S.C. Code Regs. § 8-1252 - IRC R3902.17 Arc Fault Circuit Interrupted Protection
In areas other than kitchen and laundry areas, branch circuits that supply 120-volt single-phase, 15- and 20-ampere outlets installed in family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets, hallways, and similar rooms or areas shall be protected by any of the following: [210.12(A)]
1. A listed combination-type arc-fault
circuit-interrupter, installed to provide protection of the entire branch
circuit. [210.12(A)(1)]
2. A listed
branch/feeder-type AFCI installed at the origin of the branch-circuit in
combination with a listed outlet branch-circuit-type arc-fault
circuit-interrupter installed at the first outlet box on the branch circuit.
The first outlet box in the branch circuit shall be marked to indicate that it
is the first outlet of the circuit. [210.12(A)(2)]
3. A listed supplemental arc-protection
circuit breaker installed at the origin of the branch circuit in combination
with a listed outlet branch-circuit-type arc-fault circuit interrupter
installed at the first outlet box on the branch circuit where all of the
following conditions are met:
3.1. The
branch-circuit wiring shall be continuous from the branch-circuit overcurrent
device to the outlet branch-circuit arc-fault circuit-interrupter.
3.2. The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet shall not
exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3 m) for 12 AWG
conductors.
3.3. The first outlet
box on the branch circuit shall be marked to indicate that it is the first
outlet on the circuit. [210.12(A)(3)].
4. A listed outlet branch-circuit type
arc-fault circuit interrupter installed at the first outlet on the branch
circuit in combination with a listed branch-circuit overcurrent protective
device where all of the following conditions are met:
4.1. The branch-circuit wiring shall be
continuous from the branch-circuit overcurrent device to the outlet
branch-circuit arc-fault circuit-interrupter.
4.2. The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet shall not
exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3m) for 12 AWG
conductors.
4.3. The first outlet
box on the branch circuit shall be marked to indicate that it is the first
outlet on the circuit.
4.4. The
combination of the branch-circuit overcurrent device and outlet branch-circuit
AFCI shall be identified as meeting the requirements for a system
combination-type AFCI and shall be listed as such.