Or. Admin. Code § 437-002-2310 - Materials Handling and Storage
(1) General. For general industry activities,
materials handling and storage must comply with applicable material handling
and material storage requirements in Division 2, including those in Division
2/N, except for Helicopters, which must comply with
437-002-2323. For construction
activities, materials handling and storage must comply with applicable material
handling and material storage requirements in Division 3, including those in
Division 3/N and Division 3/CC, except for Helicopters, which must comply with
437-002-2323.
(2) Materials storage near energized lines or
equipment.
(a) In areas to which access is
not restricted to qualified persons only, materials or equipment may not be
stored closer to energized lines or exposed energized parts of equipment than
the following distances, plus a distance that provides for the maximum sag and
side swing of all conductors and for the height and movement of
material-handling equipment:
(A) For lines
and equipment energized at 50 kilovolts or less, the distance is 3.05 meters
(10 feet).
(B) For lines and
equipment energized at more than 50 kilovolts, the distance is 3.05 meters (10
feet) plus 0.10 meter (4 inches) for every 10 kilovolts over 50 kilovolts.
(b) In areas restricted
to qualified employees, materials may not be stored within the working space
about energized lines or equipment.
Note to paragraph (2)(b): 437-002-2320(1) Substations; and 437-002-2321(3) Power Generation Installations; of Division 2/RR, specify the size of the working space.
Notes
Stat. Auth.: ORS 654.025(2) & 656.726(4)
Stats. Implemented: ORS 654.001 - 654.295
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.