12 Va. Admin. Code § 5-590-411 - Disinfection byproduct precursors, disinfection byproducts, and maximum residual disinfection level treatment techniques
Required Step 1 TOC reductions, indicated in Table 411.1, are based upon specified source water parameters. A waterworks practicing softening is required to meet the Step 1 TOC reductions in the far-right column (source water alkalinity greater than 120 mg/L) for the specified source water TOC.
|
TABLE 411.1Required Percentage Removals of TOCa,b |
|||
|
SOURCE WATER TOC, mg/L |
SOURCE WATER ALKALINITY, mg/L as CaCO3 |
||
|
0 - 60 |
>60 - 120 |
>120c |
|
|
>2.0 - 4.0 |
35.0% |
25.0% |
15.0% |
|
>4.0 - 8.0 |
45.0% |
35.0% |
25.0% |
|
>8.0 |
50.0% |
40.0% |
30.0% |
|
aA waterworks meeting at least one of the conditions in subdivisions A 1 c (1) through A 1 c (6) of this section is not required to operate with enhanced coagulation. bA waterworks utilizing softening and meeting one of the alternative compliance criteria in subdivision A 1 d of this section is not required to operate with enhanced softening. cA waterworks practicing softening shall meet the TOC removal requirements in this column. |
|||
|
TABLE 411.2Enhanced Coagulation |
|
|
ALKALINITY (mg/L as CaCO3) |
TARGET pH |
|
0 - 60 |
5.5 |
|
>60 -120 |
6.3 |
|
>120 - 240 |
7.0 |
|
>240 |
7.5 |
[1-(treated water TOC/source water TOC)] X 100.
|
DISINFECTION BYPRODUCT |
BEST AVAILABLE TECHNOLOGY |
|
Bromate |
Control of ozone treatment process to reduce production of bromate |
|
Chlorite |
Control of treatment processes to reduce disinfectant demand and control of disinfection treatment processes to reduce disinfectant levels |
|
DISINFECTION BYPRODUCT |
BEST AVAILABLE TECHNOLOGY |
|
TTHM and HAA5 |
Enhanced coagulation or enhanced softening or GAC10, with chlorine as the primary and residual disinfectant |
|
DISINFECTION BYPRODUCT |
BEST AVAILABLE TECHNOLOGY |
|
TTHM and HAA5 |
Enhanced coagulation or enhanced softening, plus GAC10; or NF with a molecular weight cutoff fewer than or equal to 1,000 Daltons; or GAC20 |
|
DISINFECTION BYPRODUCT |
BEST AVAILABLE TECHNOLOGY |
|
TTHM and HAA5 |
A waterworks serving equal to or greater than 10,000 people: Improved distribution system and storage tank management to reduce residence time, plus the use of chloramines for residual disinfectant maintenance A waterworks serving fewer than 10,000 people: Improved distribution system and storage tank management to reduce residence time |
Notes
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.