Utah Admin. Code R432-7-4 - General Construction, Ancillary Support Facilities
R432-4-23(1) through (20) applies with the following modifications:
(1) Leaf width for
patient room doors and doors to patient treatment rooms shall be a minimum of
three feet.
(2) Corridors in
patient use areas shall be a minimum of six feet wide.
(3) Grab Bars. Where grab bars are provided,
the space between the bar and the wall shall be filled. Bars, including those
which are part of such fixtures as soap dishes, shall be sufficiently anchored
to sustain a concentrated load of 250 pounds. Grab bars shall meet the
requirements of ADA/ABA-AG.
(4)
Emergency Electrical Service. An on-site emergency generator shall be provided
connecting the following services:
(a) life
safety branch, as defined in section 517-32 of the National Electric Code NFPA
70;
(b) critical branch, as defined
in 517-33 of the National Electric Code NFPA 70;
(c) equipment system, as defined in 517-34 of
the National Electric Code NFPA 70;
(d) telephone;
(e) nurse call;
(f) heating equipment necessary to provide
heating space to house all patients under emergency conditions;
(g) one duplex convenience outlet in each
patient bedroom;
(h) one duplex
convenience outlet at each nurses station; and
(i) duplex convenience outlets in the
emergency heated part at a ratio of one for each ten patients.
(5) Nurse Call System. A nurse
call system is optional. If installed, provisions shall be made for the easy
removal or covering of call buttons.
(6) X-ray Equipment. If installed, fixed and
mobile x-ray equipment shall conform to Articles 517 and 660 of NFPA
70.
(7) Security glazing. Security
glazing and other security features shall be used at all windows of the nursing
unit and other patient activity and treatment areas to reduce the possibility
of patient injury or escape.