12 Va. Admin. Code § 5-590-480 - Operational control testing and monitoring
A. Water analyses and tests performed at
waterworks are conducted for four main purposes:
(i) to ensure compliance;
(ii) to control water treatment plant
operation;
(iii) to record water
treatment plant performance; and
(iv) to provide information for improving
water treatment plant performance. Tests designed to control operation shall
present evidence that:
1. Each key process,
such as mixing, coagulation, sedimentation, filtration, softening, iron and
manganese removal, disinfection, and taste and odor control, is effective;
and
2. The finished product is
clean, is free from objectionable taste and odor, is free from undesirable
chemical characteristics, and is safe for human consumption.
B. Testing for
regulatory compliance purposes shall use an EPA-approved analytical method
found in 40 CFR Parts 141 and 143. Instruments used for operational control
purposes must be calibrated in accordance with manufacturer instructions.
Calibrations shall be documented in a manner acceptable to the
department.
C. Ample laboratory
space shall be provided for all required laboratory analyses as specified in
12VAC5-590-760.
D. Required waterworks onsite laboratory
analyses. The analyses listed in this subsection are the minimum required.
Additional testing may be required by the department.
1. The owner of a waterworks employing
chemical coagulation or lime softening in combination with any filtration
treatment for turbidity removal or TOC reduction shall provide equipment for
the analysis of pH, alkalinity, hardness, turbidity, water temperature, and
coagulant dosage. A calibrated electric pH meter must be provided; however, a
color comparator may be used as a backup unit. Turbidities must be determined
by the use of a calibrated turbidimeter.
2. The owner of a waterworks employing
membrane filtration without chemical coagulation or lime softening shall
provide equipment for the analysis of turbidity and temperature. Turbidities
shall be determined by the use of a calibrated turbidimeter.
3. The owner of a waterworks employing
softening only and utilizing chemical precipitation shall provide equipment for
the analysis of pH utilizing a calibrated electric pH meter, alkalinity,
hardness, water temperature, and chemical dosage for precipitation utilizing a
multiple jar stirring machine.
4.
The owner of a waterworks employing iron and manganese removal by chemical
precipitation shall provide equipment for the analysis of pH, alkalinity, iron,
manganese, and water temperature.
5. The owner of a waterworks employing
fluoridation shall provide equipment for the analysis of the fluoride ion
concentration and water temperature.
6. The owner of a waterworks employing
chlorination, rechlorination, chloramination, or rechloramination shall provide
equipment for the analysis of the appropriate chlorine residual measurement and
temperature.
7. The owner of a
waterworks employing iron and manganese removal by ion exchange or softening by
ion exchange shall provide equipment for the analysis of iron and
manganese.
E. Process
control instruments, monitors, gauges, and controllers, including reading,
recording, and alarm features, required in Part III, Manual of Practice
(12VAC5-590-640 et seq.), shall be
maintained fully operational and calibrated in accordance with the manufacturer
instructions.
1. The owner of a waterworks
employing UV for inactivation credit shall perform UV sensor calibration
checks. Calibrations and instrument checks shall be documented in a manner
acceptable to the department. All UV sensors shall be calibrated with a
reference UV sensor at least monthly. It is also recommended that offline and
standby sensors be calibrated at the same time. At least one reference sensor
for calibration of online sensors shall be provided. The reference UV sensor
shall be calibrated at least yearly at a qualified facility, usually the
manufacturer. Ultraviolet transmittance (UVT) analyzer calibration is required
when used as a control instrument. The UVT analyzer shall be calibrated at
least weekly by comparing online measurements to a benchtop spectrophotometer
that is calibrated in accordance with manufacturer instructions. Instead of an
online UVT analyzer, a benchtop spectrophotometer may be utilized to determine
UV transmittance at least every four hours.
2. The owner of a waterworks employing ozone
for inactivation credit shall perform calibration checks on continuous, online
ozone residual monitors at least weekly. Inactivation credits for a multiple
chamber contactor shall be based on only the chambers that have a measured
ozone residual greater than 0.02 mg/L or higher, depending on residual analysis
instrumentation.
Notes
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.