S.C. Code Regs. § 61-84.2000.2001 - Alarms
A. Facilities with
six (6) or more licensed beds shall have a partial, manual, automatic,
supervised fire alarm system. The facility shall arrange the system to transmit
an alarm automatically to a third party. The alarm system shall notify by
audible and visual alarm all areas and floors of the building. The alarm system
shall shut down central recirculation systems and outside air units that serve
the area(s) of alarm origination as a minimum.
B. All fire, smoke, heat, sprinkler flow, and
manual fire alarming devices must be connected to and activate the main fire
alarm system when activated.