S.D. Admin. R. 74:56:03:12 - Secondary containment required for existing AST systems
Secondary containment systems required in accordance with ยง 74:56:03:04 for existing AST systems located at facilities with a total capacity of 250,000 gallons or more shall consist of the following:
Plans and specifications for the secondary containment system must be submitted for approval by the department at least 30 days before construction of the system.
Aboveground and underground piping from the AST is exempt from these requirements provided that pressure tests are performed every five years to demonstrate the piping's integrity.
Notes
General Authority: SDCL 34A-2-93, 34A-2-101.
Law Implemented: SDCL 34A-2-100, 34A-2-101.