28 Tex. Admin. Code § 34.518 - Fire Extinguisher Fixed System Plans for Other Than Pre-Engineered Systems
(a) A set of shop
drawings and hydraulic calculations showing details of system piping,
calculations, and alarm configurations must be provided to the building owner
or his representative when installation of a fixed extinguisher system
protecting special hazards is complete. The firm must also maintain a set of
shop drawings for the life of the system.
(b) Subsequent alterations or additions must
be legibly noted on updated plans and provided to the owner. Additions to
systems protecting previously unprotected hazards also require updated plans.
Updated plans must be maintained by the firm for the life of the
system.
(c) All shop drawings must
bear the signature of a Type PL licensee, his license number, the date of
installation, and the certificate-of-registration number of the registered
firm.
(d) A rubber stamp may be
used to supply the required information; however, a stamped signature is
prohibited. If a rubber stamp is used, it shall produce an imprint 2 1/2 inches
wide by one inch high, all in boldface type and capital letters and in the
following sample format.