Or. Admin. R. 918-480-0125 - Uniform Alternate Construction Standard for One and Two Family Dwellings
(1) For
lots of record created on or after July 2, 2001, if the building official
intends to allow one or more of the Uniform Alternate Construction Standards at
the time of building permit application, triggered by fire official
determinations of inadequate apparatus access or water supply, the building
official must:
(a) Provide at least a general
notification of the intent to allow such Uniform Alternate Construction
Standards; and
(b) Provide such
notification in conjunction with the approval of a land use application under
ORS 197.522.
(2) The building official, acting in
conformance with these rules, may choose to apply one or more Uniform Alternate
Construction Standards after a determination by a fire official with authority
over water supply and apparatus access, that the water supply, apparatus
access, or both are inadequate at a site. A building official shall give
consideration to advice of the State Fire Marshal or local fire official that
does not conflict with this rule, but shall retain the authority to make final
decisions. Decisions to consider a Uniform Alternate Construction Standard and
the selection of one or more Uniform Alternate Construction Standards by a
building official are final.
(3) A
Uniform Alternate Construction Standard is not a Statewide Alternate Method.
(4) Uniform Alternate Construction
Standards for One and Two Family Dwellings. Uniform Alternate Construction
Standards are limited to one or more of the following fire suppression and fire
containment components:
(a) Installation of
an NFPA Standard 13D fire suppression system;
(b) Installation of additional layers of 5/8
inch, Type-X gypsum wallboard;
(c)
Installation of fire-resistive compartmentalization of dwellings to limit the
spread of fire by use of fire-resistant building elements, components or
assemblies. Fire-resistance ratings shall be determined in accordance with the
Oregon Structural Specialty Code;
(d) Installation of fire-resistive exterior
wall covering and roofing components; or
(e) Provide fire separation containment in
accordance with the default standards as set forth in the Wildland-Urban
Interface rules adopted by the Oregon Department of Forestry (see OAR
629-044-1060).
(5) When
unique site conditions exist on a lot or when installation of a full NFPA
Standard 13D fire suppression system is impractical due to substantially
increased local system development charges, a building official may accept
installation of a partial NFPA Standard 13D fire suppression system in
conjunction with one or more of the Uniform Alternate Construction Standards
listed in subsections (4)(a) through (e) of this rule.
Notes
Stat. Auth.: ORS 455.610
Stats. Implemented: ORS 455.610
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.