20.5.1
501.0
General
Requirements
501.1
Alterations are defined as the reconfiguration of any space, the addition or
elimination of any door or window, the reconfiguration or extension of any
system, or the installation of any additional equipment. All alterations shall
comply with the requirements of Chapters 5 and 4.
Exception: As modified in Part 904.0 for historical
buildings.
501.2 Extensive
Alterations
501.2.1 The alteration of an
entire building or an entire occupancy within a building shall be considered as
a reconstruction and shall comply with the requirements of Chapter 6 for the
applicable occupancy. BFO
Exception: Alteration work that is exclusively either
plumbing, mechanical, fire protection system or electrical shall not be
considered a reconstruction, regardless of its extent.
501.2.2 When the total area of all the
rehabilitation work areas included in an alteration exceeds fifty (50%) percent
of the area of the building the work shall be considered as a reconstruction
and shall comply with the requirements of Chapter 6 for the applicable
occupancy. BFO
Exception: Rehabilitation work areas in which the
alteration work is exclusively either plumbing, mechanical, fire protection
system or electrical shall not be included in the computation of total area of
all rehabilitation work areas.
501.3 All newly constructed elements,
components and systems, including the installation of new elevators and
boilers, shall comply with the requirements of the Building Code, Mechanical
Code, Plumbing Code, NFPA 101 Life Safety Code for new construction, Electrical
Code, Boiler Safety Code, Energy Code, Elevator Code, and Accessibility Code as
applicable. BFO
Exceptions:
1.
Openable windows may be added without requiring compliance with the light and
ventilation requirements of the Building Code.
2. Newly installed electrical equipment shall
comply with the requirements of Part 504.0.
501.4 The alteration work shall not make the
building less conforming with the building, plumbing, mechanical, electrical or
fire codes of the jurisdiction, or with alternative materials, design and
methods of construction or any previously approved plans, modifications,
alternate methods or compliance alternatives, than it was before the alteration
was undertaken. BFO
501.5 Interior
Space Dimensions
501.5.1 In Groups R-1 and
R-2, when habitable spaces as defined in Chapter 2 of the Building Code are
created in previously unoccupied space, other than a kitchen, they shall not be
less than seven (7') feet in any plan dimension. B
501.5.2 In Groups R-1 and R-2, when habitable
spaces as defined in Chapter 2 of the Building Code are created in previously
unoccupied space, they shall have a ceiling height of not less than seven (7')
feet. B
Exceptions:
1.
Beams, girders, ducts or pipes spaced not less than four (4') feet on center
and projecting not more than six (6") inches below the required ceiling
height.
2. For rooms with a sloped
ceiling, the prescribed ceiling height is required for at least 35 square feet
of the floor area of the room. Any portion of the room measuring less than five
(5') feet from the finished floor to the finished ceiling shall not be
considered usable floor area and shall not be included in any computation of
the minimum area thereof.
501.5.3 In Groups R-1 and R-2, when habitable
spaces as defined in Chapter 2 of the Building Code are created in previously
unoccupied space, other than a kitchen, they shall have a net floor area of not
less than 70 square feet. B
20.5.2
502.0
Structural
Requirements
502.1 General:
Where alteration work includes installation of additional equipment that is
structurally supported by the building or reconfiguration of space such that
portions of the building become subjected to higher gravity loads as required
by Tables 1607.1 and 1607.6 of the Building Code, the provisions of this
section shall apply. B
502.2
Reduction of strength: Alterations shall not reduce the structural strength or
stability of the building, structure or any individual member thereof. B
Exception: Such reduction shall be allowed as long as the
strength and the stability of the building are not reduced to below the
Building Code requirements.
502.3 New structural members: New structural
members in alterations, including connections and anchorage, shall comply with
the Building Code unless the authority having jurisdiction specifically allows
replacement with like materials. B
502.4 Existing structural members: Existing
structural components supporting additional equipment or subjected to
additional loads based on the Building Code Tables 1607.1 and 1607.6 as a
result of a reconfiguration of spaces shall comply with 502.4.1 through
502.4.3. B
502.4.1 Gravity loads: Existing
structural elements supporting any additional gravity loads as a result of
additional equipment or space reconfiguration shall comply with the Building
Code. B
Exceptions:
1.
Structural elements whose stress is not increased by more than five (5%)
percent.
2. Buildings of Group R
occupancy with not more than five (5) dwelling units or guest rooms used solely
for residential purposes where the existing building and its alteration comply
with the conventional light-frame construction methods of the Building
Code.
502.4.2 Snow drift
loads: Any structural element of an existing building subjected to additional
loads from the effects of snow drift as a result of additional equipment shall
comply with the Building Code. B
Exceptions:
1.
Structural elements whose stress is not increased by more than five (5%)
percent.
2. Buildings of Group R
occupancy with no more than 5 dwelling units or guest rooms used solely for
residential purposes where the existing building and its alteration comply with
the conventional light-frame construction methods of the Building
Code.
20.5.3
503.0
Accessibility
503.1 Buildings undergoing an alteration that
affects the usability of the building by persons with disabilities shall comply
with Part Chapter 10. B
20.5.4
504.0
Electrical Equipment and
Wiring
504.1 All newly
installed electrical equipment and wiring relating to work done in any
rehabilitation work area shall comply with the materials and methods
requirements as defined in Part Chapter 2. B
Exception: Electrical equipment and wiring in newly
installed partitions and ceilings shall comply with all applicable requirements
of the Electrical Code.
504.2 Existing wiring in all rehabilitation
work areas in Groups A-1, A-2, and A-5 (Theater, Assembly), shall be upgraded
to meet the materials and methods requirements as defined in Part Chapter 2.
B
504.3 Service and/or feeder in
Group R-2: Service to each existing dwelling unit in any rehabilitation work
area shall be a minimum of one hundred ampere, three-wire capacity, and service
equipment shall be dead front having no live parts exposed whereby accidental
contact could be made. B
Exception: Existing service of sixty-ampere three-wire
capacity, and feeders of thirty ampere or larger two- or three-wire capacity,
shall be accepted if adequate for the electrical load being served.
504.3.1 Type "S" fuses shall be installed in
accordance with 240-53 and 240-54 of the Electrical Code when fused equipment
is used. B
504.4 In
Group R-2, when the rehabilitation work area includes any of the following
areas within a dwelling unit, the following requirements shall apply: B
504.4.1 All enclosed areas, other than
closets, kitchens, basements, garages, hallways, laundry areas and bathrooms
shall have a minimum of two duplex receptacle outlets or one duplex receptacle
outlet and one ceiling or wall type lighting outlet. B
504.4.2 Kitchen areas shall have a minimum of
two duplex receptacle outlets and a hard-wired lighting outlet. At least one of
the required duplex receptacles shall be provided to serve counter space.
B
504.4.3 Laundry areas shall have
a minimum of one duplex receptacle outlet located near the laundry equipment
and installed on an independent circuit. B
504.4.4 Ground fault circuit interruption
shall be provided on newly installed receptacle outlets if required by Section
210-8(a) Electrical Code. B
504.4.5
At least one lighting outlet shall be provided in every bathroom, hallway,
stairway, attached garage and detached garage with electric power, and to
illuminate outdoor entrances and exits. B
504.4.6 At least one lighting outlet shall be
provided in utility rooms and basements where these spaces are used for storage
or contain equipment requiring service. B
504.4.7 Clearance for electrical service
equipment shall be provided in accordance with 110-16 of the Electrical Code.
B
504.5 In Group R-2,
when the rehabilitation work area includes spaces converted into kitchen or
laundry areas, receptacle outlets in these areas shall comply with applicable
requirements of 210-52(a), (b), (c), and (f) of the Electrical Code.
B
504.6 Where the work changes an
existing space where ground fault circuit interruption is not required into a
location where such protection is required by 210-8 (dwelling units, all
bathrooms and rooftops), 555-3(boathouses), 511-10 (commercial garages), 620-85
(elevators, escalators and moving walkways), 517-20 and 517-21 (health care
facilities), 422-8(d)(3) (high-pressure spray washing appliances), 680-70
(hydromassage bathtubs), 530-73(a)(1) (motion picture and TV studios), and
680-6(a) (permanently installed pools) of the Electrical Code, existing
receptacle outlets shall be provided with such protection in accordance with
the. B
20.5.5
505.0
Plumbing
Fixtures
505.1 Where the
rehabilitation work area is more than fifty (50%) percent of the gross floor
area as defined in 1002 of the Building Code, and the occupant load will be
increased by at least twenty (20%) percent as a result of the modification,
plumbing fixtures shall be provided based on the increased occupant load in the
rehabilitation work area in quantities and locations specified in 403 of the
Plumbing Code based on the increased occupant load. B
20.5.6
506.0
Mechanical
506.1 All reconfigured spaces intended for
occupancy and all spaces converted to habitable or occupiable space in any
rehabilitation work area shall be provided with either natural or mechanical
ventilation. B
506.1.1 Natural ventilation
shall be provided by the minimum openable area to the outdoors of four (4%)
percent of the floor area being ventilated. B
506.1.2 Newly installed mechanical
ventilation systems shall comply with the requirements of Section 403 of the
International Mechanical Code. B
Exception: Existing mechanical ventilation systems shall
comply with the requirements of Section 506.2.
506.2 In mechanically ventilated spaces,
existing mechanical ventilation systems that are altered, reconfigured or
extended shall be capable of providing not less than five (5) cubic feet per
minute (cfm) per person of outdoor air and not less than fifteen (15) cfm of
ventilation air per person. B
506.3
All newly-introduced devices, equipment or operations that produce airborne
particulate matter, odors, fumes, vapor, combustion products, gaseous
contaminants, pathogenic and allergenic organisms, and microbial contaminants
in such quantities to adversely affect or impair health, or cause discomfort to
occupants shall be provided with an exhaust system in compliance with Chapter 5
of the Mechanical Code or a means of collection and removal of the
contaminants. Such exhaust shall discharge directly to an approved location at
the exterior of the building. B
20.5.7
507.0
Commercial
Kitchens
507.1 Where the
rehabilitation work area includes a commercial kitchen and the alteration
includes reconfiguration or extension of cooking equipment or the installation
of additional cooking equipment, existing grease ducts, exhaust equipment, and
kitchen hoods shall be brought into compliance with all the requirements in
Sections 506 and 507 of the Mechanical Code and enforced by the Building
Official. Jurisdiction for the suppression system for commercial cooking will
be enforced solely by the fire official in compliance with NFPA 96 as
referenced in the State Fire Code. BF
NOTE: Where the section is followed by the letter "B", "F",
or "O", the following meaning shall apply:
"B" This means that the Building Official or the Plumbing,
Mechanical or Electrical Inspector shall review the plans, issue the permit,
inspect the installation, and approve the final certificate.
"F" This means that the Fire Official shall review the
plans for approval, the Fire Official and/or the Building Official inspects the
installation, and the Fire Official observes the final test and approves the
final installation. The Building Official shall issue the permits.
"O" This would indicate another State agency approval and
inspection is needed. An explanation will indicate the agency and approvals
needed.