Or. Admin. R. 411-087-0450 - Heating and Ventilating Systems
(1) Energy Conservation. Special design
considerations should be given to energy conservation in accordance with
Section 53 of the Oregon Structural Specialty
Code.
(2) Temperature:
(a) Design. For all areas occupied by
residents, the indoor winter design temperature shall be 75 degrees Fahrenheit
(24 degrees Celsius). For all other occupied areas, the indoor winter design
temperature shall be 72 degrees Fahrenheit (22 degrees Celsius).
NOTE: This does not preclude operation at lower temperatures where appropriate and resident safety is not affected.
(b) Function. For all areas
occupied by residents, the indoor temperature shall be maintained at not less
than 70 degrees Fahrenheit (21 degrees Celsius).
(3) Ventilation Design. In the interest of
energy conservation, the facility is encouraged to utilize recognized
procedures such as variable air volume and load shedding systems in areas not
listed in Table 2 and where direct care is not affected such as
administrative and public areas, general storage, etc. Consideration may be
given to special design innovations of Table 2 provided that
pressure relationships as an indication of direction of air flow and total
number of air changes as listed is maintained. All such proposed design
innovations are subject to review and approval by the Division.
(4) Ventilation System Details. All
air-supply and air-exhaust systems shall be mechanically operated. All fans
serving exhaust systems shall be located at the discharge end of the system and
have motor life ratings suitable for continuous use (20,000 hours minimum). The
ventilation rates shown in Table 2 shall be considered as minimum
acceptable rates and shall not be construed as precluding the use of higher
ventilation rates when needed for temperature control or control of odors:
(a) Outdoor air intakes shall be located as
far as practical but not less than 25 feet (7.62 m) from exhaust outlets of
ventilating systems, combustion equipment stacks, vacuum systems, plumbing vent
stacks, or from areas which may collect vehicular exhaust and other noxious
fumes (plumbing and vacuum vents that terminate above the level of the top of
the air intakes may be located as close as ten feet (3.05 m)). The bottom of
outdoor air intakes serving central systems shall be located as high as
practical but not less than six feet (1.83 m) above ground level, or if
installed above the roof, three feet (91 cm) above roof level;
(b) The ventilation systems shall be designed
and balanced to provide the air exchange rate and pressure relationship shown
in Table 2;
(c) The
bottoms of ventilation openings shall be not less than three inches (7.6 cm)
above the floor of any room;
(d)
Corridors shall not be used to supply air or exhaust air from any occupiable
room. Pressurization of corridors for odor control will be allowed within
limits established by the agency having jurisdiction for enforcement of the
Oregon Mechanical Specialty Code;
(e) All central ventilation or air
conditioning systems shall be equipped with filters having efficiencies no less
than those specified in Table 3. The filter bed shall be located upstream of
the air conditioning equipment unless a pre-filter is employed. In this case,
the pre-filter shall be upstream of the equipment and the main filter bed shall
be located further downstream. Electronic filter systems meeting required
efficiency ratings may be proposed as an acceptable alternative when installed
and maintained in accord with recommendations of the manufacturer.
Manufacturer's specifications and recommendations for installation shall be
submitted for approval by the Division. If electronic filters are used, the
facility shall comply with the manufacturer's specifications and
recommendations for maintenance and cleaning. This information, including a
copy of the manufacturer's specifications and recommendations, shall be
documented and available in the facility;
(f) All filter(s) efficiencies shall be
average atmospheric dust spot efficiencies tested in accordance with
ASHRAE Standard 52-76. Filter frames shall be durable and
carefully dimensioned and shall provide an airtight fit with the enclosing duct
work. All joints between filter segments and the enclosed duct work shall have
gaskets or seals to prevent air leakage. A manometer shall be installed across
each filter bed serving central air systems;
(g) Air handling duct systems shall meet the
requirements of NFPA Standard 90A;
(h) Fire and smoke dampers shall be
constructed, located, and installed in accordance with the requirements of
NFPA Standard 90A except that all systems, regardless of size,
serving more than one smoke or fire zone shall be equipped with smoke detectors
to shut down fans automatically as delineated in Paragraph 4-3.2 of the
Standard. Access for maintenance shall be provided at all dampers.
Switching for restart of fans may be conveniently located for fire department
use to assist in evacuation of smoke after the fire is controlled, provided
provisions are made to avoid possible damage to the system because of closed
dampers.
(5) Testing
Required. Prior to facility licensure, all mechanical systems shall be tested,
balanced, and operated to demonstrate to the design engineer or his/her
representative that installation and performance of these systems conform to
the design intent. Test results shall be made available on request to
representatives of the Division.
(6) Exceptions. Facilities continuously
licensed since January 1, 1992 shall not be required to meet sections (1), (3),
(4) and (5) of this rule unless required to conform pursuant to OAR
411-087-0010.
Notes
Tables referenced are available from the agency.
Stat. Auth.: ORS 410.070 & 441.055
Stats. Implemented: ORS 441.055 & 441.615
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.