Ohio Admin. Code 1301:3-5-04 - Notification of unsafe working condition; requirements for cover removal; notification of accident
(A) If, in the course of any inspection, an
inspector finds that the boiler or pressure vessel is not in safe working
condition, is not provided with the fittings necessary for safety, or that the
fittings are improperly arranged, the inspector shall immediately notify the
superintendent, the owner or user, and the person in charge of the boiler or
pressure vessel of the inspector's finding. The
superintendent may deny, revoke, or refuse to
renew the certificate of operation of any boiler or pressure vessel that is
found to not be in safe working condition, and
the owner or user shall not operate the boiler or pressure vessel, or permit it to be operated until a certificate
of operation has been issued or renewed
granted or restored.
(B) If an inspector determines upon an
external or internal inspection that a boiler or pressure vessel has a leak or
crack, the inspector may require that a sufficient amount of the covering of
the boiler or pressure vessel be removed in order to inspect the boiler or
pressure vessel to determine its safety. When an inspector requires that the
covering of a boiler or pressure vessel be removed after having determined that
a boiler or pressure vessel has a leak or crack,
the boiler or pressure vessel shall not be operated until the boiler or
pressure vessel has successfully
completed
passed an inspection by an
inspector holding a certificate of competency held
in accordance with Chapter 4104. of the Revised Code.
(C) In the event that an accident occurs
affecting the safety of a boiler or pressure vessel and which
that serves
to render the boiler or pressure vessel inoperable, the owner or user shall
immediately notify the superintendent and submit a detailed report of the
accident. In the case of a serious accident, such as an explosion or other
accident causing personal injury, the owner or user shall immediately notify
the division's boiler section chief by telephone, electronic mail, or other
means of immediate communication, with receipt confirmed, and except as
necessary to protect human life or to facilitate emergency response, the boiler
or pressure vessel and any of its parts shall not be removed or disturbed
before an examination has been made by an inspector of the division of
industrial compliance.
Notes
Promulgated Under: 119.03
Statutory Authority: 4104.06
Rule Amplifies: 4104.06, 4104.15, 4104.16
Prior Effective Dates: 10/13/2005, 11/07/2014, 02/07/2020
Promulgated Under: 119.03
Statutory Authority: 4104.06
Rule Amplifies: 4104.06, 4104.15, 4104.16
Prior Effective Dates: 10/13/2005, 11/07/2014
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
(A) If, in the course of any inspection, an inspector finds that the boiler or pressure vessel is not in safe working condition, is not provided with the fittings necessary for safety, or that the fittings are improperly arranged, the inspector shall immediately notify the superintendent , the owner or user, and the person in charge of the boiler or pressure vessel of the inspector 's finding. The superintendent may deny, revoke, or refuse to renew the certificate of operation of any boiler or pressure vessel that is found to not be in safe working condition, and the owner or user shall not operate the boiler or pressure vessel, or permit it to be operated until a certificate of operation has been issued or renewed granted or restored.
(B) If an inspector determines upon an external or internal inspection that a boiler or pressure vessel has a leak or crack, the inspector may require that a sufficient amount of the covering of the boiler or pressure vessel be removed in order to inspect the boiler or pressure vessel to determine its safety. When an inspector requires that the covering of a boiler or pressure vessel be removed after having determined that a boiler or pressure vessel has a leak or crack, the boiler or pressure vessel shall not be operated until the boiler or pressure vessel has successfully completed passed an inspection by an inspector holding a certificate of competency held in accordance with Chapter 4104. of the Revised Code.
(C) In the event that an accident occurs affecting the safety of a boiler or pressure vessel and which that serves to render the boiler or pressure vessel inoperable, the owner or user shall immediately notify the superintendent and submit a detailed report of the accident. In the case of a serious accident, such as an explosion or other accident causing personal injury, the owner or user shall immediately notify the division 's boiler section chief by telephone, electronic mail, or other means of immediate communication, with receipt confirmed, and except as necessary to protect human life or to facilitate emergency response, the boiler or pressure vessel and any of its parts shall not be removed or disturbed before an examination has been made by an inspector of the division of industrial compliance .