(1)
902.1 Definitions. The following terms are
defined in rule
1301:7-7-02 of the
Administrative Code.
"Alarm notification
appliance."
"Alarm
signal."
"Alarm verification
feature."
"Annunciator."
"Audible alarm notification
appliance."
"Automatic."
"Automatic fire-extinguishing
system."
"Automatic smoke detection
system."
"Automatic sprinkler
system."
"Automatic water mist
system."
"Average ambient sound
level."
"Carbon dioxide extinguishing
system."
"Clean
agent."
"Commercial motor
vehicle."
"Constantly attended
location."
"Deluge
system."
"Detector,
heat."
"Dry-chemical extinguishing
agent."
"Elevator
group."
"Emergency alarm
system."
"Emergency voice/alarm
communications."
"Fire alarm box,
manual."
"Fire alarm system."
"Fire area."
"Fire detector,
automatic."
"Fire protection
system."
"Fire safety
functions."
"Fixed base operator
(FBO)."
"Foam-extinguishing
system."
"Halogenated extinguishing
system."
"Impairment
coordinator."
"Initiating
device."
"Manual fire alarm
box."
"Multiple-station alarm
device."
"Multiple-station smoke
alarm."
"Notification
zone."
"Nuisance
alarm."
"Private
garage."
"Record
drawings."
"Single-station smoke
alarm."
"Sleeping
unit."
"Smoke
alarm."
"Smoke
detector."
"Standpipe system, classes
of."
"Class I
system."
"Class II
system."
"Class III system."
"Standpipes, types of."
"Automatic dry."
"Automatic wet."
"Manual dry."
"Manual wet."
"Semiautomatic
dry."
"Supervising
station."
"Supervisory
service."
"Supervisory
signal."
"Supervisory signal-initiating
device."
"Tires, bulk storage
of."
"Transient
aircraft."
"Trouble
signal."
"Visible alarm notification
appliance."
"Wet-chemical extinguishing
agent."
"Wireless protection
system."
"Zone."
"Zone,
notification."
(2)
903.2 Where
required.
Approved automatic sprinkler
systems in new buildings and structures shall be provided in the locations
where required by the building code as listed in rule
1301:7-7-80
of the Administrative Code and as described in this paragraph.
The requirements for automatic sprinkler systems in new buildings contained in
this rule are subject to and do not supersede or otherwise conflict with the
requirements of paragraph (D)(2)(a)(104.2.1) of rule
1301:7-7-01
of the Administrative Code.
Exception:
Spaces or areas in telecommunications buildings used
exclusively for telecommunications equipment, associated electrical power
distribution equipment, batteries and standby engines, provided those spaces or
areas are equipped throughout with an automatic smoke detection system in
accordance with paragraph (G)(2)( 907.2) of this
rule and are separated from the remainder of the building by not less
than 1-hour fire barriers constructed in accordance with section 707 of the
building code as listed in rule
1301:7-7-80
of the Administrative Code or not less than 2-hour horizontal
assemblies constructed in accordance with section 711 of the building
code as listed in rule
1301:7-7-80
of the Administrative Code, or both.
(a)
903.2.1
Group A. An automatic sprinkler system shall be provided throughout
buildings and portions thereof used as Group A occupancies as provided in this
paragraph. For Group A-1, A-2, A-3 and A-4 occupancies, the
automatic sprinkler system shall be provided throughout the story where the
fire area containing the Group A-1, A-2, A-3 or A-4 occupancy is located, and
throughout all stories from the Group A occupancy to, and including, the levels
of exit discharge serving the Group A occupancy. For Group A-5 occupancies, the
automatic sprinkler system shall be provided in the spaces indicated in
paragraph (C)(2)(a)(iv)(903.2.1.5) of this
rule.
(i)
903.2.1.1 Group A-1. An automatic
sprinkler system shall be provided for fire areas containing Group A-1
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 12,000 square feet (1115
m2).
(b)
The fire area has
an occupant load of 300 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
(d)
The fire area contains a multi-theater
complex.
(ii)
903.2.1.2 Group A-2. An automatic
sprinkler system shall be provided for fire areas containing Group A-2
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 5,000 square feet (464
m2).
(b)
The fire area has
an occupant load of 100 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
(iii)
903.2.1.3 Group A-3. An automatic
sprinkler system shall be provided for fire areas containing Group A-3
occupancies and intervening floors of the building where one of the following
conditions exists:
(a)
The fire area exceeds 12,000 square feet (1115
m2).
Exception:
Fire areas used exclusively for religious worship services
with fixed seating.
(b)
The fire area has
an occupant load of 300 or more.
Exceptions:
1.
Fire areas
used primarily for worship with fixed seating.
2.
Fire areas
without fixed seating not used for exhibition or
display.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
Exception:
Areas used exclusively as participant sports areas where the
main floor area is located at the same level as the level of exit discharge of
the main entrance and exit.
(iv)
903.2.1.4
Group A-4. An automatic sprinkler system shall be provided for fire
areas containing Group A-4 occupancies and intervening floors of the building
where one of the following conditions exists:
(a)
The fire area
exceeds 12,000 square feet (1115
m2).
(b)
The fire area has
an occupant load of 300 or more.
(c)
The fire area is
located on a floor other than a level of exit discharge serving such
occupancies.
Exception:
Areas used exclusively as participant sport areas where the
main floor area is located at the same level as the level of exit discharge of
the main entrance and exit.
(v)
903.2.1.5
Group A-5. An automatic sprinkler system shall be provided for Group A-5
occupancies in the following areas: concession stands, retail areas, press
boxes and other accessory use areas in excess of 1,000 square feet (93
m2).
(vi)
903.2.1.6
Assembly occupancies on roofs. Where an occupied roof has an assembly
occupancy with an occupant load exceeding 100 for Group A-2 and 300 for other
Group A occupancies, all floors between the occupied roof and the level of exit
discharge shall be equipped with an automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) or
(C)(3)(a)(ii)(903.3.1.2) of this rule.
Exception:
Open parking garages of Type I or Type II
construction.
(vii)
903.2.1.7 Multiple fire areas. An
automatic sprinkler system shall be provided where multiple fire areas of Group
A-1, A-2, A-3 or A-4 occupancies share exit or exit access components and the
combined occupant load of these fire areas is 300 or more.
(b)
903.2.2 Ambulatory care facilities.
An automatic sprinkler system shall be installed
throughout the entire floor containing an ambulatory care facility where either
of the following conditions exist at any time:
(i)
Four or more care
recipients are incapable of self-preservation, whether rendered incapable by
staff or staff has accepted responsibility for care recipients already
incapable.
(ii)
One or more care recipients that are incapable of
self-preservation are located at other than the level of exit discharge serving
such facility.
In buildings where ambulatory care is
provided on levels other than the level of exit discharge, an automatic
sprinkler system shall be installed throughout the entire floor where such care
is provided as well as all floors below, and all floors between the level of
ambulatory care and the nearest level of exit discharge, including the level of
exit discharge.
(c)
903.2.3
Group E.
An automatic sprinkler system
shall be provided for Group E occupancies as follows:
(i)
Throughout all
Group E fire areas greater than 20,000 square feet
(1858 m2) in area.
(ii)
Throughout every
portion of educational buildings below the lowest level of exit discharge
serving that portion of the building.
Exception:
An automatic sprinkler system is not required in any
area below the lowest level of exit discharge serving that area where every
classroom throughout the building has not fewer than one exterior exit door at
ground level.
(iii)
Throughout every portion of Group E day care
facilities - 21/2 years or less of age.
Exception:
An automatic sprinkler system is not required in day care
facilities that provide care for more than five but no more than 100 children
21/2 years or less of age and the day care facilities are at the level of exit
discharge and where every room where care is provided has no fewer than one
exterior exit door for which the exit access and exit discharge do not require
the traversing of stairs.
(d)
903.2.4
Group F-1.
An automatic sprinkler system
shall be provided throughout all buildings containing a Group F-1 occupancy
where one of the following conditions exists:
1.
A Group F-1 fire
area exceeds 12,000 square feet (1115
m2).
2.
A Group F-1 fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group F-1 fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group F-1
occupancy used for the manufacture of upholstered furniture or mattresses
exceeds 2,500 square feet (232 m2).
(i)
903.2.4.1
Woodworking operations. An automatic sprinkler system shall be provided
throughout all Group F-1 occupancy fire areas that contain woodworking
operations in excess of 2,500 square feet in area (232
m2) that generate finely divided combustible waste
or use finely divided combustible materials.
(e)
903.2.5 Group H.
Automatic sprinkler systems shall be provided in high-hazard
occupancies as required in paragraphs (C)(2)(e)(i)(903.2.5.1)
to (C)(2)(e)(iii)(903.2.5.3) of this
rule.
(i)
903.2.5.1 General. An automatic sprinkler
system shall be installed in Group H occupancies.
(ii)
903.2.5.2
Group H-5 occupancies. An automatic sprinkler system shall be installed
throughout buildings containing Group H-5 occupancies. The design of the
sprinkler system shall be not less than that required under the
building code as listed in rule
1301:7-7-80
of the Administrative Code for the occupancy hazard classifications in
accordance with Table 903.2.5.2 of this rule.
Where the design area of the sprinkler
system consists of a corridor protected by one row of sprinklers, the maximum
number of sprinklers required to be calculated is 13.
Table
903.2.5.2
Group H-5 sprinkler design
criteria
Location
|
Occupancy hazard
classification
|
Fabrication areas
|
Ordinary hazard group
2
|
Service corridors
|
Ordinary hazard group
2
|
Storage rooms without
dispensing
|
Ordinary hazard group
2
|
Storage rooms with
dispensing
|
Extra hazard group
2
|
Corridors
|
Ordinary hazard group
2
|
(iii)
903.2.5.3 Pyroxylin plastics. An automatic
sprinkler system shall be provided in buildings, or portions thereof, where
cellulose nitrate film or pyroxylin plastics are manufactured, stored or
handled in quantities exceeding 100 pounds (45 kg).
(f)
903.2.6
Group I.
An automatic sprinkler system
shall be provided throughout buildings with a Group I fire area.
Exceptions:
1.
An automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of this rule shall be permitted in
Group I-1 Condition 1 facilities.
2.
An automatic
sprinkler system is not required where Group I-4 day care facilities are at the
level of exit discharge and where every room where care is provided has not
fewer than one exterior exit door.
3.
In buildings where
Group I-4 day care is provided on levels other than the level of exit
discharge, an automatic sprinkler system in accordance with
paragraph (C)(3)(a)(i)(903.3.1.1) of this
rule shall be installed on the entire floor where care is provided,
all floors between the level of care and the level of exit discharge and all
floors below the level of exit discharge other than areas classified as an open
parking garage.
4.
An automatic sprinkler system is not required
in day care facilities that provide care for more than five but no more than
100 children 21/2 years or less of age and the day care facilities are at the
level of exit discharge and where every room where care is provided has no
fewer than one exterior exit door for which the exit access and exit discharge
do not require the traversing of stairs.
(g)
903.2.7
Group M.
An automatic sprinkler system
shall be provided throughout buildings containing a Group M occupancy where one
of the following conditions exists:
1.
A Group M fire area exceeds 12,000 square feet (1115
m2).
2.
A Group M fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group M fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group M
occupancy used for the display and sale of upholstered furniture or mattresses
exceeds 5,000 square feet (464 m2).
(i)
903.2.7.1
High-piled storage. An automatic sprinkler system shall be provided as
required in rule
1301:7-7-32
of the Administrative Code in all buildings of Group M where storage
of merchandise is in high-piled or rack storage
arrays.
(h)
903.2.8
Group R. An automatic sprinkler system installed in accordance with
paragraph (C)(3)( 903.3) of this rule shall
be provided throughout all buildings with a Group R fire area.
Exception: Group
R-2.
An automatic
sprinkler system is not required in buildings of Group R-2 permitted to have a
single exit per section 1006.3.2 of the building code as listed in rule
1301:7-7-80
of the Administrative Code where:
1.
The
building is not used as an "SRO" occupancy as defined in rule
1301:7-7-02 of the
Administrative Code, and
2.
The exit
is constructed as an exterior stair per section 1027 of the building code as
listed in rule
1301:7-7-80
of the Administrative Code, and
3.
The
dwelling units egress directly into an exit, and,
4.
Two-hour
fire barriers divide the building into fire areas with a maximum of two
dwelling units per floor and not more than six dwelling units per fire area,
and
5.
All dwelling units in the fire area must have separations as
required by section 708.1 of the building code as listed in rule
1301:7-7-80
of the Administrative Code for dwelling units, and
6.
The
building is limited to a basement and two stories above grade plane,
and
7.
The building contains no more than four dwelling units
per floor and no more than twelve dwelling units per building.
(i)
903.2.8.1
Group R-3. An automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(iii)(903.3.1.3) of this
rule shall be permitted in Group R-3 occupancies.
(ii)
[F]
903.2.8.2 Group R-4 Condition 1. An automatic sprinkler system installed
in accordance with paragraph (C)(3)(a)(iii)(903.3.1.3)
of this rule shall be permitted in Group R-4 Condition 1
occupancies.
(iii)
[F] 903.2.8.3 Group R-4 Condition 2. An
automatic sprinkler system installed in accordance with
paragraph (C)(3)(a)(ii)(903.3.1.2) of this
rule shall be permitted in Group R-4 Condition 2 occupancies. Attics
shall be protected in accordance with paragraph
(C)(2)(g)(iii)(a)(903.2.8.3.1) or
(C)(2)(g)(iii)(b)(903.2.8.3.2) of this
rule.
(a)
[F] 903.2.8.3.1 Attics used for living purposes,
storage or fuel-fired equipment. Attics used for living purposes,
storage or fuel-fired equipment shall be protected throughout with an automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(ii)(903.3.1.2) of this rule.
(b)
[F]
903.2.8.3.2 Attics not used for living purposes, storage or fuel-fired
equipment.
Attics not used for living
purposes, storage or fuel-fired equipment shall be protected in accordance with
one of the following:
(i)
Attics protected throughout by a heat detector system
arranged to activate the building fire alarm system in accordance with
paragraph (G)(2)(j)(907.2.10) of this
rule.
(ii)
Attics constructed of noncombustible
materials.
(iii)
Attics constructed of fire-retardant-treated wood
framing complying with section 2303.2 of the building code as listed in
rule
1301:7-7-80
of the Administrative Code.
(iv)
The automatic
sprinkler system shall be extended to provide protection throughout the attic
space.
(iv)
903.2.8.4 Care facilities. An automatic
sprinkler system installed in accordance with paragraph
(C)(3)(a)(iii)(903.3.1.3) of this rule shall be permitted in
care facilities with five or fewer individuals in a single-family
dwelling.
(i)
903.2.9
Group S-1. An automatic sprinkler system shall be provided throughout
all buildings containing a Group S-1 occupancy where one of the following
conditions exists:
1.
A Group S-1 fire area exceeds 12,000 square feet (1115
m2).
2.
A Group S-1 fire
area is located more than three stories above grade plane.
3.
The combined area
of all Group S-1 fire areas on all floors, including any mezzanines, exceeds
24,000 square feet (2230 m2).
4.
A Group S-1 fire
area used for the storage of commercial motor vehicles where the fire area
exceeds 5,000 square feet (464 m2).
5.
A Group S-1
occupancy used for the storage of upholstered furniture or mattresses exceeds
2,500 square feet (232 m2).
(i)
903.2.9.1
Repair garages. An automatic sprinkler system shall be provided
throughout all buildings used as repair garages in accordance with section
406.8 of the building code as listed in rule
1301:7-7-80
of the Administrative Code, as shown:
(a)
Buildings having
two or more stories above grade plane, including basements, with a fire area
containing a repair garage exceeding 10,000 square feet (929
m2).
(b)
Buildings no more
than one story above grade plane, with a fire area containing a repair garage
exceeding 12,000 square feet (1115
m2).
(c)
Buildings with
repair garages servicing vehicles parked in basements.
(d)
A Group S-1 fire
area used for the repair of commercial motor vehicles where the fire area
exceeds 5,000 square feet (464
m2).
(ii)
903.2.9.2
Bulk storage of tires. Buildings and structures where the area for the
storage of tires exceeds 20,000 cubic feet (566 m3)
shall be equipped throughout with an automatic sprinkler system in accordance
with paragraph (C)(3)(a)(i)(903.3.1.1) of this
rule.
(j)
903.2.10
Group S-2 enclosed parking garages. An automatic sprinkler system shall
be provided throughout buildings classified as enclosed parking garages in
accordance with section 406.6 of the building code as listed in rule
1301:7-7-80
of the Administrative Code where either of the following conditions
exists.
1.
Where
the fire area of the enclosed parking garage exceeds 12,000 square feet (1115
m2).
2.
Where the enclosed
parking garage is located beneath other groups.
Exception:
Enclosed parking garages located beneath Group R-3
occupancies.
(i)
903.2.10.1 Commercial parking garages. An
automatic sprinkler system shall be provided throughout buildings used for
storage of commercial motor vehicles where the fire area exceeds 5,000 square
feet (464 m2).
(k)
903.2.11
Specific buildings areas and hazards. In all occupancies other than
Group U, an automatic sprinkler system shall be installed for building design
or hazards in the locations set forth in paragraphs
(C)(2)(k)(i)(903.2.11.1) to (C)(2)(k)(vi)(903.2.11.6)
of this rule.
(i)
903.2.11.1 Stories without openings. An
automatic sprinkler system shall be installed throughout all stories, including
basements, of all buildings where the floor area exceeds 1,500 square feet (
139.4 m2) and where there is not provided not fewer
than one of the following types of exterior wall openings:
1.
Openings below
grade that lead directly to ground level by an exterior stairway complying with
paragraph (K)(1011) of rule
1301:7-7-10 of
the Administrative Code or an outside ramp complying with
paragraph (L)(1012) of rule
1301:7-7-10 of
the Administrative Code. Openings shall be located in each 50 linear
feet (15 240 mm), or fraction thereof, of exterior wall in the story on at
least one side. The required openings shall be distributed such that the lineal
distance between adjacent openings does not exceed 50 feet (15 240
mm).
2.
Openings entirely above the adjoining ground level
totaling not less than 20 square feet ( 1.86 m2) in
each 50 linear feet (15 240 mm), or fraction thereof, of exterior wall in the
story on at least one side. The required openings shall be distributed such
that the lineal distance between adjacent openings does not exceed 50 feet (15
240 mm). The height of the bottom of the clear opening shall not exceed 44
inches (1118 mm) measured from the floor.
(a)
903.2.11.1.1 Opening dimensions and access.
Openings shall have a minimum dimension of not less
than 30 inches (762 mm). Such openings shall be accessible to the fire
department from the exterior and shall not be obstructed in a manner that
fire-fighting or rescue cannot be accomplished from the
exterior.
(b)
903.2.11.1.2 Openings on one side only.
Where openings in a story are provided on only one side
and the opposite wall of such story is more than 75 feet (22 860 mm) from such
openings, the story shall be equipped throughout with an approved automatic
sprinkler system or openings as specified above shall be provided on not fewer
than two sides of the story.
(c)
903.2.11.1.3 Basements.
Where any portion of a basement is located more than 75 feet
(22 860 mm) from openings required by paragraph
(C)(2)(k)(i)(903.2.11.1) of this rule, the basement shall be
equipped throughout with an approved automatic sprinkler
system.
(ii)
903.2.11.2
Rubbish and linen chutes. An automatic sprinkler system shall be
installed at the top of rubbish and linen chutes and in their terminal rooms.
Chutes shall have additional sprinkler heads installed at alternate floors and
at the lowest intake. Where a rubbish chute extends through a building more
than one floor below the lowest intake, the extension shall have sprinklers
installed that are recessed from the drop area of the chute and protected from
freezing in accordance with paragraph (C)(3)(a)(i)(903.3.1.1)
of this rule.
Such sprinklers shall be installed at
alternate floors beginning with the second level below the last intake and
ending with the floor above the discharge. Chute sprinklers shall be accessible
for servicing.
(iii)
903.2.11.3 Buildings 55 feet or more in
height. An automatic sprinkler system shall be installed throughout
buildings that have one or more stories with an occupant load of 30 or more
located 55 feet (16 764 mm) or more above the lowest level of fire department
vehicle access, measured to the finished floor.
Exceptions:
1.
Open parking
structures.
2.
Occupancies in Group F-2.
(iv)
903.2.11.4
Ducts conveying hazardous exhausts. Where required by the
mechanical code as listed in rule
1301:7-7-80
of the Administrative Code, automatic sprinklers shall be provided in
ducts conveying hazardous exhaust, flammable or combustible materials.
Exception:
Ducts where the largest cross-sectional diameter of the
duct is less than 10 inches (254 mm).
(v)
903.2.11.5
Commercial cooking operations. An automatic sprinkler system shall be
installed in commercial kitchen exhaust hood and duct systems where an
automatic sprinkler system is used to comply with paragraph (D)(904) of
this rule.
(vi)
903.2.11.6 Other required suppression
systems. In addition to the requirements of paragraph
(C)(2)( 903.2) of this rule, the provisions indicated in
Table 903.2.11.6 of this rule require the installation of a
fire suppression system for certain buildings and areas.
Table
903.2.11.6
Additional required
fire-extinguishing systems
Section
|
Subject
|
914.2.1
|
Covered and open mall
buildings
|
914.3.1
|
High rise
buildings
|
914.4.1
|
Atriums
|
914.5.1
|
Underground
structures
|
914.6.1
|
Stages
|
914.7.1
|
Special amusement
buildings
|
914.8.2
|
Airport traffic control
towers
|
914.8.3, 914.8.6
|
Aircraft hangars
|
914.9
|
Flammable finishes
|
914.10
|
Drying rooms
|
914.11.1
|
Ambulatory care
facilities
|
1029.6.2.3
|
Smoke-protected assembly
seating
|
1103.5.1
|
Pyroxylin plastic storage in
existing buildings
|
1103.5.2
|
Existing Group I-2
occupancies
|
1103.5.3
|
Existing Group I-2 Condition 2
occupancies
|
1103.5.4
|
Pyroxylin plastics
|
2108.2
|
Dry cleaning
plants
|
2108.3
|
Dry cleaning
machines
|
2309.3.2.6.2
|
Hydrogen motor fuel-dispensing
area canopies
|
2404.2
|
Spray finishing in Group A, E,
I or R
|
2404.4
|
Spray booths and spray
rooms
|
2405.2
|
Dip-tank rooms in Group A, I or
R
|
2405.4.1
|
Dip tanks
|
2405.9.4
|
Hardening and tempering
tanks
|
2703.10
|
HPM facilities
|
2703.10.1.1
|
HPM work station
exhaust
|
2703.10.2
|
HPM gas cabinets and exhausted
enclosures
|
2703.10.3
|
HPM exit access
corridor
|
2703.10.4
|
HPM exhaust ducts
|
2703.10.4.1
|
HPM noncombustible
ducts
|
2703.10.4.2
|
HPM combustible
ducts
|
2807.3
|
Lumber production conveyor
enclosures
|
2808.7
|
Recycling facility conveyor
enclosures
|
3006.1
|
Class A and B
ovens
|
3006.2
|
Class C and D
ovens
|
Table 3206.2
|
Storage fire
protection
|
3206.4
|
Storage
|
3704.5
|
Storage of more than 1,000
cubic feet of loose combustible fibers
|
5003.8.4.1
|
Gas rooms
|
5003.8.5.3
|
Exhausted
enclosures
|
5004.5
|
Indoor storage of hazardous
materials
|
5005.1.8
|
Indoor dispensing of hazardous
materials
|
5104.4.1
|
Aerosol warehouses
|
5106.3.2
|
Aerosol display and
merchandising areas
|
5306.2.1
|
Exterior medical gas storage
room
|
5306.2.2
|
Interior medical gas storage
room
|
5306.2.3
|
Medical gas storage
cabinet
|
5606.5.2.1
|
Storage of smokeless
propellant
|
5606.5.2.3
|
Storage of small arms
primers
|
5704.3.7.5.1
|
Flammable and combustible
liquid storage rooms
|
5704.3.8.4
|
Flammable and combustible
liquid storage warehouses
|
5705.3.7.3
|
Flammable and combustible
liquid Group H-2 or H-3 areas
|
6004.1.2
|
Gas cabinets for highly toxic
and toxic gas
|
6004.1.3
|
Exhausted enclosures for highly
toxic and toxic gas
|
6004.2.2.6
|
Gas rooms for highly toxic and
toxic gas
|
6004.3.3
|
Outdoor storage for highly
toxic and toxic gas
|
6504.1.1
|
Pyroxylin plastic storage
cabinets
|
6504.1.3
|
Pyroxylin plastic storage
vaults
|
6504.2
|
Pyroxylin plastic storage and
manufacturing
|
The building code as
listed in rule
1301:7-7-80
of the Administrative Code
|
Sprinkler system
requirements as set forth in section 903.2.11.6 of the building code as listed
in rule
1301:7-7-80
of the Administrative Code
|
For SI: 1 cubic foot = 0.023
m3.
(l)
903.2.12
During construction. Automatic sprinkler systems required during
construction, alteration and demolition operations shall be provided in
accordance with paragraph (M)(3313) of rule
1301:7-7-33
of the Administrative Code.