34 Pa. Code § 51.81 - Hazardous areas
(a) Boiler or
furnace rooms, repair or maintenance rooms, trash rooms, and rooms or spaces
used for storage of combustible materials in quantities deemed hazardous by the
Department shall be separated from other areas of the building by 1-hour
partitions, floors, and ceilings. Openings shall be protected by C label door
assemblies. Combustion and ventilation air for boiler, incinerator or heater
rooms shall be taken directly from and discharged directly to the outside
air.
(b) American Gas Association
approved gas fire forced air furnaces and space heaters; U. L. approved
electrical resistive coil heating furnaces and U. L. approved oil fired forced
air furnaces and space heaters need not be enclosed.
(c) Aisles in auditoriums shall be provided
with general illumination of not less than 0.1 foot candles at the front row of
seats and not less than 0.2 foot candles at the last row of seats, and the
illumination shall be maintained throughout the showing of motion pictures or
other projections.