S.D. Admin. R. 74:56:03:13 - Overfill control
Overfill control is required on all AST systems to prevent inadvertent or accidental releases during filling. The requirements are as follows:
(1) All owners or operators must ensure that
releases due to overfills do not occur. The owners or operators must ensure
that the volume available in the tanks will contain the volume of regulated
substance to be transferred to the tanks; and
(2) Overfill control required in accordance
with ยง
74:56:03:04 for AST systems shall
utilize one or more of the following overfill prevention devices or methods;
(a) Tanks gauged at frequent intervals by
personnel during regulated substance transfer who are in communication with the
supplier so that flow may be shut down or diverted;
(b) Tanks equipped with high level detection
devices independent of other gauging equipment. Alarms shall be located either
on-site or remote so that the flow of regulated substance may be stopped or
diverted; or
(c) An equivalent
device or system, approved by the department, designed to prevent releases due
to overfills.
Notes
General Authority: SDCL 34A-2-93.
Law Implemented: SDCL 34A-2-100.