S.C. Code Regs. § 8-1105 - NEC Article 210.12(A) Dwelling Units
All 120-volt, single-phase, 15- and 20- ampere branch circuits supplying outlets or devices installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by any of the means described in (1) through (6) below:
(1) A listed combination-type arc-fault
circuit interrupter installed to provide protection of the entire branch
circuit.
(2) A listed
branch/feeder-type AFCI installed at the origin of the branch-circuit in
combination with a listed outlet branch-circuit-type arc-fault circuit
interrupter installed at the first outlet box on the branch circuit. The first
outlet box in the branch circuit shall be marked to indicate that it is the
first outlet of the circuit.
(3) A
listed supplemental arc protection circuit breaker installed at the origin of
the branch circuit in combination with a listed outlet branch-circuit type
arc-fault circuit interrupter installed at the first outlet box on the branch
circuit where all of the following conditions are met:
a. The branch-circuit wiring shall be
continuous from the branch-circuit overcurrent device to the outlet
branch-circuit arc-fault circuit interrupter.
b. The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet shall not
exceed 15.2m (50 ft) for a 14 AWG conductor or 21.3m (70 ft) for a 12 AWG
conductor.
c. The first outlet box
in the branch circuit shall be marked to indicate that it is the first outlet
of the circuit.
(4) A
listed outlet branch-circuit-type arc-fault circuit interrupter installed at
the first outlet on the branch circuit in combination with a listed
branch-circuit overcurrent protective device where all of the following
conditions are met:
a. The branch-circuit
wiring shall be continuous from the branch-circuit overcurrent device to the
outlet branch-circuit arc-fault circuit interrupter.
b. The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet shall not
exceed 15.2 m (50 ft) for a 14 AWG conductor or 21.3 m (70 ft) for a 12 AWG
conductor.
c. The first outlet box
in the branch circuit shall be marked to indicate that it is the first outlet
of the circuit.
d. The combination
of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall
be identified as meeting the requirements for a system combination-type AFCI
and shall be listed as such.
(5) If metal raceway, metal wireways, metal
auxiliary gutters, or Type MC, or Type AC cable meeting the applicable
requirements of 250.118, with metal boxes, metal conduit bodies, and metal
enclosures are installed for the portion of the branch circuit between the
branch-circuit overcurrent device and the first outlet, it shall be permitted
to install a listed outlet branch-circuit-type AFCI at the first outlet to
provide protection for the remaining portion of the branch circuit.
(6) Where a listed metal or nonmetallic
conduit or tubing or Type MC cable is encased in not less than 50 mm (2 in.) of
concrete for the portion of the branch circuit between the branch-circuit
overcurrent device and the first outlet, it shall be permitted to install a
listed outlet branch-circuit-type AFCI at the first outlet to provide
protection for the remaining portion of the branch circuit.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.