12 Va. Admin. Code § 5-590-380 - Bacteriological compliance
A. The
owner needs only to determine the presence or absence of total coliforms and E.
coli for routine bacteriological monitoring at entry points or distribution
system locations.
B. PMCLs for
microbial contaminants.
1. A waterworks is in
compliance with the PMCL for E. coli unless any of the conditions identified in
this subdivision occur. A violation may pose an acute risk to public health and
is a Tier 1 condition requiring public notification as described in
12VAC5-590-540 A
1 when:
a. A
repeat sample following a total coliform-positive routine sample is E. coli
positive;
b. A repeat sample
following an E. coli-positive routine sample is total coliform
positive;
c. The owner fails to
collect all required repeat samples following an E. coli-positive routine
sample; or
d. The owner fails to
test for E. coli when any repeat sample tests positive for total
coliform.
2. Compliance
shall be determined with the PMCL for E. coli for each monitoring period for
which monitoring for total coliforms is required.
C. The best available technology (BAT),
treatment techniques, or other means available for achieving compliance with
the PMCL for E. coli shall be:
1. Protection
of wells from contamination by coliforms by appropriate placement,
construction, and maintenance of the wells;
2. Maintenance of a detectable residual
disinfectant throughout the distribution system;
3. Proper maintenance of the distribution
system including appropriate pipe replacement and repair procedures, water main
flushing programs, proper operation and maintenance of storage tanks and
reservoirs, continual maintenance of positive water pressure in all parts of
the distribution system, and an approved cross-connection control
program;
4. Filtration and
disinfection of a surface water source, a GUDI source, or both; and
5. Disinfection of groundwater using strong
oxidants such as chlorine, chlorine dioxide, or ozone.
D. A total coliform-positive result is
indicative of a breakdown in the protective barriers and shall be cause for
repeat monitoring and special follow-up action to locate and eliminate the
cause of contamination.
1. For each routine
sample found to be total coliform positive, the owner shall collect a set of
three repeat samples within 24 hours of being notified of the positive result.
The department may extend the 24-hour limit on a case-by-case basis. For
groundwater systems, the requirements of
12VAC5-590-379 shall also apply,
and all repeat samples must be analyzed for E. coli using one of the analytical
methods in
40
CFR 141.402(c).
a. The owner shall collect at least one
repeat sample from the sampling tap where the original total coliform-positive
sample was collected, and at least one repeat sample at a tap within five
service connections upstream and at least one repeat sample at a tap within
five service connections downstream of the original sampling site. If a total
coliform-positive sample is at the end of the distribution system or one
service connection away from the end of the distribution system, the owner must
still collect all required repeat samples.
b. The owner shall collect an additional set
of repeat samples if one or more repeat samples in the current set of repeat
samples is total coliform positive. The owner shall collect the additional set
of repeat samples within 24 hours of being notified of the positive results,
unless the department extends the limit as provided in this section. The owner
shall continue to collect additional sets of repeat samples until either total
coliforms are not detected in one complete set of repeat samples or the owner
determines that a coliform treatment technique trigger specified in
12VAC5-590-392 B
has been exceeded as a result of a repeat sample being total coliform positive
and notifies the department. If a trigger identified in
12VAC5-590-392 B
is exceeded as a result of a routine sample being total coliform positive, then
the owner is required to conduct only one round of repeat monitoring for each
total coliform-positive routine sample.
c. If the owner collects a routine sample
before learning the results of the previous routine sample, and the sample is
collected within five service connections of the initial routine sample, then
the owner may count the subsequent sample as a repeat sample when the initial
sample results are found to be total coliform positive.
d. If one or more repeat samples collected at
the monitoring location required for triggered source water monitoring are E.
coli positive, then the owner has exceeded the E. coli PMCL and must comply
with the groundwater system treatment technique requirements specified in
12VAC5-590-421.
e. If all repeat samples collected at the
monitoring location required for triggered source water monitoring are E. coli
negative, and a repeat sample collected at a monitoring location other than the
one required for triggered source water monitoring is E. coli positive, then
the owner has exceeded the E. coli PMCL. However, the owner is not required to
collect five additional source water samples from the same source within 24
hours of learning the E. coli-positive result.
f. The owner shall collect all repeat samples
on the same day, except the department may allow the owner of a waterworks with
a single service connection to collect the required set of repeat samples over
a three-day period or to collect a larger volume repeat sample in one or more
sample containers of any size as long as the total volume collected is at least
300 ml.
g. If a repeat sample
collected at the monitoring location required for triggered source water
monitoring is E. coli-positive, then the owner has exceeded the E. coli PMCL
and must collect five additional source water samples from the same source
within 24 hours of learning the E. coli-positive result.
2. Results of all routine and repeat samples
not invalidated by the department shall be used to determine compliance with
the PMCL for E. coli and whether a treatment technique trigger specified in
12VAC5-590-392 B
has been exceeded.
3.
Special-purpose samples, such as those collected to determine whether
disinfection practices are sufficient following pipe placement, replacement, or
repair, and samples collected before start-up of a seasonal waterworks, shall
not be used to determine compliance. Repeat samples are not considered
special-purpose samples.
E. A total coliform-positive sample
invalidated under this subsection does not count toward meeting the minimum
monitoring requirements of this section. To invalidate a total
coliform-positive sample under this subsection, the written decision and
rationale shall be evaluated, approved, and signed by the department. The
department shall make this document available to EPA and the public. The
written documentation shall state the specific cause of the total
coliform-positive sample and what action the owner has taken, or will take, to
correct this problem. The department shall not invalidate a total
coliform-positive sample solely on the grounds that all repeat samples are
total coliform negative.
1. The department
may invalidate a total coliform positive sample if any of the following
conditions are met:
a. The laboratory
establishes that improper sample analysis caused the total coliform-positive
result;
b. The department, on the
basis of the results of repeat samples collected as required by subdivision D 1
of this section, determines that the total coliform-positive sample resulted
from a domestic or other nondistribution system plumbing problem. The
department cannot invalidate a sample on the basis of repeat sample results
unless all repeat samples collected at the same tap as the original total
coliform-positive sample are also total coliform positive, and all repeat
samples collected at a location other than the original tap are total coliform
negative (e.g., the department cannot invalidate a total coliform-positive
sample on the basis of repeat samples if all the repeat samples are total
coliform negative or if the waterworks has only one service connection);
or
c. The department has
substantial grounds to believe that a total coliform-positive result is due to
a circumstance or condition that does not reflect water quality in the
distribution system. In this case, the owner shall still collect all repeat
samples required under subdivision D 1 of this section, and use them to
determine whether a coliform treatment technique trigger in
12VAC5-590-392 B
has been exceeded.
2. A
laboratory must invalidate a sample because of sampling interference (i.e.,
turbid culture in absence of (i) gas production, or (ii) acid reaction;
exhibition of confluent growth; or production of colonies too numerous to
count). The owner shall collect a replacement sample from the same location
within 24 hours, and have it analyzed for the presence of total coliforms. The
owner must continue to resample within 24 hours and have the samples analyzed
until a valid result is obtained. The department may waive the 24-hour time
limit on a case-by-case basis.
F. Escherichia coli (E. coli).
1. If a routine, repeat, or replacement
sample is total coliform positive, then the owner shall analyze the total
coliform-positive culture medium to determine if E. coli are present. If E.
coli are present, then the owner shall notify the department by the end of the
day when the owner is notified of the test result, unless the department is
closed, in which case the department must be notified before the end of the
next business day.
2. The
department has the discretion to allow an owner, on a case-by-case basis, to
forgo E. coli testing on a total coliform-positive sample if the owner assumes
that the total coliform-positive sample is E. coli positive. Accordingly, the
owner must notify the department as specified in subdivision F 1 of this
subsection and the provisions of subdivision B 1 of this section
apply.
G. Groundwater
sources.
1. Groundwater sources shall be
disinfected in accordance with
12VAC5-590-421 A 1
d when the results of the source water
monitoring samples specified in
12VAC5-590-430 B
2 or
12VAC5-590-840 K 1
a indicate a total coliform concentration
(geometric mean) of the 20 samples to be greater than 3 colonies/100 mL but
less than 100 colonies/100 mL. The value 1.0 shall be used to represent a zero
coliform result in the calculation of the geometric mean.
2. Groundwater source monitoring results
conducted in accordance with
12VAC5-590-430 B
2 or
12VAC5-590-840 K 1
a that indicate a total coliform
concentration equal to or greater than 100 colonies/100 ml constitutes
contamination that is not treatable by single-barrier disinfection treatment
alone.
3. Groundwater sources shall
be disinfected in accordance the requirements of
12VAC5-590-421 A 1
d when the source water quality contributes
to the waterworks' failure to meet the bacteriological PMCL specified in
subsection B of this section.
4. If
the results of the source water monitoring required by
12VAC5-590-379 C
or 12VAC5-590-430 B
2 indicate the presence of E. coli in two or
more samples collected during any running six-month period, then the owner
shall:
a. Issue a Tier 1 public notice in
accordance with
12VAC5-590-540 A
1.
b. Provide disinfection treatment to achieve
a 4-log virus inactivation and removal as specified in
12VAC5-590-421 A 1
d.
5. If the results of the
source water monitoring required in
12VAC5-590-379 C
indicate total coliform concentration in excess of 50 colonies/100 mL in three
or more samples collected during any running six-month period or the presence
of E. coli in two or more samples collected during any running six-month
period, then the source water shall be reevaluated for GUDI determination in
accordance with
12VAC5-590-430.
6. The department may require that any
groundwater source be disinfected in accordance with the requirements of
12VAC5-590-421 A 1
d.
H. All samples shall be analyzed by
laboratories that have received certification by EPA or DCLS as specified in
12VAC5-590-440 for drinking water
analyses.
Notes
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.