34 Pa. Code § 47.121 - Reserved
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
There shall be at least one walk serving each of the buildings as set forth in § 47.111 (relating to scope) conforming to the following specifications:
(1) Be at least 48 inches wide with a slope no portion of which is steeper than 5%.
(2) Be of a continuing common surface uninterrupted by steps or abrupt changes in grade.
(3) Blend to a common level whenever the walk crosses other walks, driveways or parking lots.
(4) Have a level platform at the building entrance which it serves and the platform shall be at least 5 feet square if a door swings out on to the platform or toward the walk; the platform shall extend at least 1 foot beyond each side of the doorway.
(5) Have a level platform at least 3 feet deep and 5 feet wide if the door does not swing on to the platform or toward the walk; the platform shall extend at least 1 foot beyond each side of the doorway.