S.D. Admin. R. 74:56:03:17 - Inspections
Routine inspection of the AST system must be performed as follows to ensure proper performance:
(1) At a minimum, all owners or operators must perform the following inspections:
(a) Take daily inventory measurements of regulated substance levels except on weekends and holidays. Take weekly inventory measurements of regulated substance levels if there is a secondary containment facility;
(b) Perform monthly reconciliations of inventory records;
(c) Inspect all overfill devices, release detection instruments, gauges, valves, and operation of all components of cathodic protection systems at least biannually not to exceed 7 1/2 months between inspections; and
(d) Visually inspect all internal components of ASTs not exempted in §
74:56:03:05, according to the schedule established in §
74:56:03:05. Owners or operators of an AST which cannot comply with this requirement may request a variance pursuant to §
74:56:03:06;
(2) All owners or operators of AST systems must maintain detailed records of all inspections;
(3) Any defects in the AST system detected in the course of any inspections must be repaired or replaced in accordance with §
74:56:03:16. Any releases detected must be reported in accordance with §
74:56:03:21 and corrective action implemented in accordance with §
74:56:03:22.
Notes
General Authority: SDCL 34A-2-93, 34A-2-101.
Law Implemented: SDCL 34A-2-100, 34A-2-101.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.