A
waterworks that uses a surface water source, a GUDI source, or both is
considered to be in compliance with the requirements of subdivision A 1 of this
section if it meets the following disinfection and filtration requirements:
a. Disinfection requirements.
(1) The disinfection treatment shall be
sufficient to ensure that the total treatment processes of that waterworks
achieve at least 99.9% (3-log) inactivation or removal of Giardia lamblia and
at least 99.99% (4-log) inactivation or removal of viruses. If any physical
process can achieve at least a 3-log removal of Giardia lamblia but cannot
adequately remove pathogens, then the disinfection treatment shall provide a
second treatment barrier for Giardia lamblia, Legionella, heterotrophic
bacteria, and viruses. The disinfection treatment shall be sufficient to assure
at least a 0.5 log inactivation of Giardia lamblia.
(2) The residual disinfectant concentration
in the water entering the distribution system shall not be less than 0.2 mg/L
for more than four hours.
(3) The
residual disinfectant concentration in the distribution system, measured as
total chlorine, free chlorine, combined chlorine, or chlorine dioxide, shall
not be undetectable in more than 5% of the samples each month, for any two
consecutive months that the waterworks serves water to the public. If the
department determines that a waterworks is experiencing excessive coliform
occurrences in its distribution system, then the department may require the
owner to maintain minimum chlorine residual levels of 0.2 mg/L or
monochloramine levels of 0.5 mg/L throughout the distribution system. Water in
the distribution system with a heterotrophic bacteria concentration less than
or equal to 500/mL, measured as HPC, is deemed to have a detectable residual
disinfectant for the purposes of determining compliance with this requirement.
Thus, the value "V," in percent, in the following formula shall not exceed 5%
in one month, for any two consecutive months.
V = [(c + d + e) / (a + b)] X 100
where
a = number of instances where the residual disinfectant
concentration is measured;
b = number of instances where the residual disinfectant
concentration is not measured but HPC is measured;
c = number of instances where the residual disinfectant
concentration is measured but not detected and no HPC is measured;
d = number of instances where no residual disinfectant
concentration is detected and where the HPC is greater than 500/mL; and
e = number of instances where the residual disinfectant
concentration is not measured and HPC is greater than 500/mL.
(4) The department may determine that the HPC
compliance requirements of subdivision A 2 a (3) of this section do not apply
based on site-specific considerations or if an owner has no means for having a
sample transported and analyzed for HPC by a certified laboratory under the
requisite time and temperature conditions and the waterworks is providing
adequate disinfection in the distribution system.
b. Filtration requirements. A waterworks that
uses a surface water source, a GUDI source, or both shall provide filtration
treatment by using one of the following methods:
(1) Conventional filtration.
(a) Achieve a filtered water turbidity of
less than or equal to 0.3 NTU in at least 95% of the measurements taken each
month. Samples shall be representative of the waterworks' filtered
water.
(b) The turbidity level of
representative samples of a waterworks' filtered water shall at no time exceed
one NTU, measured as specified in
12VAC5-590-440.
(c) A waterworks that uses lime softening may
acidify representative samples before analysis using a protocol approved by the
department.
(d) Water treatment
plants utilizing conventional or direct filtration with gravity flow granular
media filters are capable of producing filtered water with turbidity
consistently less than 0.10 NTU. Therefore, for these types of water treatment
plants, the operational goal for filter effluent turbidity for each filter,
before any post-filtration chemical addition, shall be 0.10 NTU.
(2) Diatomaceous earth filtration.
(a) The turbidity level of representative
samples of a waterworks' filtered water shall be less than or equal to one NTU
in at least 95% of the measurements taken each month.
(b) The turbidity level of representative
samples of a waterworks' filtered water shall at no time exceed five
NTU.
(3) Slow sand
filtration.
(a) The turbidity level of
representative samples of a waterworks' filtered water shall be less than or
equal to one NTU in at least 95% of the measurements taken each month, except
that if the department determines there is no significant interference with
disinfection at a higher turbidity level, then the department may substitute
this higher turbidity limit for that waterworks.
(b) The turbidity level of representative
samples of a waterworks' filtered water shall at no time exceed five
NTU.
(4) Membrane
filters, bag filters, and cartridge filters.
(a) The turbidity level of representative
samples of a waterworks' filtered water shall be less than or equal to 0.3 NTU
in at least 95% of the measurements taken each month, except that if the
department determines there is no significant interference with disinfection at
a higher turbidity level, then the department may substitute this higher
turbidity limit for that waterworks.
(b) Water treatment plants utilizing membrane
filtration are capable of producing filtered water with turbidity consistently
less than 0.05 NTU. Therefore, for these types of water treatment plants, the
operational goal for filter effluent turbidity for each filter, before any
post-filtration chemical addition, is 0.05 NTU.
(c) The turbidity level of representative
samples of a waterworks' filtered water shall at no time exceed one
NTU.
(5) The owner may
use a filtration technology not listed in this section if the owner
demonstrates to the satisfaction of the department by full-scale, pilot plant,
or challenge studies, or by other approved means that the alternative
filtration technology, in combination with disinfection, will meet the
requirements of this section.