20.9.1
901.0
General
901.1 Historical buildings shall comply with
the provisions of this Chapter, or with the provisions of Chapters 3, 4, 5, 6
and 7, relating to their repair, renovation, alteration, reconstruction,
movement and change of occupancy. Where the owner of a historical building
wishes to use an alternative to comply with the intent of specific provisions
of this code, a written request shall be submitted to the authority having
jurisdiction in accordance 901.2. BO
901.1.1
Definition: Historical building (BFO) Any building or structure that:
a. is listed in the Rhode Island Register or
National Register of Historical Places either individually or as a contributing
building to a historical district; or
b. has been issued a Determination of
Eligibility by the Keeper of the National Register of Historical Places;
or
c. has been designated by a city
or town ordinance pursuant to R.I. Gen. Laws Chapter 45-24.1 and has been
certified by the Executive Director of the RIHPHC as contributing to the
heritage of the community; or
d.
the State Historic Preservation Officer (hereinafter the SHPO), pursuant to the
request of the owner, has determined as eligible to be listed on the National
Register of Historical Places either individually or as a contributing building
to a historical district.
901.1.2 Owner's responsibility: In order to
utilize the provisions of this Chapter, the building owner, or authorized
representative, shall contact the Rhode Island Historical Preservation and
Heritage Commission (hereinafter the RIHPHC) for written verification that the
subject building qualifies as an Historical Building as defined in 901.1.1. The
building owner shall further equip the subject building with an approved fire
alarm system installed in accordance with the provisions of R.I. Gen. Laws
Chapter 23-28.25, as amended. BFO
901.1.3 Modifications to historical
buildings: This chapter shall only apply to the historically significant
spaces, features, or fabric of the building as certified by the Executive
Director of the RIHPHC. In order to utilize the provisions of this Chapter, the
building owner shall maintain the historical interior of the subject building
unless such proposed modifications are determined to be incidental by the
Executive Director. The Executive Director shall so advise the building and
fire officials, in writing, prior to the commencement of the plan review.
BFO
901.1.4 Appeals: A building
owner, utilizing the provisions of this chapter, shall notify Executive
Director of the RIHPHC upon the filing of an appeal of any of the provisions of
this Chapter with the Joint Committee on the Rehabilitation Building and Fire
Code for Existing Buildings and Structures. BF
901.2 Alternatives: Where the owner of a
historical building wishes to use an alternative to comply with the intent of
the specific provisions of this Code, a written request shall be submitted to
the authority having jurisdiction. Such request shall identify all
non-conformities with the requirements of this Code and shall include: a
statement of the requirements of this Code from which an alternative is sought,
a statement of the manner in which strict compliance with the provisions of
this Code would result in practical difficulties or would detract from the
historical character of the building and a statement of feasible alternatives
to the requirements of this Code that would adequately protect the health,
safety, and welfare of the intended occupants and of the public generally. If
in the opinion of the local building or fire official insufficient information
has been provided in the request, the officials shall have the authority to
require the submission of additional information, including an evaluation
prepared by a registered architect, licensed engineer, or fire protection
engineer for the appropriate subject matter. A copy of the request shall be
submitted to the Executive Director of the RIHPHC including any additional
information required by the authority having jurisdiction. In acting on the
request, the authority having jurisdiction shall consider comments, if any,
from the RIHPHC. BFO
901.3
Accessibility requirements: The accessibility requirements contained in Chapter
10 shall apply to historical buildings undergoing renovations, alterations,
reconstruction or a change of occupancy. If the historical features or
historical character of the building is adversely affected, and the building is
required to comply with ADAAG by the provisions of Chapter 10, then
substantially equivalent alternative provisions of accessibility shall be
permitted, in accordance with Chapter 10. B
901.4 Museums: When a historical building is
used as a museum, the building shall be classified as use Group B (Business)
provided that the building complies with the following conditions:
1. A limit on occupancy, not to exceed 50, is
set by the authority having jurisdiction based on egress capacity and travel
distance using the following parameters: F
a.
For buildings with a single means of egress, occupancy shall be limited to the
first and second floors, and the travel distance shall not exceed 75 feet.
F
b. Two means of egress shall be
required from all floors above the second floor where occupancy is permitted.
F
2. There is
supervision by a guide or other employee or volunteer knowledgeable in the
emergency exiting procedures during all times that the building is occupied by
visitors. F
901.5 Flood
hazard areas: For historical buildings or structures located in whole or in
part in flood hazard areas, work on the building or structure shall be
permitted, provided all of the following are met:
1. If a historical building will continue to
be listed or eligible for listing as a historical building, then work proposed
to be undertaken is not considered to be a substantial improvement. B
2. If all work proposed constitutes
substantial improvement, including repairs, work required due to a change of
occupancy, and alterations, then the existing building shall comply with the
flood hazard provisions of the Building Code. B
3. The proposed work is the minimum necessary
to comply with life and safety requirements of this Code. B
4. A variance to the flood provisions of this
code is granted by the Board of Appeals. B
20.9.2
902.0
Repairs
902.1 Repairs to any portion of a historical
building or structure shall be permitted to be made with original or like
materials and original methods of construction, subject to the provisions of
this Chapter. B
20.9.3
903.0
Relocated
Buildings
903.1
Construction: Any repair, renovation, alteration, reconstruction, movement and
change of use of relocated historical structures shall comply with the
requirements of this Chapter. B
903.2 Foundations: Foundations of relocated
historical buildings shall comply with Chapter 18 of the Building Code.
Relocated historical buildings shall otherwise be considered as historical
buildings for the purposes of this Code. B
903.3 Relocated historical buildings and
structures shall be so sited that fire separation distance and opening
protectives comply with the requirements of paragraphs 704.5 and 704.8 of the
Building Code. B
20.9.4
904.0
Repair, Renovation, Alteration or
Reconstruction
904.1 General:
Historical buildings undergoing repair, renovation, alteration or
reconstruction shall comply with all of the applicable requirements Chapters 3,
4, 5 and 6, except as specifically permitted in this Chapter. BF
904.2 Replacement: Replacement of existing or
missing features using original or like materials shall be permitted. Partial
replacement for repairs that match the original in configuration, height and
size shall be permitted. Such replacements shall not be required to meet the
materials and methods requirements in 401.2. B
Exception: Replacement glazing in hazardous locations shall
comply with 302.2.
904.3
Roof Covering: The existing type of roof covering shall be permitted to be
continued and replaced with the same materials if the historical materials are
documented to the satisfaction of the local jurisdiction. B
904.4 Means of egress: In buildings protected
throughout by a fire alarm system installed in accordance with 602.6, existing
door openings, window openings intended for emergency egress and corridor and
stairway widths of less than those that would be acceptable for non-historical
buildings under this code shall be approved, provided that in the opinion of
the local jurisdiction there is sufficient width and height for a person to
pass through the opening or traverse the exit and that the capacity of the exit
system is adequate for the occupant load or where other operational controls to
limit occupancy are approved by the authority having jurisdiction. F
904.4.1 Paneled doors: Existing paneled doors
in corridor walls required to have a fire rating of one hour will be allowed to
remain if fitted with smoke seals provided that the egress system of the entire
building is equipped with an approved sprinkler system, with a head located on
each side of the door. If the above sprinkler system is not otherwise required,
it may be domestically supplied provided that it is properly engineered to the
satisfaction of the authority having jurisdiction. Alternative methods of
establishing an approximate fire rating of twenty (20) minutes for the above
doors may be approved by the authority having jurisdiction in accordance with
certifications provided by nationally recognized testing facilities.
F
904.4.2 Transoms: In all
buildings of Group R-2, all transoms in corridor walls in rehabilitation work
areas shall be either glazed with 1/4 inch wired glass set in metal frames
or other glazing assemblies having a fire protection rating as required for the
door and permanently secured in the closed position or sealed with materials
consistent with the corridor construction. F
Exception: In buildings of Group R-2, where the egress
system is fully sprinklered, existing transoms in corridors and other fire
rated walls may be maintained if fixed in the closed position. A sprinkler head
shall be installed on each side of the transom. If the above sprinkler system
is not otherwise required, it may be domestically supplied provided that it is
properly engineered to the satisfaction of the authority having
jurisdiction.
904.4.3 Dead
end corridors: In other than use group A, existing dead-end corridors in any
rehabilitation work area shall not exceed 35 feet. Newly constructed dead-end
corridors shall comply with NFPA 101, Life Safety Code, for new buildings. F
Exceptions:
Where existing dead-end corridors of greater length are
permitted by NFPA 101, Life Safety Code, for existing buildings.
In other than Group A, the maximum length of an existing
dead-end corridor shall be 50 feet in buildings equipped throughout with an
automatic sprinkler system installed in accordance with Fire Safety
Code.
904.5 Door
swing: Existing front or main entry doors need not swing in the direction of
exit travel when serving fewer than 50 persons, or if official having
jurisdiction determines that other approved exits have sufficient capacity to
serve the total occupant load. F
904.6 Interior finishes: The existing
finishes of walls and ceilings shall be accepted where it is demonstrated that
it is the historical finish. F
Exception: Finishes in exit ways shall have a flame-spread
classification of Class C or better in accordance with NFPA 101, Life Safety
Code for new construction. Existing nonconforming materials shall be surfaced
with an approved fire-retardant paint or finish unless the building is equipped
throughout with an automatic fire sprinkler system installed in accordance with
NFPA 13, Standard for Installation of Sprinkler Systems.
904.7 Stairway Enclosure
904.7.1 Stairway enclosures may be omitted in
a historical building where such stairway serves only one adjacent floor.
F
904.7.2 In buildings of three
stories or less, exit enclosure construction shall limit the spread of smoke by
the use of tight fitting doors and solid elements. Such elements need not have
a fire rating. F
904.7.3 Riser
height and tread width: When stairs are replaced or repaired, the existing or
original riser height and tread width shall be permitted to remain. F
904.7.4 Approved sprinkler systems or other
solutions may be considered in lieu of enclosure of a stairway. F
904.8 One-hour fire-resistive
assemblies: Where one-hour fire-resistive construction is required by this code
in buildings protected throughout by a fire alarm system installed in
accordance with 602.6, one-hour construction need not be provided regardless of
construction or occupancy where the existing wall and ceiling finish is wood
lathe and plaster that is in good condition and egress system doors maintain an
approximate fire rating of at least twenty (20) minutes or are otherwise
protected as outlined in 904.4.1 above. F
904.8.1 Stairway railing: Historically
significant stairways shall be accepted without complying with the handrail and
guardrail requirements. Existing handrails and guards shall be permitted to
remain provided they are not structurally dangerous. Stairway railings may be
reconstructed with handrails matching the original handrails. F
904.8.2 Guardrails: Guardrails of at least 30
inches in height shall be accepted and the existing or original baluster
spacing permitted to remain where the vertical drop does not exceed 48 inches.
Historically significant guardrails of lesser dimension, deemed not to be
hazardous by the authority having jurisdiction, shall also be allowed to
remain. F
904.8.3 One-hour
fire-resistive construction may be omitted when existing building is fully
sprinklered. F
904.8.4 Occupancy
separations of more than one hour may be reduced to one-hour fire-resistive
construction with all openings protected by not less than 3/4 hour
fire-resistive assemblies of the self-closing or automatic-closing type when
building is fully sprinklered. F
904.8.5 Winders: Existing winders that are in
good structural repair will be permitted to remain in R-2 occupancies, or in
buildings with an occupant load less than 50, or if there is a second approved
means of egress, or if the building is protected throughout with an approved
fire alarm system. F
904.9 Exit signs: The local jurisdiction
shall accept alternate exit sign or egress path marking location where such
signs or markings would have an adverse effect upon the historical character.
Alternative signs shall identify the exits and egress path. F
904.10 Sprinkler alternative: After review of
the report specified in 901.2, every historical building which does not conform
to the construction requirements specified in other chapters of this Code for
the occupancy or use and which, due to conditions not addressed in this Chapter
in the opinion of the local fire official constitutes a fire safety hazard,
shall be equipped throughout with an automatic sprinkler system installed in
accordance with NFPA 13, Standard for Installation of Sprinkler Systems.
However, such automatic sprinkler system shall not be used to substitute for,
or act as an alternate to, the required number of exits from any facility.
F
20.9.5
905.0
Change of
Occupancy
905.1 General:
Historical buildings undergoing a change of occupancy shall comply with the
applicable provisions of Chapter 7 except as specifically permitted in this
Chapter. Where Chapter 7 requires compliance with specific requirements of
Chapter 6, and where those requirements are subject to Exceptions in 904.0, the
same Exceptions shall apply in this section. BF
905.2 Building area: The allowable floor area
for historical buildings undergoing a change of occupancy shall be permitted to
exceed the allowable areas specified in Chapter 7 by fifty (50%) percent.
B
905.3 Location on property:
Historical structures undergoing a change of use to a higher hazard category in
accordance with 702.4.1 may use alternative methods to comply with the
fire-resistance and exterior opening protective requirements. Such alternatives
shall comply with 901.2. B
905.4
Roof covering: Regardless of occupancy or use group, roof-covering materials
not less than Class C shall be permitted where a fire-retardant roof covering
is required. B
905.5 Means of
egress: In buildings protected throughout by a fire alarm system installed in
accordance with 602.6 or an automatic suppression system in accordance with
NFPA 13 or NFPA 13R, existing door openings, window openings intended for
emergency egress and corridor and stairway widths of less than those that would
be acceptable for non-historical buildings under this code shall be approved,
provided that in the opinion of the local jurisdiction there is sufficient
width and height for a person to pass through the opening or traverse the exit
and that the capacity of the exit system is adequate for the occupant load, or
where other operational controls to limit occupancy are approved by the local
jurisdiction. F
905.6 Door swing:
When approved by the local jurisdiction, or when the occupant load is less than
50, the existing front or main entry doors need not swing in the direction of
exit travel, provided other approved exits having sufficient capacity to serve
the total occupant load are provided. F
905.7 Transoms: In corridor walls required to
be fire rated by this code, existing transoms may be maintained if fixed in the
closed position and fixed wired glass set in a steel frame or other approved
glazing shall be installed on one side of the transom. F
Exception: Transoms conforming to 904.4.2 shall be
accepted.
905.8 Finishes:
Where finish materials are required to have a flame-spread classification of
Class C or better in accordance with NFPA 101, Life Safety Code for new
construction, existing nonconforming materials shall be surfaced with an
approved fire-retardant paint or finish. F
Exception: Existing nonconforming materials need not be
surfaced with an approved fire-retardant paint or finish when the building is
equipped throughout with an automatic fire suppression system installed in
accordance with NFPA 13, and the nonconforming materials can be substantiated
as historical in character.
905.9 One-hour fire-resistive assemblies: In
buildings protected throughout by a fire alarm system installed in accordance
with 602.6 or an automatic suppression system in accordance with NFPA 13 or
NFPA 13R, where one-hour fire-resistive construction is required by this code,
it need not be provided regardless of construction or occupancy where the
existing wall and ceiling finish is wood lathe and plaster or provides an
approximate twenty (20) minute rating. F
905.10 Stairs and railings: Existing
stairways shall comply with the requirements of this Code. The local
jurisdiction shall grant alternatives for historically significant stairways
and railings if alternative stairways are found to be acceptable or if judged
as meeting the intent of this Code. Existing open stairways shall comply with
904.10. F
905.11 Exit signs: The
local jurisdiction may accept alternate exit sign locations where such signs
would have an adverse effect upon the historical character. Such signs shall
identify the exits and exit path. F
905.12 Exit stair live load: Existing
historical stairways in buildings changed to Groups R-1 and R-2 shall be
accepted where it can be shown that the stairway can support 75 pounds per
square foot live load. B
905.13
Natural light: When it is determined by the local jurisdiction that compliance
with the natural light requirements of 705.1 will lead to loss of historical
character and/or historical materials in the building, the existing level of
natural lighting shall be considered acceptable. B
905.14 Energy Conservation: Historical
buildings shall comply with the requirements of 706.0 to the fullest extent
possible without altering the historical fabric of the building. B
NOTE: Where the section is followed by the letter "B", "F",
or "O", the following meaning shall apply:
"B" This means that the Building Official or the Plumbing,
Mechanical or Electrical Inspector shall review the plans, issue the permit,
inspect the installation, and approve the final certificate.
"F" This means that the Fire Official shall review the
plans for approval, the Fire Official and/or the Building Official inspects the
installation, and the Fire Official observes the final test and approves the
final installation. The Building Official shall issue the permits.
"O" This would indicate another State agency approval and
inspection is needed. An explanation will indicate the agency and approvals
needed.