12 Va. Admin. Code § 5-590-860 - Chemical application
A.
Plans and specifications shall be submitted for evaluation and approval, as
required in Part I (12VAC5-590-200 through
12VAC5-590-220), and shall
include:
1. Descriptions of feed equipment,
including maximum and minimum feed ranges;
2. Location of feeders, piping layout, and
points of application;
3. Chemical
storage and handling facilities;
4.
Specifications for chemicals to be used;
5. Operating and control features;
and
6. Descriptions of testing
equipment and procedures.
B. Chemicals shall be applied to the water at
such points and by such means as to:
1. Assure
maximum efficiency of treatment;
2.
Provide maximum protection to the consumer;
3. Provide maximum safety to
operators;
4. Assure satisfactory
mixing of the chemicals with the water;
5. Provide maximum flexibility of operation
through various points of application, when appropriate;
6. Prevent backflow or backsiphonage between
multiple points of feed through common manifolds; and
7. Provide for the application of
pH-affecting chemicals to the source water before the addition of the coagulant
in turbidity removal processes.
C. Feed equipment.
1. Where chemical feed is necessary for the
treatment of the source water, such as chlorination, coagulation, or other
essential processes, a standby feeder or combination of feeders shall be
available to provide the required chemical dose with the largest feeder out of
service.
2. Feeders shall be of
such design and capacity to meet the following requirements:
a. Feeders shall be able to supply the
necessary amounts of chemical at an accurate rate throughout the range of feed
at all times.
b. Proportioning of
chemical feed to the rate of flow shall be provided where the water flow is not
constant or where specifically required by the department.
c. Positive displacement type solution feed
pumps, or gravity feed through rotameters, shall be used to feed liquid
chemicals, but should not normally be used to feed chemical slurries.
d. Chemical contact materials and surfaces
shall be resistant to the aggressiveness of the chemical solution.
e. Dry chemical feeders shall:
(1) Measure chemicals volumetrically or
gravimetrically;
(2) Provide
effective solution of the chemical in the solution pot;
(3) Provide gravity feed from solution pots;
and
(4) Completely enclose
chemicals to prevent emission of dust to the room.
f. No direct connection shall exist between
any sewer and a drain or overflow from the feeder or solution chamber or
tank.
g. A separate chemical waste
tank should be considered.
3. Chemical feed equipment:
a. Shall be located near points of
application to minimize length of feed lines;
b. Shall be readily accessible for servicing
and repair, and observation of operation; and
c. Shall be located within a protective
curbing so that chemicals resulting from equipment failure, spillage, or
accidental drainage shall not enter the water in conduits or treatment or
storage basins.
4.
Control.
a. Feeders shall be capable of both
manual and automatic control with the automatic control reverting to manual
control as necessary;
b. Feeders
shall be manually started following shutdown, unless otherwise approved by the
department; and
c. Automatic
chemical dose controls with residual analyzers shall provide alarms for
critical values and shall include indicating and recording equipment.
5. Solution tanks. All solution
tanks shall be manufactured of materials suitable for food contact or that meet
the requirements of
12VAC5-590-810.
a. Means shall be provided to maintain
uniform strength of solution, consistent with the nature of the chemical
solution. Continuous agitation shall be provided to maintain slurries in
suspension.
b. Solution tanks shall
be of sufficient number and capacity to assure continuous chemical application
during tank servicing, and the access openings shall be curbed and fitted with
tight covers.
c. Each tank
exceeding 30 gallons in capacity or fixed in place shall be provided with a
drain unless other means of dewatering the tank are provided.
(1) Direct connection between any tank or
drain and a sewer is prohibited.
(2) All drains shall terminate at least two
pipe diameters, but not less than two inches, above the rim of the receiving
sump, conduit, or waste receptacle.
d. Means shall be provided to indicate the
solution level in the tank.
e.
Process water shall enter the tank above the rim at a distance of two pipe
diameters but not less than two inches.
f. Chemical solutions shall be kept
covered.
g. Buried or subsurface
chemical storage or solution tanks are prohibited.
h. Overflow pipes, when provided, shall:
(1) Be turned downward, and when located
outside, be provided with an appropriately sized screened end to prevent entry
of insects and small animals;
(2)
Have free discharge;
(3) Be located
where noticeable; and
(4) Be
directed so as not to contaminate the water or be a hazard to operating
personnel.
6.
Weighing scales.
a. Shall be provided for
weighing cylinders at all water treatment plants utilizing chlorine gas; for
large water treatment plants, indicating and recording type are
desirable;
b. Shall be provided for
fluorosilicic acid feed systems in conjunction with a loss-of-weight
recorder;
c. Shall be considered
for volumetric dry chemical feeders; and
d. Shall be accurate to measure increments of
0.5% of load.
7. Feed
lines.
a. Shall be as short as possible in
length of run and be:
(1) Of durable,
corrosion-resistant material;
(2)
Easily accessible throughout the entire length;
(3) Protected against freezing; and
(4) Readily cleanable;
b. Shall slope upward from chemical source to
feeder, when conveying gases.
c.
Shall introduce corrosive chemicals in a manner as to minimize potential for
corrosion.
d. Shall be designed
consistent with scale forming solids depositing properties of the water,
chemical solution, or mixture conveyed.
e. Shall not carry chlorine gas beyond the
chlorine feeder room unless the chlorine is under vacuum.
f. Shall be designed so that liquid alum does
not mix with water before the point of application.
8. Process water.
a. Water used for dissolving dry chemicals,
diluting liquid chemicals, or operating chemical feeders shall be:
(1) From a safe, approved source;
(2) Protected from contamination by
appropriate means;
(3) Ample in
supply and adequate in pressure;
(4) Provided with means for measurement when
preparing specific solution concentrations by dilution; and
(5) Properly treated for hardness when
necessary.
b. Where a
booster pump is required, a spare pump shall be provided.
c. Backflow prevention shall be achieved by
appropriate means such as:
(1) An air gap
between the fill pipe and overflow rim of the solution or dissolving tank, and
equivalent to two pipe diameters but not less than two inches;
(2) An approved reduced pressure zone
backflow preventer, consistent with the degree of hazard, aggressiveness of
chemical solution, back pressure sustained, location, and available means for
maintaining and testing the device; or
(3) A satisfactory vacuum relief
device.
D. Chemicals.
1. Storage.
a. Space shall be provided where at least 30
days of chemical supply can be stored, based on the average dose and average
annual water treatment plant flow rate. Storage shall be at a location that is
convenient for efficient handling and safety. Lesser storage capacity may be
approved if the owner can demonstrate that the local suppliers or other
conditions will provide an uninterrupted source of chemicals.
b. Cylinders of chlorine gas shall be:
(1) Isolated from operating areas;
(2) Restrained in position to prevent upset;
and
(3) Stored in rooms separate
from ammonia storage.
c.
Liquid chemical storage tanks shall:
(1) Have
a liquid level indicator; and
(2)
Have an overflow and a receiving basin or drain capable of receiving accidental
spills or overflows.
d.
Special precautions shall be taken with sodium chlorite to eliminate any danger
of explosion.
e. Activated carbon.
The following special precautions shall be taken in areas where activated
carbon is stored, handled, and fed.
(1)
Isolated, cool, and dry areas free from sources of ignition shall be provided
for activated carbon storage;
(2)
Electrical equipment, devices, and materials shall comply with applicable
codes;
(3) Ventilation in areas
associated with the storage, handling, and feeding of activated carbon shall be
localized so as not to cause dust or material to be drawn into other areas;
and
(4) Activated carbon shall not
be stored with strong oxidants such as ozone, liquid chlorine (i.e., compressed
chlorine gas), and permanganate.
f. Chemicals shall be stored in covered or
unopened shipping containers, unless the chemical is transferred into an
approved covered storage unit.
g.
Solution storage or day tanks supplying feeders directly should have sufficient
capacity for one day of operation.
h. Acid storage tanks shall be vented to the
outside atmosphere, but not through vents in common with day tanks.
2. Handling.
a. Provisions shall be made for measuring
quantities of chemicals used to prepare feed solutions.
b. Storage tanks and pipelines for liquid
chemicals shall be specific to the chemicals and not for alternates.
c. Chemicals that are incompatible shall not
be fed, stored, or handled together.
d. Provisions shall be made for the proper
transfer of dry chemicals from shipping containers to storage bins or hoppers
to mitigate the quantity of dust that may enter the room in which the equipment
is installed. Control shall be provided by use of:
(1) Vacuum pneumatic equipment or closed
conveyor systems;
(2) Facilities
for emptying shipping containers in special enclosures; or
(3) Exhaust fans and dust filters that put
the hoppers or bins under negative pressure.
e. Precautions shall be taken with electrical
equipment to prevent explosions and other hazards.
f. Acids shall:
(1) Be kept in closed, acid-resistant
shipping containers or storage units; and
(2) Not be handled in open vessels, but
should be pumped in undiluted form from original containers, through a suitable
hose, to the point of treatment or to a covered day tank.
g. Carts, elevators, and other appropriate
means shall be provided for lifting chemical containers to mitigate excessive
lifting by operators.
h. Provisions
shall be made for disposing of empty containers by an approved procedure that
will mitigate exposure to the chemical.
E. Housing.
1. Structures, rooms, and areas accommodating
chemical feed equipment shall provide convenient access for servicing, repair,
and observation of operation.
2.
Floor surfaces shall be smooth and impervious, slip-proof, and well
drained.
3. Open basins, tanks, and
conduits shall be protected from chemical spills or accidental
drainage.
F. Operator
safety. Safety provisions shall protect people at the waterworks from chemical
exposures in accordance with VOSH laws and regulations.
1. Gases from feeders, storage, and equipment
exhausts shall be conveyed to the outside atmosphere, above grade, and remote
from air intakes.
2. See
12VAC5-590-1000 and
12VAC5-590-1001 for special
provisions for handling and storing chlorine.
3. A plastic bottle of hydrochloric acid
(muriatic acid in commercial form) shall be available for ammonia leak
detection where ammonia gas is used or stored.
4. At least one pair of rubber gloves with
long gauntlets, a dust respirator of a type that complies with VOSH laws and
regulations for toxic dusts, and an apron or other protective clothing shall be
provided for each operator in any shift who will handle dry
chemicals.
5. Facilities such as
emergency eye wash and showers shall be provided for washing of the face,
gloves, and protective equipment.
Notes
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.