Ohio Admin. Code 4101:2-10-01 - Boilers, water heaters and pressure vessels
Chapter 10 of the International Mechanical Code, 2021 edition, as incorporated by reference and modified in Section 101.1.1 of this code, is further modified as follows:
(A)
Modify the
first paragraph of section
1001.1 to read as
follows:
1001.1
Scope.
This chapter is
to govern the installation,
alteration
and
repair
of boilers in Group R occupancy buildings with 4 or 5
dwelling units, water heaters and pressure vessels.
(B)
Add
exceptions 8 and 9 to section
1001.1 to read as
follows:
8.
Potable water heaters are to comply with the "Ohio
Boiler and Pressure Vessel rules", Chapters 4101:4-1 to 4101:4-10 of the
Administrative Code, when any of the following limitations are exceeded:
a.
Heat input of two
hundred thousand BTU per hour;
b.
Water temperature
of two hundred ten degrees Fahrenheit;
c.
Nominal water
containing capacity of one hundred twenty gallons.
9.
Any boiler, water
heater, or unfired pressure vessel within the scope of Chapters 4101:4-1 to
4101:4-10 of the Administrative Code entitled "Ohio Boiler and Pressure Vessel
Rules".
(C)
Add section
1001.2 to read as
follows:
1001.2
Enforcement.
The
superintendent of the division of industrial compliance is to enforce all
provisions of rules
4101:4-1-01 to
4101:4-10-01 and rules
1301:3-5-01 to
1301:3-5-10 of the
Administrative Code relating to the design, construction, repair, alteration,
and maintenance of boilers, pressure vessels, and potable hot water heaters not
within the scope of this chapter.
(D)
Modify
Section 1004.1 to read as follows:
Standards.
Boilers are to be designed,
constructed and certified in accordance with the ASME Boiler and Pressure
Vessel Code, Section I or IV. The boiler is to be provided with safety devices
and controls as required in the applicable section of the "ASME Boiler and
Pressure Vessel Code". Alternatively, controls and safety devices for boilers
with fuel input ratings of less than 12,500,000 Btu/hr (3,662,500 W) are to
meet the requirements of ASME CSD-1. Controls and safety devices for boilers
with inputs greater than or equal to 12,500,000 Btu/hr (3,662,500 W) are to
meet the requirements of NFPA 85. Packaged oil-fired boilers are to be listed
and labeled in accordance with UL 726. Packaged electric boilers are to be
listed and labeled in accordance with UL 834. Solid-fuel-fired boilers are to
be listed and labeled in accordance with UL 2523.
Replaces: 4101:2-10-01
Notes
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1), 4104.02 (A)(1)
Rule Amplifies: 3781.10, 3781.11, 3791.04
Prior Effective Dates: 03/01/1998, 01/01/2002, 03/01/2005, 07/01/2007, 11/01/2011, 11/01/2017