Tenn. Comp. R. & Regs. 0780-02-01-.11 - DWELLING UNITS
(1) Where installed
as separate units, ovens and cooktop units shall be served by individual
circuits.
(2) Only designated
circuits shall be energized following a "service release" inspection. Such an
inspection shall only be valid for a period of forty-five (45) days from the
date of inspection.
(3) All
electrical connection, including HVAC equipment, shall be completed and
inspected prior to final approval pursuant to T.C.A. §§
68-102-143(c) and
(e), except as defined in paragraph (2) of
this section.
(4) No newly
constructed one-family or two-family dwelling shall be approved for connection
of electric service on a permanent basis under T.C.A. §
68-102-143, unless the dwelling is
equipped with a smoke alarm that has been:
(a)
Listed in accordance with the standards of Underwriters Laboratories, or
another testing agency or laboratory accepted by the state fire marshal;
and
(b) Installed in accordance
with the building construction safety standards adopted pursuant to T.C.A.
§
68-120-101 and in accordance with
the manufacturer's directions, unless those directions conflict with applicable
standards adopted by the state fire marshal. Notwithstanding the building
construction safety standards adopted pursuant to T.C.A. §
68-120-101, battery operated smoke
alarms shall be permitted when installed in buildings without commercial
power.
(5) Service
equipment shall have only one (1) main means of disconnecting services of two
hundred twenty-five (225) amps or below.
(6) The installation of receptacles for
island counter spaces and peninsular counter spaces below the countertop shall
be optional.
(7) Receptacles shall
not be required in the wall space behind doors which may be opened fully
against a wall surface. Wall space measurement shall begin at the edge of the
door when fully opened.
(8) Light
fixtures in crawl spaces shall have guarded covers.
(9) Occupancy of a dwelling shall be
prohibited before final inspection has been completed and approved.
(10) In Article 334.15(C) of the 2017 edition
of the National Electrical Code, Nonmetallic-Sheathed Cable shall not be
required to be run through bored holes in unfinished basements and crawl spaces
with less than four feet (4') and six inches (6") of clearance.
Notes
Authority: T.C.A. §§ 68-102-113, 68-102-143, 68-102-150, and 68-120-111.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.