Ohio Admin. Code 3745-15-06 - Malfunction of equipment; scheduled maintenance; reporting
(A) Scheduled
maintenance of air pollution control equipment shall be conducted according to
the following:
(1) For the purposes of this
rule, maintenance of air pollution control equipment which is scheduled to
prevent a malfunction which would occur within two weeks if the maintenance
were not performed shall be considered to be a malfunction and
shall be subject to the provisions of
paragraph (B) of this rule.
(2)
Except as otherwise indicated in paragraph
paragraphs
(A)(3) and (A)(5) of this rule, scheduled
maintenance of air pollution control equipment, that requires the
shutdown
shutting down or bypassing
of said
the
equipment, must
shall be accompanied by the shutdown of the associated
air pollution sources.
(3) In cases where a complete source shutdown
may result in damage to the air pollution
sources
source or is otherwise
impossible,
or impractical, or
unsafe, the owner or operator may request authorization to continue
operating the sources
source during the scheduled maintenance of air
pollution control equipment. Any such request shall be made in a written report
at least two weeks prior to the planned shutdown of the air pollution control
equipment. The director shall authorize the continued
operation of the source despite shutdown of the air pollution control
equipment if, in his
the director's judgment, the situation justifies
continued operation of the sources
source . Any written report
request
submitted pursuant to this paragraph shall contain the following:
(a)
Identification
The
identification, including the Ohio EPA facility identification number and
permit application number, and location of the specific source for which
air pollution control equipment will be taken out of service.
The identification shall include the Ohio
environmental protection agency permit application number.
(b) The expected length of time that the air
pollution control equipment will be taken out of service.
(c) The nature and estimated quantity of
emissions of air contaminants
regulated air pollutants which are likely to
occur during the shutdown period
from all affected air pollution sources at the facility
during the scheduled maintenance, compared to the maximum authorized emissions
of the same air pollutants from all affected air pollution sources at the
facility during normal operation .
(d) Measures such as the use of off-shift
labor and equipment that will be taken to minimize the length of the
shutdown period
scheduled maintenance .
(e) The reasons
that
reason it will be impossible,
or
impractical, or unsafe to shut down the source
operation during the scheduled maintenance period.
(f) A demonstration that all feasible
description of the interim control measures
that will be taken to reduce emissions from the
source during the shutdown
scheduled maintenance period.
(4)
The
director retains the responsibility to evaluate any notification, request, or
report submitted pursuant to this rule. The director shall take appropriate
action upon a determination that the notification, request, or reporting
requirements of this rule have not been satisfied, that the equipment was not
properly operated and maintained prior to the scheduled maintenance, that
shutdown of the source or operation during the period of scheduled maintenance
was or has become practicable and safe, that the maintenance period was or has
become avoidable, or was induced or prolonged in bad faith, or that the
emissions attributable to the continued operation during the scheduled
maintenance period endanger or are projected to endanger the health or safety
of the public.
(5)
In cases where a complete source shutdown during the
scheduled maintenance of air pollution control equipment may result in damage
to the source or is otherwise impossible, impractical, or unsafe, the owner or
operator shall comply with the following work practices:
(a)
Take all
practicable measures to minimize the duration of the scheduled
maintenance.
(b)
Take all feasible interim control measures to reduce
emissions from the source during the scheduled maintenance.
(6)
Within
five business days of completing the scheduled maintenance of air pollution
control equipment identified in paragraph (A)(3) of this rule, the owner or
operator of the source shall notify the director that the scheduled maintenance
has been completed and described any deviations from the initial
notification.
(7)
Deviations from any emissions limitation or term and
condition of a permit shall be reported in accordance with Chapter 3745-77 of
the Administrative Code or paragraph (D) of rule
3745-15-03 of the Administrative
Code.
(B)
Malfunctions of air pollution control
equipment shall be reported as follows:
(1)
In the event
that any emission source, air pollution control equipment, or related facility
breaks down in such a manner as to cause the emission of air contaminants in
violation of any applicable law
If a
malfunction occurs , the person responsible for such
the equipment
in question shall immediately notify the Ohio
environmental protection agency
EPA district office or delegate agency of such
failure or breakdown
malfunction via telephone or email. Giving notice is not an
admission or proof of a violation of any specific emissions limitation,
standard or permit term . If the malfunction continues for more than
seventy-two
twenty-four hours, the source owner or operator shall
provide a written statement to the director within two weeks
one week of
the date the malfunction occurred. The
and include in both the immediate notification
and written statement shall include the
following data:
(b)(d) The estimated or
actual duration of breakdown
malfunction .
(c)(e) The nature and
estimated quantity of regulated air contaminants
which have been or may be emitted into the ambient air during the
breakdown
malfunction period.
(d)(g) Statements
demonstrating the following:
(a)
Identification
and location of such equipment including the Ohio environmental protection
agency permit application number for each air contaminant source.
The name of the owner or operator of the regulated entity
experiencing the malfunction event and the Ohio EPA facility identification
number.
(b)
The identification and location of such equipment
including the Ohio EPA emissions unit identification number for each air
pollution source involved in the malfunction.
(c)
A summary of the
event which caused the malfunction to occur.
(f)
Any adverse
impacts to human health or the environment as a result of the malfunction that
have been identified.
(i) Shutdown or
reduction of source operation during the breakdown
malfunction
period will be or would have been impossible,
or impractical, or
unsafe (if applicable). .
(ii)
The estimated breakdown
malfunction period will be or was reasonable in
duration based on installation or repair time, delivery dates of equipment,
replacement parts, or materials, or current unavailability of essential
equipment, parts, or materials, or personnel .
(iii) Available alternative operating
procedures and interim control measures will be or have been implemented during
the breakdown
malfunction period to reduce adverse effects on public
health or welfare.
(iv) All actions
necessary and required by any applicable preventive maintenance and malfunction
abatement plan will be or have been implemented.
(2) The Ohio environmental protection agency
EPA district office or delegate agency shall be
notified when the condition causing the failure or
breakdown
malfunction has been corrected
and the equipment is again in normal operation.
Notification of the correction of the condition causing the
failure or breakdown
malfunction may be given verbally if the duration of
the malfunction is seventy-two
twenty-four hours or less. Otherwise, such notification shall be
or in writing if the duration
exceeds twenty-four hours .
(3) Within two months following a
failure or breakdown
malfunction which exceeded seventy-two
twenty-four hours in duration, the owner or operator
of such equipment shall prepare and submit a detailed report which identifies a
program to prevent, detect and correct, as expeditiously as practicable,
similar future failures or breakdowns
malfunctions of such equipment.
(C) The director retains the responsibility
to evaluate any notification, request, or report
submitted pursuant to this rule. The director shall take appropriate action
upon a determination that the notification, request,
or reporting requirements of this rule have not been satisfied, that the
equipment was not properly operated and maintained prior to
breakdown
scheduled
maintenance or malfunction , that shutdown of the source or operation
during the period of maintenance or breakdown
malfunction
was or has become practicable and safe , that the
shutdown or breakdown
maintenance or malfunction was or has become
avoidable, or was induced or prolonged in bad faith, or that the emissions
attributable to the continued operation of the source
during the scheduled maintenance or the malfunction endanger or tend to
endanger the health or safety of the public.
(D) If, in the judgment of the director,
excessive or unduly prolonged malfunctions of any emission
air pollution
source, air pollution control equipment or related facility have occurred, the
director may require the owner or operator of said source, equipment or related
facility to prepare, submit and implement a preventive maintenance and
malfunction abatement plan which is acceptable to the director. Such plan shall
be designed to prevent, detect and correct malfunctions or equipment failures
which could result in emissions exceeding any applicable law.
(1) Each preventive maintenance and
malfunction abatement plan shall be in writing and specify the following:
(a) A comprehensive preventive maintenance
program, including a description of the items or conditions that will be
inspected, the frequency of these inspections or repairs, and an identification
of the types and quantities of the replacement parts which will be maintained
in inventory for quick replacement.
(b) An identification of the source and the
operating outlet variables of the air pollution control equipment that will be
monitored in order to detect a malfunction or failure, the normal operating
range of these variables, and a description of the monitoring or surveillance
procedures and of the method of informing operating personnel of any
malfunction, including alarm systems, lights or other indicators.
(c) A description of the corrective
procedures that will be taken in the event of a malfunction or failure in order
to achieve compliance with any applicable law as expeditiously as
practicable.
(2) Any
acceptable preventive maintenance and malfunction abatement plan shall be
specified in the terms and conditions of any permit or variance issued for a
source covered by such plan.
(3)
Operation and maintenance records shall be maintained by the owner or operator
of the source to demonstrate that any preventive maintenance and malfunction
abatement plan is fully implemented. All such records shall be maintained for a
minimum of two years and shall be subject
to inspection by the director or his representative upon request.