Or. Admin. R. 414-205-0105 - Testing for Lead in Drinking Water

(1) For purposes of this rule, "drinking water faucet or fixture"
(a) means any plumbing fixture on the premises used to obtain water for drinking, cooking, preparing infant formula, or preparing food; and
(b) does not include any plumbing fixture used to obtain water for handwashing, bathing, or diaper changing.
(2) Water obtained from fixtures identified in subsection (1)(b) of this rule cannot be used for drinking, cooking, preparing infant formula, or preparing food.
(3) Initial Testing
(a) Any provider with an active registration as of September 30, 2018 must test each drinking water faucet or fixture by November 30, 2018.
(b) The following providers must test each drinking water faucet or fixture for lead in the water prior to being eligible to receive a license from CCLD:
(A) Any provider with a pending registration application as of September 30, 2018; and
(B) Any provider applying for registration on or after September 30, 2018, including, but not limited to, initial applications, renewal applications, and reopen applications.
(c) A provider identified in (3)(a) or (b) does not need to conduct the initial testing if:
(A) All drinking water faucets or fixtures have been tested within 6 years prior to the effective date of this rule; and
(B) The testing was conducted in accordance with the requirements of subsection (5) of this rule.
(d) A provider identified in subsection (3)(a) must submit all test results to CCLD no later than November 30, 2018. The test results must be accompanied by a written statement that identifies the location of each drinking water faucet or fixture tested.
(e) A provider identified in (3)(b) must submit test results to CCLD within 10 calendar days of the facility receiving the results from the laboratory. The test results must be accompanied by a written statement that identifies the location of each drinking water faucet or fixture tested.
(4) Ongoing Testing
(a) After a provider conducts the initial testing under subsection (3) of this rule, the provider must test all drinking water faucets or fixtures at least once every six years from the date of the last test.
(b) All test results obtained in accordance with subsection (4)(a) of this rule must be submitted to CCLD within 10 calendar days of the provider receiving the results from the laboratory. The test results must be accompanied by a written statement that identifies the location of each drinking water faucet or fixture tested.
(5) Sampling and Testing
(a) All sample collection and testing must be in accordance with the Environmental Protection Agency (EPA)'s 3Ts for Reducing Lead in Drinking Water in Schools and Child Care Facilities, Revised Manual from October 2018, adopted by reference.
(b) All testing must be performed by a laboratory accredited by the Oregon Laboratory Accreditation Program according to standards set under OAR chapter 333, division 64 in effect as of September 30, 2018.
(c) If a facility does not use any of the on-site plumbing fixtures to obtain water for drinking, cooking, preparing infant formula, or preparing food, the provider must:
(A) Submit a written statement to CCLD identifying the alternative source of water and confirming that the provider does not use any on-site plumbing fixtures for drinking, cooking, preparing infant formula, or preparing food; and
(B) Notify CCLD in writing if the alternative source of water changes.
(6) Results
(a) If test results show that water from any drinking water faucet or fixture has 15 parts per billion (ppb) or more of lead, the provider must:
(A) Prevent access to that drinking water faucet or fixture immediately after receiving the test results; and
(B) Continue to prevent access to that drinking water faucet or fixture until mitigation in completed in accordance with subsection (6)(b) of this rule.
(b) Following receipt of test results showing that water from any drinking water faucet or fixture has 15 parts per billion (ppb) or more of lead, the provider must:
(A) Submit a corrective action plan to CCLD for approval within 60 days of receiving the test results. The corrective action plan must identify an appropriate mitigation strategy in accordance with Module 6 of the EPA's 3Ts for Reducing Lead in Drinking Water in Schools and Child Care Facilities, Revised Manual from October 2018, adopted by reference; and
(B) Implement the mitigation method within 30 days of approval by CCLD.
(7) Recordkeeping and Posting
(a) The provider must keep a copy of the most recent lead test results on-site at all times.
(b) The provider must post the most recent lead test results summary provided by CCLD in an area of the facility where the summary can be clearly viewed by parents. The provider must post the lead test results summary immediately after receiving the summary from CCLD.
(8) Providers must follow the routine practices identified in Module 6 of the EPA's 3Ts for Reducing Lead in Drinking Water in Schools and Child Care Facilities, Revised Manual from October 2018, adopted by reference, at all times.

Notes

Or. Admin. R. 414-205-0105
ELD 41-2018, temporary adopt filed 11/30/2018, effective 11/30/2018; ELD 8-2019, adopt filed 03/28/2019, effective 3/28/2019; DELC 137-2023, amend filed 12/06/2023, effective 1/1/2024

Statutory/Other Authority: ORS 329A.260

Statutes/Other Implemented: ORS 329A.260

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.