Or. Admin. R. 340-150-0555 - Compliance Dates for USTs and Piping
(1) An owner and permittee must comply with
all release detection requirements for a new or existing UST system or
permanently close the UST system by the following schedule:
(a) For UST systems installed before 1965 and
for UST systems where the installation date is unknown:
(A) December 22, 1989, for tanks and suction
piping.
(B) December 22, 1990, for
pressurized piping.
(b)
For UST systems installed between 1965 and 1969 -- December 22, 1990, for
tanks, suction piping and pressurized piping.
(c) For UST systems installed between 1970
and 1974:
(A) December 22, 1990, for
pressurized piping.
(B) December
22, 1991, for tanks and suction piping.
(d) For UST systems installed between 1975
and 1979:
(A) December 22, 1990, for
pressurized piping.
(B) December
22, 1992, for tanks and suction piping.
(e) For UST systems installed between 1980
and December 22, 1988:
(A) December 22, 1990,
for pressurized piping.
(B)
December 22, 1993, for tanks and suction piping.
(f) For tanks, suction piping and pressurized
piping, release detection requirements must be met upon date of installation
for all new UST systems installed after December 22, 1988.
(2) An owner and permittee of a new UST
system installed after December 22, 1988, must comply with the corrosion
protection performance standards for tanks and piping (OAR
340-150-0320 and
340-150-0325) at the time of installation.
(3)
An owner and permittee of an existing UST system installed on or before
December 22, 1988, must comply with the requirements for upgrading USTs and
piping (OAR
340-150-0560) by no later than December 22, 1998.
(4) An owner and permittee that does not
comply with section (2) or (3) of this rule must decommission the UST system in
compliance with the requirements of OAR
340-150-0166 through
340-150-0168 by no later than December 22, 1998.
(5) An owner and permittee of a hazardous
substance UST system (e.g., an UST containing any nonpetroleum regulated
substance) installed on or before December 22, 1988, must comply with the
release detection requirements of OAR
340-150-0400 and
340-150-0410 until December 22, 1998. After December 22, 1998, an owner and permittee of a
hazardous substance UST system must comply with the requirements of
340-150-0420.
(6) An owner and permittee of a new or
existing UST system that does not meet the performance standards in OAR
340-150-0300 or
340-150-0560 may use monthly inventory control and annual tank tightness testing as a
release detection method until December 22, 1998. After that date, an owner and
permittee must upgrade or permanently close the UST system.
Notes
Stat. Auth.: ORS 466.706 - 466.835, 466.994 & 466.995
Stats. Implemented: ORS 466.746 & 466.765
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.