510 R.I. Code R. 510-RICR-00-00-8.5 - Chapter 3[CE] Climate Zones
Delete section C301 in its entirety and substitute the following:
Section C301 Climate Zones
Table C301.1 Delete and substitute the following:
|
Table 301.1 Exterior Design Conditions |
Value |
Value |
|
Climate zone |
Providence County |
All others |
|
Winter, design dry-bulb (degree F) |
0 |
5 |
|
Summer, design dry-bulb |
87 |
89 |
|
Summer design wet-bulb |
71 |
73 |
|
Degree days heating |
6831 |
5950 |
|
Degree days cooling |
371 |
811 |
Delete Figure C301.1 and Substitute the following: Figure C301.1
Click here to view image
Delete without substitution section C301.2, C301.3 and C301.4
Delete without substitution Table C301.3(1)
Delete table C301.3(2) and substitute the following
TABLE C301.3(2)
RHODE ISLAND CLIMATE ZONE DEFINITION
|
Zone Number |
THERMAL CRITERIA |
|
|
IP UNITS |
SI UNITS |
|
|
5 |
5400, HDD65 °F<= 7200 |
3000 < HDD18 °C <= 4000 |