Or. Admin. R. 411-087-0440 - Electrical Systems: Alarm and Nurse Call Systems
(1) Exit Door Alarm. The facility shall have
an exit door alarm system which alerts the staff when an exit door is opened or
when a resident departs, or any other system determined to be acceptable to the
Division (such determination shall be in writing).
(2) Nurse Call System:
(a) Resident Rooms. Each resident room shall
be served by an electric nurse call system. Each resident shall have a nurse
call button which may be easily located to allow the resident to summon nursing
staff. Two call buttons serving adjacent beds may be served by one calling
station;
(b) Bath, Toilet and
Shower Rooms. Each bath, toilet and shower room must have an electric call
system;
(c) Nurses' Station. The
nurse call system shall register all calls at the nurses' station by both a
visible and audible signal. The nurse call system shall also register a visible
signal in the corridor adjacent to the door of the room from which the signal
originated:
(A) The visible signal shall
remain on until turned off at the location where the signal
originated;
(B) In multi-corridor
nursing units, additional visible signals shall be installed at corridor
intersections.
(3) Fire/Smoke Alarm System. Fire and smoke
detection/alarm systems shall comply with OAR 411-087-0020 ("Referenced
Regulations").
(4) Exceptions:
(a) Pediatric Units. Rooms in pediatric units
may have two-way voice communications in lieu of call buttons required under
subsection (2)(a) of this rule. Such systems shall be equipped with an
indicating light at each calling station which lights and remains lighted as
long as the voice circuit is operating;
(b) Locked Units. Rooms in locked units
serving residents with Alzheimers or other dementias may have wall-mounted call
buttons in lieu of call buttons on cords when necessary for resident
safety;
(c) Audible Signal. Call
systems in facilities continuously licensed since January 1, 1992 shall not be
required to have an audible call feature at the nurses' station unless required
to conform pursuant to OAR 411-087-0010.