Or. Admin. R. 333-061-0078 - Coliform Investigations
(1) A
coliform investigation, as defined in OAR 333-061-0020(22), is an evaluation to
identify the possible presence of sanitary defects, defects in distribution
system coliform monitoring practices, and the likely reason that the coliform
investigation was triggered at the public water system. Coliform investigations
are separated into two levels as described in this section.
(a) A level 1 coliform investigation is
conducted by the water supplier or a representative thereof. Minimum elements
of the investigation include review and identification of atypical events that
could affect distributed water quality or indicate that distributed water
quality was impaired; changes in distribution system maintenance and operation
that could affect distributed water quality (including water storage); source
and treatment considerations that bear on distributed water quality, where
appropriate (for example, whether a ground water system is disinfected);
existing water quality monitoring data; and inadequacies in sample sites,
sampling protocol, and sample processing.
(b) A level 2 coliform investigation is
conducted by the Authority or a party approved by the Authority and is a more
detailed and comprehensive examination of a water system (including the
system's monitoring and operational practices) than a level 1 investigation.
Minimum elements include those that are part of a level 1 investigation and
additional review of available information, internal and external resources,
and other relevant practices. Water suppliers must comply with any expedited
actions or additional actions required by the Authority in the case of an
exceedance of the MCL for E. coli.
(2) Coliform investigations must be conducted
according to section (3) of this rule after a coliform investigation trigger
identified in this section is exceeded at a water system.
(a) Level 1 coliform investigation triggers
include, but are not limited to:
(A)
Exceeding 5.0 percent total coliform-positive samples for the month at water
systems where 40 or more samples per month are collected;
(B) Having two or more total
coliform-positive samples in the same month at water systems where fewer than
40 samples per month are collected; or
(C) Failing to collect every required repeat
sample after any single total coliform-positive sample.
(b) Level 2 coliform investigation triggers
include, but are not limited to:
(A) An
exceedance of the MCL for E. coli as specified in OAR
333-061-0030(4); or
(B) A second
level 1 trigger as specified in subsection (2)(a) of this rule within a rolling
12-month period, unless the Authority has determined a likely cause for the
total coliform-positive samples responsible for the first level 1 investigation
trigger and established that the water supplier corrected the problem.
(c) The results of all
routine and repeat samples collected according to OAR 333-061-0036(6)(b)
through (g) not invalidated by the Authority must be used to determine whether
a coliform investigation trigger as specified in this section has been
exceeded.
(d) Special purpose
samples, such as those collected to determine whether disinfection practices
are sufficient following pipe placement, replacement, or repair, may not be
used to determine whether a coliform investigation trigger has been exceeded.
(3) Water suppliers must
ensure that coliform investigations are conducted in order to identify the
possible presence of sanitary defects and defects in distribution system
coliform monitoring practices.
(a) Water
suppliers must ensure that investigators evaluate at least the minimum elements
as specified in subsection (1)(a) or (1)(b) of this rule and must conduct the
investigation consistent with any Authority directives that tailor specific
investigation elements with respect to the size and type of the system and the
size, type, and characteristics of the distribution system.
(b) Water suppliers must conduct level 1
coliform investigations consistent with Authority requirements if any of the
investigation triggers specified in subsection (2)(a) of this rule are
exceeded.
(A) The coliform investigation must
be completed as soon as practical after exceeding the trigger, and must include
a report summarizing the investigation.
(B) In the completed investigation report,
water suppliers must describe sanitary defects detected, corrective actions
completed, and a proposed timetable for any corrective actions not already
completed. The investigation report may also note that no sanitary defects were
identified.
(C) If the Authority
reviews the completed coliform investigation report and determines that the
investigation is not sufficient (including any proposed timetable for any
corrective actions not already completed), the Authority will consult with the
water supplier. If the Authority requires revisions after consultation, the
water supplier must submit a revised investigation report to the Authority on
an agreed-upon schedule not to exceed 30 days from the date of the
consultation.
(c) Water
suppliers must submit to and ensure a level 2 coliform investigation is
conducted as soon as practical after a coliform investigation trigger specified
in subsection (2)(b) of this rule is exceeded. Water suppliers must ensure a
completed investigation report is submitted to the Authority as specified in
OAR 333-061-0040(1)(l).
(A) Water suppliers
must communicate with the Authority to ensure the investigation is completed
within 30 days after learning that a coliform investigation trigger was
exceeded.
(B) Completed
investigation reports must describe sanitary defects detected, corrective
actions completed, and a proposed timetable for any corrective actions not
already completed. The investigation report may also note that no sanitary
defects were identified.
(C) Water
suppliers must comply with any expedited actions or additional actions required
by the Authority in the case of an exceedance of the MCL for E.
coli.
(D) If the Authority
reviews a completed level 2 coliform investigation report and determines that
the investigation is not sufficient (including any proposed timetable for any
corrective actions not already completed), the Authority will consult with the
water supplier. If the Authority requires revisions after consultation, the
water supplier must ensure a revised investigation report is submitted to the
Authority on an agreed-upon schedule not to exceed 30 days.
(d) Upon completion and submission of a level
1 or level 2 coliform investigation report, the Authority must determine if a
likely cause for the level 1 trigger or level 2 trigger was identified and
determine whether the water supplier corrected the problem, or agreed to a
schedule acceptable to the Authority for correcting the
problem.
(4) Water
suppliers must correct sanitary defects discovered during level 1 or level 2
coliform investigations as soon as practical. For corrections not completed by
the time an investigation report is submitted to the Authority, the water
supplier must complete the corrective action(s) in compliance with a timetable
approved by the Authority in consultation with the water supplier. The water
supplier must notify the Authority when each scheduled corrective action is
completed. At any time during the investigation or corrective action phase,
either the water supplier or the Authority may request a consultation with the
other party to determine the appropriate actions to be taken. The water
supplier may consult with the Authority regarding all relevant information that
may impact its ability to comply with a requirement of this rule, including the
method of accomplishment, an appropriate timeframe, and other relevant
information.
(5) Failing to conduct
the required coliform investigation after a trigger is exceeded or failure to
complete corrective actions according to an Authority approved timetable is a
violation of this rule.
Notes
Statutory/Other Authority: ORS 448.131
Statutes/Other Implemented: ORS 448.131, 448.150 & 448.273