, repair and
removal. A brass "stop and waste" type valve must be provided just ahead of,
and on the supply side of the meter.
(g) Unless otherwise permitted by the
director, meters of two-inch size or larger must be placed inside a building or
in a water control structure of such design and dimensions, and at such a
location, as is approved by the director. Meter assemblies must be protected
from frost and other damage, and be readily accessible for reading,
examination, testing, repair and removal. The property owner is responsible for
the construction or modification of all required structures, piping, and
appurtenances, including the provision of approved backflow prevention,
required by the water board. The water meter shall be provided by the water
board and shall remain the property of the water board.
(h) Installation or replacement of water
meters two inches in size or larger shall be performed at the water board's
option, either by the water board at real cost to the property owner, or by the
property owner or his contractor subject to all requirements of the water
board.
(i) All water meters two
inches in size or larger must be provided with a suitable by-pass of such size
as will provide a continuous supply of water during such time as the water
meter is undergoing repairs, testing or replacement. The property owner shall
be billed for meter testing with the first water bill rendered after the date
of such test.
(j) A suitable check
and relief valve may be required by the director in the service pipe after the
meter, at the property owner's expense, when there is a possibility of hot
water backing up into the water meter.
(k) Each application for a water or fire
service which is two inches in size or larger must be accompanied by five
copies of a detailed dimensional plan, drawn to scale, and acceptable to the
director, which must show the exact manner of installation of the service,
including an acceptable backflow prevention device, and the water meter, if
applicable.
(l) The director is
hereby authorized to make such determinations or interpretations of these
regulations and specifications regarding the installation of water meters as
are deemed necessary by the director. Prints of the standard type of water
control structure installations and by-passes acceptable to the water board are
available upon request.
(m) Whenever
a service is to interconnect in any manner with any other supply of water, a
separate detail of such interconnection must be clearly shown. Such
interconnection must comply with requirements of the State Department of Health
Sanitary Code. The application for any interconnected service as heretofore
described shall not be granted nor any connection made to any water main until
the plan of installation has been approved by the director, the Niagara County
Health Department, and the State Department of Health.
(n) All water meters and by-pass valves shall
be sealed by the water board when they are placed in service. Such seals shall
not be removed except by the water board unless permission is first obtained in
writing from the director. If a broken seal is discovered by the water board,
for which permission was not obtained, a violation of this Part will be
presumed, resulting in appropriate enforcement action by the water board in
accordance with this Part.
(o) It
shall be the duty of the property owner to report to the water board any broken
or missing seals, including meter seals. If the director determines that the
seal was broken accidentally, then the water board shall set a new seal,
without charge or other enforcement action.
(p) The water board reserves the right to
enter, at any reasonable time, and with reasonable notice, any premises where a
water meter is installed, for the purpose of testing, examining, repairing,
removing, replacing or modifying such meter and its appurtenances when, in the
opinion of the director, such action is necessary.
(q) The water board shall repair, without
cost to the property owner, any water board-owned water meter located on a
water service within the city corporate limits, provided that such meter has
not been damaged by freezing, hot water or other act or omission by the
property owner. If the property owner or his agent, employees, or tenants are
determined to be responsible for damages by the director, then the real cost of
repairing or replacing the water meter and/or remote reading device shall be
borne by said property owner.
(r)
Water meters may be tested by the water board periodically. The costs of all
such testing shall be borne by the water board.
(s) A meter may be tested at the request of a
property owner without charge if the test reveals that the meter is not within
the limits of accuracy as determined by the director. The director may rely
upon the standards of the American Water Works Association or such other
similar standards as he or she deems appropriate. For a water meter less than
two inches in size, a small meter testing fee as identified in the board
schedule of rates will be charged if the meter is found to be within the limits
of accuracy. For meters two inches in size or larger, the real cost of
requested testing shall be paid by the property owner.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.