21 N.C. Admin. Code 18B .0805 - EXEMPTION OF CERTAIN LOW VOLTAGE WIRING SYSTEMS
Exemption. Except a fire alarm, burglar alarm or low voltage wiring system as defined in Rule .0804, the installation, maintenance, or repair of low voltage wiring systems may be performed by those not licensed by the Board if all of the following conditions are met:
(1) the system is not required by the N.C.
State Building Code;
(2) the low
voltage control circuit and power supply is a Class II or Class III system as
defined in the National Electrical Code other than that described in Rule
.0804;
(3) the system operates at a
voltage not in excess of 50 volts or meets the provisions for sound-recording
and similar equipment in the National Electrical Code;
(4) no part of the system is installed in an
area considered as hazardous under the National Electrical Code;
(5) the system is current limited or
protected by a circuit breaker, fuse, or other current limiting device;
and
(6) a failure in the system
would not, in the opinion of the electrical inspector having jurisdiction,
create a shock or fire hazard to persons or property.