Or. Admin. R. 340-239-0600 - Monitoring Requirements
When required as provided in OAR 340-239-0100 through 340-239-0800, the owner or operator of a landfill must comply with the monitoring requirements in this rule.
(1) Surface Emissions Monitoring
Requirements. The owner or operator of a landfill with a gas collection and
control system must conduct quarterly instantaneous and integrated surface
monitoring of the landfill surface using the procedures specified in OAR
340-239-0800(3). All of the following requirements apply to such monitoring:
(a) Instantaneous Surface Monitoring. Any
reading exceeding a limit specified in OAR 340-239-0100(6)(b),
340-239-0200(1)(a), or 340-239-0400(2)(c) must be recorded as an exceedance and
all of the following actions must be taken:
(A) The owner or operator must record the
name of the individual that conducted SEM, date, location, and value of each
exceedance, along with retest dates and results. The location of each
exceedance must be clearly marked and identified on a topographic map of the
landfill, drawn to scale with the location of both the grids and the gas
collection system clearly identified. The documentation required under this
subsection must be retained in the landfill's files and reported to DEQ as
provided in OAR 340-239-0700.
(B)
The owner or operator must take corrective action such as, but not limited to,
cover maintenance or repair, or well vacuum adjustments.
(C) The owner or operator must remonitor the
location of the exceedance, and the location must be remonitored within ten
days of a measured exceedance. The owner or operator must comply with all of
the following requirements:
(i) If the
remonitoring of the location shows a second exceedance, the owner or operator
must take additional corrective action and the location must be re-monitored
again no later than 10 days after the second exceedance.
(ii) If the remonitoring shows a third
exceedance, the owner or owner or operator must install a new or replacement
collection device and must demonstrate compliance no later than 120 days after
detecting the third exceedance.
(iii) Any location that initially showed an
exceedance but has a methane concentration at the 10-day remonitoring of less
than 500 ppmv methane, or 200 ppmv methane if this is to determine compliance
with OAR 340-239-0100(6)(b), must be re-monitored one month from the initial
exceedance. If the one-month re-monitoring shows a concentration less than 500
ppmv methane, or 200 ppmv methane if this is to determine compliance with OAR
340-239-0100(6)(b), no further monitoring of that location is required until
the next quarterly monitoring period. If the one-month re-monitoring shows an
exceedance, the owner or operator must install a new or replacement well to
achieve compliance no later than 120 days after detecting the third
exceedance.
(iv) For any location
where monitored methane concentration equals or exceeds 500 ppmv, or 200 ppmv
methane if this is to determine compliance with OAR 340-239-0100(6)(b), three
times within a quarterly period, a new well or other collection device must be
installed within 120 days of the initial exceedance. An alternative remedy to
the exceedance, such as upgrading the blower, header pipes or control device,
and a corresponding timeline for installation may be submitted to DEQ for
approval pursuant to OAR 340-239-0500.
(D) The owner or operator of a closed or
inactive landfill, or of any closed or inactive areas on an active landfill
that has no monitored exceedances of the limits specified in OAR
340-239-0200(1)(a) after four consecutive quarterly instantaneous surface
monitoring periods, may shift to annual instantaneous surface
monitoring.
(E) An owner or
operator that has shifted to annual instantaneous surface monitoring under
paragraph (1)(a)(C) of this rule must return to quarterly instantaneous surface
monitoring upon any exceedances of the limits specified in OAR
340-239-0200(1)(a) that cannot be remediated within 10 days or upon any
exceedances detected during a DEQ inspection.
(b) Integrated Surface Monitoring. Any
reading exceeding the limit specified in OAR 340-239-0200(1)(b) must be
recorded as an exceedance and all of the following actions must be taken:
(A) The owner or operator must record the
average surface concentration measured as methane for each grid along with
retest dates and results. The location of the grids and the gas collection
system must be clearly marked and identified on a topographic map of the
landfill drawn to scale. The documentation required under this subsection must
be retained in the landfill's files and reported to DEQ as provided in OAR
340-239-0700.
(B) Within 10 days of
a measured exceedance, corrective action must be taken by the owner or operator
such as, but not limited to; cover maintenance or repair, or well vacuum
adjustments and the grid must be remonitored. The owner or operator must comply
with all of the following requirements:
(i) If
the remonitoring of the grid shows a second exceedance, additional corrective
action must be taken and the location must be re-monitored again no later than
10 days after the second exceedance.
(ii) If the remonitoring in subparagraph
(1)(b)(B)(i) of this rule shows a third exceedance, the owner or operator must
install a new or replacement well to achieve compliance no later than 120 days
after detecting the third exceedance.
(C) The owner or operator of a closed or
inactive landfill, or of any closed or inactive areas on an active landfill
that has no monitored exceedances of the limits specified in OAR
340-239-0200(1)(b) after four consecutive quarterly integrated surface
monitoring periods, may shift to annual integrated surface
monitoring.
(D) An owner or
operator that has shifted to annual integrated surface monitoring under
paragraph (1)(b)(C) of this rule must return to quarterly integrated surface
monitoring upon the occurrence of any exceedances of the limits specified in
OAR 340-239-0200(1)(b) during annual monitoring or detected during any DEQ
inspection.
(2)
Gas Control System Equipment Monitoring. The landfill owner or operator must
monitor the gas control system using the following procedures:
(a) For enclosed flares all of the following
equipment must be installed, calibrated, maintained, and operated according to
the manufacturer's specifications:
(A) A
temperature monitoring device equipped with a continuous recorder that has an
accuracy of plus or minus (±) one percent of the temperature being
measured expressed in degrees Celsius or Fahrenheit. A temperature monitoring
device is not required for boilers or process heaters with design heat input
capacity equal to or greater than 44 megawatts per hour (150 million British
thermal units per hour).
(B) A
device that records gas flow to the control device and bypass of the control
device (if applicable). The owner or operator must:
(i) Install, calibrate, and maintain a gas
flow rate measuring device that records the flow to the control device at least
every 15 minutes; and
(ii) Secure
the bypass line valve in the closed position with a car-seal or a lock-and-key
type configuration. A visual inspection of the seal or closure mechanism must
be performed at least once every month to ensure that the valve is maintained
in the closed position and that the gas flow is not diverted through the bypass
line.
(b) For
a gas control device other than an enclosed flare, the owner or operator must
provide information describing the operation of the gas control device, the
operating parameters that would indicate proper performance, and appropriate
monitoring procedures. The owner or operator must maintain, operate, and
monitor the device according to the written manufacturer instructions and
specifications. Alternative compliance requests must be submitted to DEQ as
specified in OAR 340-239-0500. DEQ may specify additional monitoring
procedures.
(c) Components
containing landfill gas and under positive pressure must be monitored quarterly
for leaks. Any component leak over 500 ppmv methane must be tagged and repaired
within 10 days. Any component leak over 250 ppmv must be recorded pursuant to
OAR 340-239-0700(2)(a)(S). Quarterly component leak testing at landfills having
landfill gas-to-energy facilities may be conducted prior to scheduled
maintenance or planned outage periods.
(d) The owner or operator must measure gauge
pressure in the gas collection header applied to each individual well on a
monthly basis. If a positive pressure exists, other than as provided in OAR
340-239-0200(2), action must be initiated to correct the exceedance within 5
days. Any attempted corrective measure must not cause exceedances of other
operational or performance standards.
(3) Wellhead Monitoring. On a monthly basis
for each individual wellhead, the landfill owner or operator must determine and
record gauge pressure, temperature, and nitrogen or oxygen content of gas
emissions. Such monitoring must comply with all of the following requirements:
(a) If there is any positive pressure reading
other than as provided in OAR 340-239-0110(4) or (5), the owner or operator
must take the following actions. Any attempted corrective measure must not
cause exceedances of other operational or performance standards:
(A) Initiate corrective action within five
days of the positive pressure measurement;
(B) If negative pressure cannot be achieved
without excess air infiltration within 15 days of the date the positive
pressure was first measured, the owner or operator must conduct a root cause
analysis and correct the exceedance as soon as practicable, but no later than
60 days after positive pressure was first measured. The owner or operator must
submit a Corrective Action Report to DEQ pursuant to OAR
340-239-0700(3)(k);
(C) If
corrective actions cannot be fully implemented within 60 days following the
positive pressure measurement for which the root cause analysis was required,
the owner or operator must also conduct a corrective action analysis and
develop an implementation schedule to complete the corrective action(s) as soon
as practicable, but no more than 120 days following the positive pressure
measurement; and
(D) If corrective
action is expected to take longer than 120 days to complete after the initial
exceedance, the owner or operator must submit the root cause analysis,
corrective action analysis, and corresponding implementation timeline to
DEQ.
(b) If a well
exceeds the operating parameter for temperature, action must be initiated to
correct the exceedance within five days. Any attempted corrective measure must
not cause exceedances of other operational or performance standards, and the
owner or operator must comply with all of the following requirements:
(A) If a landfill gas temperature less than
62.8 degrees Celsius (145 degrees Fahrenheit), or as established in OAR
340-239-200(3), cannot be achieved within 15 days of the first measurement of
landfill gas temperature greater than 62.8 degrees Celsius (145 degrees
Fahrenheit), the owner or operator must conduct a root cause analysis and
correct the exceedance as soon as practicable, but no later than 60 days after
a landfill gas temperature greater than 62.8 degrees Celsius (145 degrees
Fahrenheit) was first measured. The owner or operator must keep records
according to OAR 340-239-0700(2).
(B) If corrective actions cannot be fully
implemented within 60 days following the temperature measurement for which the
root cause analysis was required, the owner or operator must also conduct a
corrective action analysis and develop an implementation schedule to complete
the corrective action(s) as soon as practicable, but no more than 120 days
following the measurement of landfill gas temperature greater than 62.8 degrees
Celsius (145 degrees Fahrenheit). The owner or operator must submit the items
listed in OAR 340-239-0700(3)(c)(A) as part of the next semi-annual report. The
owner or operator must keep records according to OAR 340-239-0700(2).
(C) If corrective action is expected to take
longer than 120 days to complete after the initial exceedance, the owner or
operator must submit the root cause analysis, corrective action analysis, and
corresponding implementation timeline to DEQ, according to OAR
340-239-0700(3)(c)(A) and OAR 340-239-600(3)(a)(C). The owner or operator must
keep records according to OAR 340-239-0700(2).
(D) If a landfill gas temperature measured at
either the wellhead or at any point in the well is greater than or equal to
76.7 degrees Celsius (170 degrees Fahrenheit) and the carbon monoxide
concentration measured, according to the procedures in OAR 340-239-0800(7), is
greater than or equal to 1,000 ppmv the corrective action(s) for the wellhead
temperature standard (62.8 degrees Celsius or 145 degrees Fahrenheit) must be
completed within 15 days.
(E) If a
higher operating temperature has not been approved by DEQ, the enhanced
monitoring specified in OAR 340-239-0800(8) is required at each well with a
measurement of landfill gas temperature greater than 62.8 degrees Celsius (145
degrees Fahrenheit).
(4) Cover integrity. The landfill owner or
operator shall implement a program to monitor for cover integrity and implement
cover repairs as necessary on a monthly basis. The cover must conform with
requirements in OAR chapter 340, divisions 094 and 095.
(5) The monitoring requirements of this
division apply at all times, except for periods of monitoring system
malfunctions, repairs associated with monitoring system malfunctions, and
required monitoring system quality assurance or quality control activities. A
monitoring system malfunction is any sudden, infrequent, not reasonably
preventable failure of the monitoring system to provide valid data. Monitoring
system failures that are caused in part by poor maintenance or careless
operation are not malfunctions. Monitoring system repairs completed in response
to monitoring system malfunctions to return the monitoring system to operation
must be completed as expeditiously as practicable.
Notes
Statutory/Other Authority: ORS 468.020, ORS 468A.025, ORS 468A.040 & ORS 468A.050
Statutes/Other Implemented: ORS 468A.025, ORS 468A.040 & ORS 468A.050
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.