Ohio Admin. Code 1301:3-4-02 - Attendance at operation of historical boilers, proper use and maintenance, and logbook
(A) A historical boiler shall not be left
unattended when in operation and members of the
public are present
in places open to the
public
. For purposes of this chapter, a traction engine may be considered
as not being in operation when all of the following conditions exist:
(1) The water level is at least one-third of
the water gage glass;
(2) The
header or dome valve is in a closed position, if applicable;
(3) The draft doors are closed;
(4) The fire is banked or extinguished;
and
(5) The boiler pressure is at least twenty
pounds per square inch below the safety valve relieving pressure.
(B) All piping components shall be
used in the manner for which they were designed and shall not exceed
the manufacturer's marked rating. Below the water
line, schedule eighty black pipe shall be used from the boiler to the first
valve.
(C) The owner of each
historical boiler shall keep and maintain a maintenance logbook,
which shall be furnished, upon request, to the inspector. The logbook shall
include, but not be limited to, the following information:
(1) Boiler information, including,
:
(a) The number and location of a boiler
serial number, identification number, or other
permanent marking on the boiler sufficient to identify the boiler with
specificity;
(b) The number and
location of a safety valve serial number, identification number,
or other permanent marking on the safety valve sufficient to identify the set
pressure and capacity of the safety valve;
(c) The heating surface of the boiler shall
be as reported in the manufacturer's specifications or shall be calculated by a
method acceptable to the inspector;
(2) Inspection dates and findings;
(3) Events and dates attended by the general
public where the boiler was operated;
(4) Failures;
(5) Repairs; and
(6) Performed maintenance, including, but not
limited to, the replacement of a fusible plug or a safety valve.
(D) No historical boiler and its
appurtenances shall be operated at a pressure in excess of the safe working
pressure for the boiler as stated on the
certificate of operation for that boiler issued pursuant to section
4104.36 of the Revised
Code.