13 N.C. Admin. Code 13 .0412 - EXPANSION TANKS
(a) Hot water
heating systems shall allow for thermal expansion and contraction of the piping
to prevent excessive stress from being introduced into the pipe or connected
equipment.
(b) When new equipment
is installed and a backflow prevention system is installed or already exists on
a potable water supply line for a hot water supply boiler or water heater,
expansion tanks shall be installed. For water heaters, backflow preventers or
check valves may be installed at the meter in water systems.
(c) When expansion tanks are used they shall
be constructed and stamped in accordance with the requirements of this Chapter
for pressure vessels, unless exempted due to the vessel size or operating
limits.
(d) For a closed type
system the expansion tank shall be not less than that determined as follows:
Vt = [(0.00041T - 0.0466)Vs]/[(Pa/Pf) - (Pa/Po)] where:
Vt = minimum volume of tank(s), gal
Vs = volume of system, not including tanks, gal
T = average operating temperature, deg F
Pa = atmospheric pressure, psi
Pf = fill pressure, psi
Po = maximum operating pressure, psi.
Notes
Eff. May 29, 1981;
Recodified from 13 NCAC 13 .0410 Eff. January 1, 1995;
Amended Eff. July 1, 2011; January 1, 2009; January 1, 1995;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 22, 2018.
Eff. May 29, 1981;
Recodified from 13 NCAC 13 .0410 Eff. January 1, 1995;
Amended Eff. July 1, 2011; January 1, 2009; January 1, 1995.