S.C. Code Regs. § 8-1249 - IRC R3901.4.2.1 Islands and peninsular countertops and work spaces
Receptacle outlets shall be installed in accordance with the following: [210.52(C)(2)]
1. At least
one receptacle outlet shall be provided for the first 6 feet
(0.84m2), or fraction thereof, of the countertop or
work surface. A minimum of two receptacle outlets shall be provided for any
island over 6 feet long.
2. At
least one receptacle outlet shall be located within 2 feet (600 mm) of the
outer end of a peninsular countertop or work surface. Additional receptacle
outlets shall be permitted to be located as determined by the installer,
designer or building owner. The location of the receptacle
outlets shall be in accordance with Section E3901.4.3
[210.52(C)(2)(b)].