Or. Admin. R. 918-400-0525 - Plan Review Requirements
Plans and pertinent data submitted to the department under ORS 460.048 must include proof that the elevator equipment meets the Oregon Elevator Specialty Code by providing the following information:
(1) Electrical product certification by
providing;
(a) The listing or certification
number and identification of the approved laboratory that tested the
equipment;
(b) When applicable,
date and identification of the electrical special deputy who certified the
equipment to the Oregon Elevator Specialty Code electrical requirement;
or
(c) Proof that requests for
listing or certification are pending.
(2) For the purpose of complying with plan
submittal requirements of ORS
460.048, and when applicable to
the type of equipment being proposed, a complete set of drawings must include:
(a) Elevation view;
(b) Plan view;
(c) Machine room layout (when applicable to
the type of equipment);
(d) Cab and
fixture detail;
(e) Hoistway
entrance detail; and
(f) Electrical
straight line wiring diagrams showing, as a minimum, safety circuits, normal
and final limit circuits, and door lock circuits, which must include circuitry
required by the Oregon Elevator Specialty Code.
Notes
Publications: Publications referenced are available from the agency.
Stat. Auth.: ORS 460.085
Stats. Implemented: ORS 460.048