1. Drilling.
a. The drilling process or use of drilling
fluid additives shall not contaminate any aquifer.
b. Water used in the drilling process shall
be obtained from a source that will not result in chemical or biological
contamination of any aquifer. Water taken directly from ponds, lakes, streams
or other surface water sources shall not be used.
2. Grouting.
a. The diameter of the drilled hole shall be
large enough to allow for a minimum of 1.5 inches of annular space on all sides
of the casing for forced injection of grout through a tremie pipe.
b. Grout is to be composed of neat cement, a
bentonite cement mixture, or high solids sodium bentonite grout.
(1) Neat cement grout shall be composed of
Class A, Type I Portland Cement mixed with not more than seven (7) gallons of
clean water per bag (one cubic foot or 94 pounds) of cement with a density of
15 to 16 pounds per gallon, or to manufacturer's specifications.
(2) Bentonite-cement grout shall be composed
of powdered bentonite (less than 5% by weight) mixed at not more than 8 gallons
of water to the bag, with a density of 14 to 15 pounds per gallon, or to
manufacturer's specifications.
(3)
High solids sodium bentonite grout shall have a minimum of 20% solids and be
mixed per manufacturer's specifications with water and/or other required
additives.
c. Grout
shall fill the entire annular space from a minimum depth of twenty feet from
the land surface at the time of well completion, unless otherwise approved by
the Department. While the Department discourages wells less than 20 feet to be
used for human consumption, it is recognized that due to differing
hydrogeologic conditions across the state, some wells may need to be screened
or completed at depths less than 20 feet to obtain potable water in the shallow
aquifer. Therefore, wells less than 20 feet in depth, but no less than 15 feet
in depth, are allowed. In these cases, in Type II and Type III wells, grout
shall extend from one foot above the screen to the land surface and, in Type I
and Type IV wells, the entire annular space shall be filled with grout. Any
other minimum well depths may only be allowed per the variance procedure
outlined in this regulation.
d. All
grouting shall be accomplished using forced injection to emplace the grout.
When emplacing the grouting material, the tremie pipe shall be lowered to the
bottom of the zone to be grouted. The tremie pipe shall be kept full
continuously from start to finish of the grouting procedure, with the discharge
end of the tremie pipe being continuously submerged in the grout until the zone
to be grouted is completely filled.
e. Wells shall be grouted in-place within
five (5) days after borehole completion.
f. When high solids sodium bentonite grouts
are used, a vapor barrier at the land surface at least the width of the annular
space made of suitable materials, as approved by the Department, such as native
soils, gravel, sand, or thermoplastic material, is required for public safety
and structural stability of the well.
3. Plumbness and Alignment.
Wells shall be constructed sufficiently plumb and straight so
as to cause no interference with intended use.
4. Development.
a. Wells shall be properly developed. In a
screened well, development shall be by a method that ensures that water is
forced to flow into and out of the screen.
b. Development shall be complete when the
well produces water typical of the aquifer being utilized.
5. Well Tested for Yield.
If a yield test is conducted, it shall be by a standard method
and accurately measure flow. Results are to be included with the well record to
be sent to the Department.
6. Backflow Prevention.
Approved backflow prevention devices are required on all wells
that utilize a chemical feed system for any purpose other than water treatment.
The backflow prevention device shall be installed so as to preclude any direct
pathway for any contaminant to enter an underground source of drinking
water.
7. Disinfection.
All individual residential wells and irrigation wells shall be
disinfected upon well completion. The well shall also be disinfected upon any
well maintenance, repair, pump repair, pump installation, or testing.
Disinfectants shall be placed in the well in order to provide a chlorine
residual from 50 ppm (milligrams per liter) to 250 ppm for a minimum of four
hours before being flushed from the well. The method of chlorination shall be
one that insures that the chlorine is uniformly distributed in the well. The
well shall be flushed sufficiently after disinfection to remove the
disinfectant and to condition the well for use.
8. Well Identification.
These wells shall be properly labeled with an identification
plate immediately upon well completion. The identification plate shall be
constructed of a durable, weatherproof, rustproof, material. The identification
plate shall be permanently secured to the well casing or enclosure floor around
the casing where it is readily visible. The identification plate shall be
permanently marked to show:
a. Company
name and certification number of the driller who installed the well;
b. Date well was completed;
c. Total depth (feet); and,
d. Casing depth (feet).
9. Materials.
a. Casing.
(1) Casing may be driven, lowered, or
installed in any manner that will effect a continuous water tight and plumb
installation.
(2) A well point,
drive pipe, or drive shoe shall be structurally suitable to prevent rupture
during the driving of the casing.
(3) Permanent well casing shall be new,
seamless, or electric-resistance welded steel or galvanized pipe or
thermoplastic pipe.
(4) Casing
shall have watertight joints that shall be glued or threaded and coupled if
plastic, or electrically welded or threaded and coupled with heavy
recessed-type couplings of steel, if metal.
(5) Casing shall be of standards classified
by the American Society for Testing and Materials (ASTM) and shall be NSF
approved.
(6) New steel casing
which bears mill markings and which conforms to the standard and specifications
ASTM A-53, ASTM A-120, or American Petroleum Institute (API-5L) for water well
pipe shall be used.
(7) Casing
weighing less than "standard weight" steel pipe is allowed by the Department
for water wells when the following requirements are met:
(a) The casing shall have a minimum nominal
wall thickness of 0.188 inches;
(b)
Casing meets the requirements of American National Standards Institute and ASTM
(ANSI/ASTM) for water well casing.
(8) In consolidated formations, the well
casing shall be set into the formation so as to provide a watertight seal
between the casing and the top of the consolidated formation.
(9) In unconsolidated material, well casing
shall be set into the first confining layer or to twenty feet, whichever is
greater.
(10) Casing installed
shall extend a minimum of one foot above the land surface at the time of
construction. If an above ground pump is used, the casing may extend less than
one foot above the land surface or below the land surface with a protective
wellhead cover that allows access to the wellhead if the piping connecting the
well casing to the pump is glued or threaded and is watertight.
(11) Thermoplastic casing may be used
provided the casing:
(a) Conforms to
requirements of American National Standards Institute/American Society of
Testing and Materials (ANSI/ASTM), specification F480-77 for thermoplastic
water well casing pipe and couplings made in standard dimension ratios
(SDR);
(b) Has minimum wall
thickness and tolerances to meet or exceed requirements for SDR 26
thermoplastic water well casing pipe and couplings made in standard dimension
ratios;
(c) Has wall thickness and
tolerances to meet or exceed requirements for Schedule 40 thermoplastic water
well casing pipe for nominal sizes three inches or smaller;
(d) Can be installed without interference
from formational material or other objects that may cause physical damage to
the casing during emplacement.
b. Screens.
(1) The well, if constructed to obtain water
from an unconsolidated formation, shall be equipped with a screen that will
prevent the entrance of formation material into the well after the well has
been developed and completed.
(2)
The well screen shall meet standards classified by the American Society for
Testing and Materials (ASTM) and shall be National Sanitation Foundation (NSF)
approved material, and shall be of a strength to satisfactorily withstand
chemical or physical forces applied to it during and after
installation.
(3) Thermoplastic
well screens shall:
(a) Have a minimum wall
thickness and tolerance which meet or exceed requirements for schedule 40
thermoplastic water well casing pipe for nominal sizes three inches and
smaller;
(b) Have a minimum wall
thickness and tolerance which meet or exceed requirements for SDR 26
thermoplastic water well casing for nominal sizes greater than three inches,
and;
(c) Be installed in wells
without interference from formation material or other objects that may cause
physical damage during emplacement and do not exceed manufacturers
recommendations for depth placement.
(d) Multi-screened wells shall not connect
aquifers or zones that have documented differences:
(1) In water quality that would result in
contamination of any aquifer or zone such that any State Primary Drinking Water
standard is exceeded;
(2) In static
water levels that would result in depletion of water from any aquifer or zone,
or significant loss of head in any aquifer or zone.
(e) The bottom of the lower-most well screen
shall be plugged or capped.
10. Filter Pack.
When a filter pack is used, the following criteria shall
apply:
a. The filter pack shall be
composed of uniformly sized, quartz sand or gravel being free from clay, silt,
or other deleterious material.
b.
The filter pack shall be installed using a method that ensures placement into
the annular space around the screens.
c. The filter pack shall be disinfected prior
to or during installation.
d. The
filter pack shall not connect aquifers or zones that have documented
differences:
(1) In water quality that would
result in contamination of any aquifer or zone such that any State Primary
Drinking Water standard is exceeded;
(2) In static water levels that would result
in depletion of water from any aquifer or zone, or significant loss of head in
any aquifer or zone.
11. Sanitary Seal.
a. A sanitary seal shall be provided on the
top of the well casing.
b. If a
vent is used, it shall be of a type to prevent the entrance of contaminants,
insects, or rainwater into the well.
12. Reporting.
a. The Water Well Record Form 1903, or other
approved form, shall be completed and submitted to the Department by the
contractor within thirty days after well completion. In addition to the water
well record, the driller shall submit additional information as available such
as chemical or bacterial results, if taken, and pumping information.
b. A Form 1903 shall also be submitted for
individual residential and irrigation wells that are abandoned.
13. Operations and Maintenance.
a. All wells shall be operated and maintained
at all times in such a manner so as to protect underground sources of drinking
water from contamination and to protect public health. The well owner may be
required to provide additional security against vandalism as appropriate. The
well owner is responsible for routine maintenance and operation of the
well.
b. The well driller is
responsible for ensuring wells are constructed in accordance with this
regulation. Once the well driller has provided a properly constructed well to
the well owner, the well driller is not responsible for normal wear of the
well.
c. A sampling spigot shall be
installed on the wellhead.
14. Abandonment.
a. When any well is removed from service or
prior to putting in service, the well shall be sealed with a watertight cap or
seal. The well shall be maintained such that it is not a source or channel of
contamination while it is not in service. Until a well is abandoned, all
provisions for protection of the water against contamination and for
maintaining sanitary conditions around the well shall be carried out to the
same extent as though the well were in routine use. This goal shall be met when
conducting repair or maintenance on the well, surrounding structures, or
pumps.
b. Any well removed from
service for longer than thirty-six months shall be permanently abandoned unless
a variance from the Department is requested.
c. Any well that acts as a source of
contamination shall be repaired or permanently abandoned immediately after
receipt of notice from the Department.
d. Abandonment shall be by forced injection
of grout or pouring through a tremie pipe starting at the bottom of the well or
fill material and proceeding to the surface in one continuous
operation.
e. When an individual
residential well or irrigation well is permanently abandoned, at a minimum, the
well may be filled with either bentonite-cement, neat cement, 20% high solids
sodium bentonite grout, sand, or gravel to no closer than twenty feet below the
ground surface. The remaining twenty feet to the ground surface shall be filled
with neat cement, bentonite-cement, or 20% high solids sodium bentonite
grout.