S.D. Admin. R. 74:56:03:17 - Inspections
Routine inspection of the AST system must be performed as follows to ensure proper performance:
(1) At a
minimum, all owners or operators must perform the following inspections:
(a) Take daily inventory measurements of
regulated substance levels except on weekends and holidays. Take weekly
inventory measurements of regulated substance levels if there is a secondary
containment facility;
(b) Perform
monthly reconciliations of inventory records;
(c) Inspect all overfill devices, release
detection instruments, gauges, valves, and operation of all components of
cathodic protection systems at least biannually not to exceed 7 1/2 months
between inspections; and
(d)
Visually inspect all internal components of ASTs not exempted in §
74:56:03:05, according to the
schedule established in §
74:56:03:05. Owners or operators
of an AST which cannot comply with this requirement may request a variance
pursuant to §
74:56:03:06;
(2) All owners or operators of AST systems
must maintain detailed records of all inspections;
(3) Any defects in the AST system detected in
the course of any inspections must be repaired or replaced in accordance with
§
74:56:03:16. Any releases detected
must be reported in accordance with §
74:56:03:21 and corrective action
implemented in accordance with §
74:56:03:22.
Notes
General Authority: SDCL 34A-2-93, 34A-2-101.
Law Implemented: SDCL 34A-2-100, 34A-2-101.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.