Ohio Admin. Code 3745-51-757 - Valves in gas or vapor service or in light liquid service - equipment leaks
(A)
Each valve in gas or vapor or light liquid service
shall be monitored monthly to detect leaks by the methods specified in
paragraph (B) of rule
3745-51-763 of the
Administrative Code and shall comply with paragraphs (B) to (E) of this rule,
except as provided in paragraphs (F), (G), and (H) of this rule and rules
3745-51-761 and
3745-51-762 of the
Administrative Code.
(B)
If an instrument reading of ten thousand parts per
million (ppm) or greater is measured, a leak is detected.
(C)
(1)
Any valve for which a leak is not detected for two
successive months may be monitored the first month of every succeeding quarter,
beginning with the next quarter, until a leak is detected.
(2)
If a leak is
detected, the valve shall be monitored monthly until a leak is not detected for
two successive months,
(D)
(1)
When a leak is detected, the leak shall be repaired as
soon as practicable, but no later than fifteen calendar days after the leak is
detected, except as provided in rule
3745-51-759 of the
Administrative Code.
(2)
A first attempt at repair shall be made no later than
five calendar days after each leak is detected.
(E)
First attempts at
repair include, but are not limited to, the following best practices where
practicable:
(1)
Tightening of bonnet bolts.
(2)
Replacement of
bonnet bolts.
(3)
Tightening of packing gland nuts.
(4)
Injection of
lubricant into lubricated packing.
(F)
Any valve that is
designated, as described in paragraph (G)(2) of rule
3745-51-764 of the
Administrative Code, for no detectable emissions, as indicated by an instrument
reading of less than five hundred ppm above background, is exempt from the
requirements of paragraph (A) of this rule if the valve:
(1)
Has no external
actuating mechanism in contact with the hazardous secondary material
stream.
(2)
Is operated with emissions less than five hundred ppm
above background as determined by the method specified in paragraph (C) of rule
3745-51-763 of the
Administrative Code.
(3)
Is tested for compliance with paragraph (F)(2) of this
rule initially upon designation, annually, and at other times as requested by
the director.
(G)
Any valve that is designated, as described in paragraph
(H)(1) of rule
3745-51-764 of the
Administrative Code, as an unsafe-to-monitor valve is exempt from the
requirements of paragraph (A) of this rule if:
(1)
The
remanufacturer or other person who stores or treats the hazardous secondary
material determines that the valve is unsafe to monitor because monitoring
personnel would be exposed to an immediate danger as a consequence of complying
with paragraph (A) of this rule.
(2)
The
remanufacturer or other person who stores or treats the hazardous secondary
material adheres to a written plan that requires monitoring of the valve as
frequently as practicable during safe-to-monitor times.
(H)
Any
valve that is designated, as described in paragraph (H)(2) of rule
3745-51-764 of the
Administrative Code, as a difficult-to-monitor valve is exempt from the
requirements of paragraph (A) of this rule if:
(1)
The
remanufacturer or other person who stores or treats the hazardous secondary
material determines that the valve cannot be monitored without elevating the
monitoring personnel more than two meters above a support
surface.
(2)
The hazardous secondary material management unit within
which the valve is located was in operation before the first effective date of
this rule.
(3)
The owner or operator of the valve follows a written
plan that requires monitoring of the valve at least once per calendar
year.
Notes
Five Year Review (FYR) Dates: Exempt
Promulgated Under: 119.03
Statutory Authority: 3734.12
Rule Amplifies: 3734.12