Tenn. Comp. R. & Regs. 1200-03-18-.27 - LEAKS FROM PETROLEUM REFINERY EQUIPMENT
(1)
Applicability of this rule is as follows:
(a)
This rule applies to all equipment in volatile organic compound (VOC) service
in any process unit at a petroleum refinery, regardless of size or
throughput.
(b) The requirements of
Paragraphs (4) through (8) of this rule do not apply to:
1. Any equipment in vacuum service;
2. Any pressure relief valve that is
connected to an operating flare header or vapor recovery device;
3. Any liquid pump that has a dual mechanical
pump seal with a barrier fluid system;
4. Any compressor with a degassing vent that
is routed to an operating VOC control device; and
5. Pumps and valves in heavy liquid service
except that if evidence of a leak is found by visual, audible, olfactory, or
other detection method, the owner or operator shall confirm the presence of a
leak using the methods specified in Rule .85 of this chapter. If a leak is
confirmed, the owner or operator shall repair the leak as specified in
Paragraph (7) of this rule.
(2) For the purpose of this rule, the
following definitions apply:
(a) "[In]
gas/vapor service" means that the piece of equipment in VOC service contains
process fluid that is in the gaseous state at operating conditions.
(b) "[In] heavy liquid service" means that
the piece of equipment in VOC service is not in gas/vapor service or in light
liquid service.
(c) "[In] light
liquid service" means that the piece of equipment in VOC service contains a
liquid that meets the following conditions:
1. The vapor pressure of one or more of the
components is greater than 0.3 kPa (0.044 in Hg) at 20° C° (68 F)
(standard reference texts or ASTM D2879 shall be used to determine the vapor
pressures);
2. The total
concentration of the pure components having a vapor pressure greater than 0.3
kPa (0.044 in. Hg) at 20° C (68° F) is equal to or greater than 20
percent by weight; and
3. The fluid
is a liquid at operating conditions.
(d) "[In] vacuum service" means that the
equipment in VOC service is operating at an interval pressure which is at least
5 kPa below ambient pressure.
(e)
"[In] VOC service" means that the piece of equipment contains or contacts a
process fluid that is at least 10 percent VOC by weight. The provisions of
Subparagraph (9)(b) of this rule specify how to determine that a piece of
equipment is not in VOC service.
(3) The owner or operator of a petroleum
refinery complex subject to this regulation shall ensure that:
(a) Any open-ended line or valve is sealed
with a second valve, blind flange, cap, or plug except during operations
requiring process fluid flow through the open-ended line or valve;
(b) When a second valve is used, each
open-ended line or valve equipped with a second valve is operated in such a
manner that the valve on the process fluid end is closed before the second
valve is closed; and
(c) When a
double block-and-bleed system is used, the bleed valve or line is open only
during operations that require venting of the line between the block valves and
is closed at all other times.
(4) Equipment inspection program standards as
follow apply:
(a) The owner or operator of a
petroleum refinery shall conduct quarterly monitoring of each:
1. Compressor;
2. Pump in light liquid service;
3. Valve in light liquid service, except as
provided in Paragraphs (5) and (6) of this rule;
4. Valve in gas/vapor service, except as
provided in Paragraphs (5) and (6) of this rule; and
5. Pressure relief valve in gas/vapor
service, except as provided in Paragraphs (5) and (6) of this rule.
(b) The owner or operator of a
petroleum refinery shall conduct a weekly visual inspection of each pump in
light liquid service;
(c) The owner
or operator of a petroleum refinery shall monitor each pressure relief valve
after each overpressure relief to ensure that the valve has properly reseated
and is not leaking;
(d) When an
instrument reading of 10,000 parts per million (ppm) or greater is measured, it
shall be determined that a leak has been detected;
(e) If there are indications of liquid
dripping from the equipment, it shall be determined that a leak has been
detected; and
(f) When a leak is
detected, the owner or operator shall affix a weatherproof, readily visible tag
in a bright color such as red or yellow bearing the equipment identification
number and the date on which the leak was detected. This tag shall remain in
place until the leaking equipment is repaired. The requirements of this
subparagraph apply to any leak detected by the equipment inspection program and
to any leak from any equipment that is detected on the basis of sight, sound,
or smell.
(5)
Alternative standards for skip period leak detection and repair apply as
follows:
(a) An owner or operator shall comply
initially with the requirements for valves in gas/vapor service and valves in
light liquid service, as described in Paragraph (4) of this rule.
(b) After two consecutive quarterly leak
detection periods with the percent of valves leaking equal or less than 2.0, an
owner or operator may begin to skip one of the quarterly leak detection periods
for the valves in gas/vapor and light liquid service.
(c) After five consecutive quarterly leak
detection periods with the percent of valves leaking equal to or less than 2.0,
an owner or operator may begin to skip 3 of the quarterly leak detection
periods for the valves in gas/vapor and light liquid service.
(d) If the percent of valves leaking is
greater than 2.0, the owner or operator shall comply with the requirements as
described in Paragraph (4) of this rule but can again elect to use the
requirements in Paragraph (5) of this rule.
(e) The percent of valves leaking shall be
determined by dividing the sum of valves found leaking during current
monitoring and valves for which repair has been delayed by the total number of
valves subject to the requirements of this rule.
(f) An owner or operator shall keep a record
of the percent of valves found leaking during each leak detection
period.
(6) Alternative
standards for unsafe-to-monitor valves and difficult-to-monitor valves apply as
follow:
(a) Any valve that is designated, as
described in Part (10)(e)1 of this rule, as an unsafe-to-monitor valve is
exempt from the requirements of Paragraph (4) if:
1. The owner or operator of the valve
demonstrates that the valve is unsafe to monitor because monitoring personnel
would be exposed to an immediate danger as a consequence of complying with
Paragraph (4); and
2. The owner or
operator of the valve adheres to a written plan that requires monitoring of the
valve as frequently as practicable during safe-to-monitor times.
(b) Any valve that is designated,
as described in Part (10)(e)2, as a difficult-to-monitor valve is exempt from
the requirements of Paragraph (4) if:
1. The
owner or operator of the valve demonstrates that the valve cannot be monitored
without elevating the monitoring personnel more than 2 meters (m) (6.6 feet
[ft]) above a support surface; and
2. The owner or operator of the valve follows
a written plan that requires monitoring of the valve at least once per calendar
year.
(7) The
owner or operator of a petroleum refinery shall:
(a) Make a first attempt at repair for any
leak not later than 5 calendar days after the leak is detected; and
(b) Repair any leak as soon as practicable,
but not later than 15 calendar days after it is detected except as provided in
Paragraph (8) of this rule.
(8) Delay of repair standards apply as
follow:
(a) Delay of repair of equipment for
which a leak has been detected will be allowed if the repair is technically
infeasible without a process unit shutdown. Repair of such equipment shall
occur before the end of the next process unit shutdown.
(b) Delay of repair of equipment will be
allowed for equipment that is isolated from the process and that does not
remain in VOC service.
(c) Delay of
repair beyond a process unit shutdown will be allowed for a valve, if valve
assembly replacement is necessary during the process unit shutdown, valve
assembly supplies have been depleted, and valve assembly supplies had been
sufficiently stocked before the supplies were depleted. Delay of repair beyond
the next process unit shutdown will not be allowed unless the next process unit
shutdown occurs sooner than 6 months after the first process unit
shutdown.
(9) Test
methods and procedures apply as follow:
(a) In
conducting the tests required to comply with Paragraph (4) of this rule, the
owner or operator shall use the test methods specified in Rule .85 of this
chapter.
(b) The owner or operator
shall test each piece of equipment as required under Paragraph (4) of this rule
unless it is demonstrated that a process unit is not in VOC service, i.e., that
the VOC content would never be reasonably expected to exceed 10 percent by
weight. For purposes of this demonstration, the following methods and
procedures shall be used:
1. Procedures that
conform to the general methods in ASTM E260, E168, and E169 shall be used to
determine the percent VOC content in the process fluid that is contained in or
contacts a piece of equipment;
2.
Where the test methods in Part 1 of this subparagraph also measure exempt
compounds, these compounds may be excluded from the total quantity of organic
compounds in determining the VOC content of the process fluid; and
3. Engineering judgment may be used to
estimate the VOC content, if a piece of equipment had not been shown previously
to be in VOC service. If the Technical Secretary disagrees with the judgment,
Parts 1 and 2 of this subparagraph shall be used to resolve the
disagreement.
(c) The
owner or operator shall demonstrate that a piece of equipment is in light
liquid service by showing that:
1. All of the
following conditions apply:
(i) The vapor
pressure of one or more of the components is greater than 0.3 kiloPascals (kPa)
at 20°C (0.09 inches of Mercury [in Hg] at 68°F); standard reference
texts or ASTM D2879 shall be used to determine the vapor pressures;
(ii) The total concentration of the pure
components having a vapor pressure greater than 0.3 kPa at 20°C (0.09 in Hg
at 68°F) is equal to or greater than 20 percent by weight; and
(iii) The fluid is a liquid at operating
conditions.
2. The
percent VOC evaporated is greater than 10 percent at 150°C (302°F) as
determined by ASTM D86.
(d) Samples used in conjunction with
Subparagraphs (b) and (c) of this paragraph shall be representative of the
process fluid that is contained in or contacts the equipment.
(10) Recordkeeping requirements
apply as follow:
(a) Each owner or operator
subject to the provisions of this rule shall comply with the recordkeeping
requirements of this rule. Except as noted, these records will be maintained
for a minimum of 3 years and shall be made available to the Technical Secretary
upon request.
(b) An owner or
operator of more than one affected facility subject to the provisions of this
rule may comply with the recordkeeping requirements for these facilities in one
recordkeeping system if the system identifies each record by each
facility.
(c) When each leak is
detected as specified in Paragraph (4) of this rule, the following information
shall be recorded in a log and shall be kept for 3 years:
1. The instrument and operator identification
numbers and the equipment identification number;
2. The date the leak was detected and the
dates of each attempt to repair the leak;
3. The repair methods employed in each
attempt to repair the leak;
4. The
notation "Above 10,000" if the maximum instrument reading measured by the
methods specified in Rule .85 of this chapter after each repair attempt is
equal to or greater than 10,000 ppm;
5. The notation "Repair delayed" and the
reason for the delay if a leak is not repaired within 15 calendar days after
discovery of the leak;
6. The
signature of the owner or operator (or designate) whose decision it was that
repair could not be effected without a process shutdown;
7. The expected date of successful repair of
the leak if a leak is not repaired within 15 calendar days;
8. The dates of process unit shutdowns that
occur while the equipment is unrepaired; and
9. The date of successful repair of the
leak.
(d) A list of
identification numbers of equipment in vacuum service shall be recorded in a
log that is kept.
(e) The following
information pertaining to all valves subject to the requirements of Paragraph
(6) of this rule shall be recorded in a log that is kept for 3 years:
1. A list of identification numbers for
valves that are designated as unsafe-to-monitor, an explanation for each valve
stating why the valve is unsafe to monitor, and the plan for monitoring each
valve; and
2. A list of
identification numbers for valves that are designated as difficult-to-monitor,
an explanation for each valve stating why the valve is difficult to monitor,
and the schedule for monitoring each valve.
(f) The following information for valves
complying with Paragraph (5) of this rule shall be recorded in a log that is
kept for 3 years:
1. A schedule of
monitoring; and
2. The percent of
valves found leaking during each monitoring period as noted in Subparagraph
(5)(f) of this rule.
(g)
Information and data used to demonstrate that a piece of equipment is not in
VOC service shall be recorded in a log that is kept 3 years in a readily
accessible location for use in determining exemptions as provided in Paragraph
(1) of this rule.
(11)
The owner or operator of any facility containing sources subject to this rule
shall comply with the requirements in Paragraphs .04(1) and (2) of this
chapter.
Notes
Authority: T.C.A. §§ 4-5-202 and 68-201-105.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.