S.C. Code Regs. § 8-1251 - IRC E3902.5 Basement receptacles
125-volt receptacles installed in basements and supplied by single phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(5)].
Exceptions:
1. A
receptacle supplying only a permanently installed fire alarm or burglar alarm
system. A receptacle installed in accordance with this exception shall not be
considered as meeting the requirement of Section E3901.9. Receptacles installed
in accordance with this exception shall not be considered as meeting the
requirement of Section E3901.9 [210.8(A)(5) Exception].
2. Receptacles in walk-out basements are
excluded from this requirement.