Or. Admin. R. 918-271-0040 - Mandatory Inspection Practices
(1)
Electrical inspectors shall inspect and verify the appropriateness of the size,
placement, protection and termination of the following electrical
installations. Inspectors shall note discrepancies and require correction of
code violations pursuant to OAR 918-098-1900. Physical contact is not required
to inspect the electrical installations listed below.
(a) Service entrance conductors;
(b) Service equipment;
(c) Grounding electrode and grounding
electrode conductor;
(d) Bonding;
(e) Overcurrent protection;
(f) Branch circuits;
(g) Feeders; and
(h) Underground installations.
(2) Electrical inspectors shall
test ground-fault circuit interrupter devices (GFCI) and arc-fault circuit
interrupter devices (AFCI) for functionality. Ground fault protection services
(GFP) shall be performance tested in accordance with the Oregon Electrical
Specialty Code.
(3) A final
inspection shall be requested and provided to verify all mandatory items in
sections (1) and (2) of this rule are in compliance.
(4) A final inspection shall be performed by
the inspecting jurisdiction as soon as practicable, but not later than five
working days following the date on which it is requested. Subject to the
approval of the building official, the permit holder may schedule a final
inspection prior to completion of the electrical installation in order to allow
the permit holder to be present at the time of inspection and facilitate access
to energized installations.
Notes
Stat. Auth: ORS 479.855
Stats. Implemented: ORS 455.160 & 479.855