T.C.A. § 0780-02-02-.01 - ADOPTION BY REFERENCE

(1) Unless otherwise provided by applicable law or the provisions of this chapter, the required minimum standards for fire prevention, fire protection, and building construction safety in the state of Tennessee shall be those prescribed in the following publications:
(a) The International Building Code (IBC), 2021 edition, published by the International Code Council (ICC), except for the following changes:
1. Remove Chapter 11 Accessibility.
2. The requirements of Section 423 Storm Shelters shall not be required.
3. Section 903.3.1.2 NFPA 13R sprinkler systems shall be replaced with the following:

Automatic sprinkler systems in Group R occupancies may be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions:

(i) Four stories or less above grade plane.
(ii) For occupancies other than Group R-2, the floor level of the highest story is 30 feet (9144 mm) or less above the lowest level of fire department vehicle access.

For Group R-2 occupancies, the roof assembly is less than 45 feet (13716 mm) above the lowest level of fire department vehicle access. The height of the roof assembly shall be determined by measuring the distance from the lowest required fire vehicle access road surface adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest parapet, whichever yields the greatest distance.

(iii) The floor level of the lowest story is 30 feet (9144 mm) or less below the lowest level of fire department vehicle access.

The number of stories of Group R occupancies constructed in accordance with Sections 510.2 and 510.4 of the International Building Code shall be measured from grade plane.

4. For Group E occupancies in all jurisdictions in Tennessee, local education agencies, public charter schools, and non-public schools may allow classroom doors to be locked to prevent unwanted entry provided that the locking means meets the requirements in the National Fire Protection Association (NFPA) (2021) Section 15.2.2.2.4.1.
5. For college and university instructional buildings in all jurisdictions in Tennessee, college and university administrators may allow classroom doors to be locked to prevent unwanted entry provided that the locking means meets the requirements in the NFPA (2021) Section 39.2.2.2.2.
6. Dwellings licensed by the Department of Human Services (DHS) as Family Home Daycares shall use Appendix AM of the 2021 International Residential Code.
7. Where ASCE 7-16 is referenced for seismic design or mapped ground accelerations, ASCE 7-22 mapped ground accelerations may be used to determine the S1 and Ss values.
8. The requirements for flammable gas shall be those found in the International Building Code (IBC), 2024 edition, published by the International Code Council (ICC), and shall include the following:
(i) For Chapter 2, the definition for Flammable Gas shall be replaced with the definition found in the 2024 International Building Code.
(ii) For flammable gases, Table 307.1(1) shall be replaced with Table 307.1(1) of the 2024 International Building Code.
(iii) For flammable gases, Section 307.4 High-Hazard Group H-2 shall be replaced with Section 307.4 High-Hazard Group H-2 of the 2024 International Building Code.
(iv) For flammable gases, Section 307.5 High-Hazard Group H-3 shall be replaced with Section 307.5 High-Hazard Group H-3 of the 2024 International Building Code.
(v) For flammable gases, Section 414.2.5 shall be replaced with Section 414.2.5 of the 2024 International Building Code.
(vi) For flammable gases, Table 414.5.1 shall be replaced with Table 414.5.1 of the 2024 International Building Code.
(b) The International Fuel Gas Code (IFGC), 2021 edition, published by the International Code Council (ICC).
(c) The International Mechanical Code (IMC), 2021 edition, published by the International Code Council (ICC).
(d) The International Plumbing Code (IPC), 2021 edition, published by the International Code Council (ICC).
(e) The International Property Maintenance Code (IPMC), 2021 edition, published by the International Code Council (ICC), except the following sections shall be removed: 302.4 Weeds, 302.8 Motor Vehicles, 302.9 Defacement of Property, 304.2 Protective Treatment, 304.8 Decorative Features, 304.14 Insect Screens, and 308 Rubbish and Garbage.
(f) The International Fire Code (IFC), 2021 edition, published by the International Code Council (ICC), except for the following changes:
1. Section 510.1 Exception 2 shall be replaced with the following:

Where it is determined by the local fire chief in coordination with local law enforcement and EMS that the radio coverage system is not needed.

2. Section 903.3.1.2 NFPA 13R sprinkler systems shall be replaced with the following:

Automatic sprinkler systems in Group R occupancies may be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions:

(i) Four stories or less above grade plane.
(ii) For other than Group R-2 occupancies, the floor level of the highest story is 30 feet (9144 mm) or less above the lowest level of fire department vehicle access.

For Group R-2 occupancies, the roof assembly is less than 45 feet (13716 mm) above the lowest level of fire department vehicle access. The height of the roof assembly shall be determined by measuring the distance from the lowest required fire vehicle access road surface adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest parapet, whichever yields the greatest distance.

(iii) The floor level of the lowest story is 30 feet (9144 mm) or less below the lowest level of fire department vehicle access. The number of stories of Group R occupancies constructed in accordance with Sections 510.2 and 510.4 of the International Building Code shall be measured from grade plane.
3. Appendix L (Requirements for Fire Fighter Air Replenishment Systems) shall be optional.
4. For Group E occupancies in all jurisdictions in Tennessee, local education agencies, public charter schools, and non-public schools may allow classroom doors to be locked to prevent unwanted entry provided that the locking means meets the requirements in the National Fire Protection Association (NFPA) (2021) Section 15.2.2.2.4.1.
5. For college and university instructional buildings in all jurisdictions in Tennessee, college and university administrators may allow classroom doors to be locked to prevent unwanted entry provided that the locking means meets the requirements in the NFPA (2021) Section 39.2.2.2.2.
6. The requirements for flammable gas shall be those found in the International Fire Code (IFC), 2024 edition, published by the International Code Council (ICC), and shall include the following:
(i) For Chapter 2, the definition for Flammable Gas shall be replaced with the definition found in the 2024 International Fire Code.
(ii) For flammable gases, Table 911.1 shall be replaced with Table 911.1 of the 2024 International Fire Code.
(iii) For flammable gases, Table 5003.1.1(1) shall be replaced with Table 5003.1.1(1) of the 2024 International Fire Code.
(iv) For flammable gases, Table 5003.1.1(3) shall be replaced with Table 5003.1.1(3) of the 2024 International Fire Code.
(v) For flammable gases, Section 5003.8.3.5 shall be replaced with Section 5003.8.3.5 of the 2024 International Fire Code.
(vi) For flammable gases, Section 5003.11 shall be replaced with Section 5003.11 of the 2024 International Fire Code.
(g) The International Energy Conservation Code (IECC), 2021 edition, published by the International Code Council (ICC), except for the following changes:
1. Remove C405.11 Automatic Receptacle Control, C405.12 Energy Monitoring, and C408 Commissioning.
2. The 2006 edition shall apply to the following occupancy classifications as defined by the International Building Code (IBC), 2021 edition:
(i) Moderate-hazard factory industrial, Group F-1;
(ii) Low-hazard factory industrial, Group F-2;
(iii) Moderate-hazard storage, Group S-1; and
(iv) Low-hazard storage, Group S-2.
3. For daycares licensed by DHS not located in a dwelling unit, the 2015 edition shall apply, except C408 System Commissioning shall be removed.
(h) The International Existing Building Code (IEBC), 2021 edition, published by the International Code Council (ICC), except for the following changes:
1. Remove Chapter 3 Section 306 Accessibility for existing buildings.
2. Replace Section 405.2.3.3 Extent of repair for noncompliant buildings with the following:

If the evaluation does not establish that the building in its predamaged condition complies with the provisions of Section 405.2.3.1, then the building, including its foundation, shall be retrofitted to comply with the provisions of this section. The wind loads for the repair and retrofit shall be those required by the building code in effect at the time of original construction, unless the damage was caused by wind, in which case the wind loads shall be in accordance with the International Building Code. The seismic loads for this retrofit design shall be those required by the building code in effect at the time of original construction, but not less than the reduced seismic forces.

3. Replace 405.2.4 Substantial structural damage to gravity load-carrying components with the following:

Gravity load-carrying components that have sustained substantial structural damage shall be rehabilitated to comply with the applicable provisions for dead, live, and snow loads in the International Building Code. Undamaged gravity load-carrying components, including undamaged foundation components, that receive dead, live, or snow loads from rehabilitated components shall also be rehabilitated if required to comply with the design loads of the rehabilitation design.

4. The requirements of Section 303 Storm Shelters are not required.
(i) NFPA 101 Life Safety Code, 2021 edition, published by the National Fire Protection Association (NFPA), shall govern new Small Residential Board and Care facilities that:
1. Are a change of occupancy from either a residential occupancy or a health care occupancy; and
2. House eight (8) or fewer residents, and all residents have and maintain the ability to move reliably and escape to a point of safety as a group within three (3) minutes.
(j) No provision of the preceding cited publications shall be adopted that conflicts with:
1. The installation and service standards of portable fire extinguishers and fixed fire extinguisher systems in Tenn. Comp. R. & Regs. 0780-02-14-.02; and
2. The standards for engaging in the liquefied petroleum gas business in Tenn. Comp. R. & Regs. 0780-02-17-.02.
(2) Paragraph (1) of this rule shall not be construed as adopting any provision of the cited publications which establishes:
(a) An optional or recommended, rather than mandatory, standard or practice;
(b) Any agency, procedure, fees, or penalties for administration or enforcement purposes inconsistent with the statute or rules; or
(c) Any permits, fees, or inspections that are inconsistent with Tenn. Comp. R. & Regs. 0780-02-03 or other rules of the Department of Commerce and Insurance.

Notes

T.C.A. § 0780-02-02-.01
Original rule certified June 10, 1974. Repeal and new rule filed August 17, 1976; effective September 16, 1976. Repeal and new rule filed July 27, 1982; effective August 26, 1982. Amendment filed October 11, 1985; effective November 10, 1985. Amendment filed July 9, 1990; effective August 23, 1990. Amendment filed March 13, 1996; effective May 27, 1996. Amendment filed October 14, 1997; effective December 28, 1997. Amendment filed June 12, 2001; effective August 26, 2001. Amendment filed March 19, 2004; effective June 2, 2004. Amendment filed November 16, 2007; withdrawn December 28, 2007. Emergency rule filed January 25, 2008; effective through July 8, 2008. Emergency rule filed July 8, 2008; effective through December 20, 2008. Amendment filed June 18, 2008; effective September 1, 2008. Amendments filed October 2, 2008; effective December 16, 2008. Amendments filed March 29, 2010; effective June 27, 2010. Repeal and amendments filed May 6, 2016; effective August 4, 2016. Emergency rules filed June 1, 2018; effective through November 28, 2018. Amendments filed August 24, 2018; effective November 22, 2018. Emergency rule filed June 14, 2023; effective through December 11, 2023. Emergency rule expired effective December 12, 2023, and the rule reverted to its previous status. Amendments filed January 17, 2025; effective 4/17/2025.

Authority: T.C.A. §§ 68-102-113 and 68-120-101.

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.