Tenn. Comp. R. & Regs. 0800-03-03-.12 - EXISTING PRESSURE VESSELS
(1) Maximum
Allowable Working Pressure for Standard Pressure Vessels. The maximum allowable
working pressure for standard vessels shall be determined in accordance with
the applicable provisions of the ASME Code or the API-ASME Code. The maximum
allowable working pressure shall not be increased to a greater pressure than
shown on the manufacturer's nameplate stamping and data report unless prior
approval is obtained from the Chief Inspector or Chief Inspector's
Designee.
(2) Maximum Allowable
Working Pressure for Nonstandard Pressure Vessels.
(a) The maximum allowable working pressure of
a nonstandard pressure vessel shall be determined in accordance with ASME Code,
Section VIII, Division 1, PG-27.
Click to view Image
(b) The
minimum factor of safety shall in no case be less than five (5) for existing
installations. The working pressure shall be decreased when deemed necessary by
the inspector to insure the operation of the vessel and its particular
service.
(c) The maximum allowable
working pressure permitted for formed heads under pressure shall be determined
by using the appropriate formulas from ASME Code, Section VIII, Division 1, and
the tensile strength and factors of safety given in this rule.
(d) The maximum allowable working pressure
for nonstandard pressure vessels subject to external pressure shall be
determined in accordance with ASME Code, Section VIII, Division 1.
(3) Inspection of Inaccessible
Parts. If the inspector determines during an inspection that it may be
necessary to remove the interior or exterior lining, covering, or brickwork to
expose certain parts of the vessel not normally visible, the owner or user
shall remove such material to permit a proper inspection and the remaining
thickness.
(4) Overpressure
Protection. Each pressure vessel shall be provided with safety relief valves
and controlling devices as necessary to protect against overpressure. These
devices shall be so constructed, located and installed that they cannot be
rendered inoperative. The relieving capacity of such pressure relief devices
shall be adequate to prevent a rise in pressure in the vessel of no more than
ten percent (10%) above the highest pressure to which any pressure relieving
device is set. The opening pressure of the lowest set pressure relieving device
shall be no greater than the maximum allowable working pressure of the vessel.
Where an additional hazard is involved due to fire or other unexpected sources
of external heat, the pressure relief devices shall meet the requirements of
ASME Code, Section VIII, Division 1, Paragraph UG-125 or Division 2, Paragraph
9.2, whichever is applicable.
(5)
Repairs and Renewals of Fittings and Appliances. Whenever repairs are made to
fittings and appliances or it becomes necessary to replace them, the work must
comply with the requirements for new installations.