Wash. Admin. Code § 173-443-040 - List of prohibited substances
TABLE 1. Prohibited Substances for New Products and Equipment
|
End-Use Category: Aerosol Propellants |
||
|
End-Use |
Prohibited Substances |
Effective Date |
|
Aerosol propellants |
HFC-125, HFC-134a, HFC-227ea and blends of HFC-227ea and HFC-134a |
January 1, 2020 |
|
End-Use Category: Air Conditioning |
||
|
End-Use |
Prohibited Substances |
Effective Date |
|
Centrifugal chillers - Cooling only (New) |
FOR12A, FOR12B, HFC-134a, HFC-227ea, HFC-236fa, HFC-245fa, R-125/134a/600a (28.1/70/1.9), R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-423A, R-424A, R-434A, R-438A, R-507A, RS-44 (2003 composition), THR-03 |
January 1, 2024 |
|
Positive displacement chillers - Cooling only (New) |
FOR12A, FOR12B, HFC-134a, HFC-227ea, KDD6, R-125/134a/600a (28.1/70/1.9), R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-424A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 composition), SP34E, THR-03 |
January 1, 2024 |
|
Centrifugal chillers - Heating and heating and cooling (New) |
FOR12A, FOR12B, HFC-134a, HFC-227ea, HFC-236fa, HFC-245fa, R-125/134a/600a (28.1/70/1.9), R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-423A, R-424A, R-434A, R-438A, R-507A, RS-44 (2003 composition), THR-03 |
January 1, 2025 |
|
Positive displacement chillers - Heating and heating and cooling (New) |
FOR12A, FOR12B, HFC-134a, HFC-227ea, KDD6, R-125/134a/600a (28.1/70/1.9), R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-424A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 composition), SP34E, THR-03 |
January 1, 2025 |
|
End-Use Category: Refrigeration |
||
|
End-Use |
Prohibited Substances |
Effective Date |
|
Cold storage warehouses (New) |
HFC-227ea, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-423A, R-424A, R-428A, R-434A, R-438A, R-507A, RS-44 (2003 composition) |
January 1, 2023 |
|
Household refrigerators and freezers (New) |
FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03 |
January 1, 2022 |
|
Household refrigerators and freezers - Compact (New) |
FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03 |
January 1, 2021 |
|
Household refrigerators and freezers - Built-in appliances (New) |
FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03 |
January 1, 2023 |
|
Supermarket systems (Retrofit) |
R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A |
January 1, 2020 |
|
Supermarket systems (New) |
HFC-227ea, R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A |
January 1, 2020 |
|
Remote condensing units, except for automatic commercial ice machines (Retrofit) |
R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A |
January 1, 2020 |
|
Remote condensing units, except for automatic commercial ice machines (New) |
HFC-227ea, R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A |
January 1, 2020 |
|
Automatic commercial ice machines - Remote condensing units (New and retrofit) |
R-404A, R-507, R-507A, R-428A, R-422C, R-434A, R-421B, R-408A, R-422A, R-407B, R-402A, R-422D, R-421A, R-125/R-290/R-134a/R-600a (55.0/1.0/42.5/1.5), R-422B, R-424A, R-402B, GHG-X5, R-417A, R-438A, and R-410B |
January 1, 2025 |
|
Stand-alone units, except for automatic commercial ice machines (Retrofit) |
R-404A, R-507A |
January 1, 2020 |
|
Stand-alone medium-temperature units (New) |
FOR12A, FOR12B, HFC-134a, HFC-227ea, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03 |
January 1, 2020 |
|
Stand-alone low-temperature units (New) |
HFC-227ea, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 formulation) |
January 1, 2020 |
|
Automatic commercial ice machines - Stand-alone units (New and retrofit) |
R-404A, R-507, R-507A, R-428A, R-422C, R-434A, R-421B, R-408A, R-422A, R-407B, R-402A, R-422D, R-421A, R-125/R-290/R-134a/R-600a (55.0/1.0/42.5/1.5), R-422B, R-424A, R-402B, GHG-X5, R-417A, R-438A, R-410B, R-407A, R-410A, R-442A, R-417C, R-407F, R-437A, R-407C, RS-24 (2004 formulation), and HFC-134a |
January 1, 2025 |
|
Refrigerated food processing and dispensing equipment (New) |
HFC-227ea, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 formulation) |
January 1, 2021 |
|
Vending machines (Retrofit) |
R-404A, R-507A |
January 1, 2022 |
|
Vending machines (New) |
FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-426A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), SP34E |
January 1, 2022 |
|
End-Use Category: Foams |
||
|
End-Use |
Prohibited Substances |
Effective Date |
|
Rigid polyurethane and polyisocyanurate laminated boardstock |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof |
January 1, 2020 |
|
Flexible polyurethane |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof |
January 1, 2020 |
|
Integral skin polyurethane |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Polystyrene extruded sheet |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Phenolic insulation board and bunstock |
HFC-143a, HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof |
January 1, 2020 |
|
Rigid polyurethane slabstock and other |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Rigid polyurethane appliance foam |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Rigid polyurethane commercial refrigeration and sandwich panels |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Polyolefin |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Rigid polyurethane marine flotation foam |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6 |
January 1, 2020 |
|
Polystyrene extruded boardstock and billet (XPS) |
HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel B, Formacel Z-6 |
January 1, 2021 |
|
Rigid polyurethane high-pressure two-component spray foam |
HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI |
January 1, 2020 |
|
Rigid polyurethane low-pressure two-component spray foam |
HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI |
January 1, 2021 |
|
Rigid polyurethane one-component foam sealants |
HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI |
January 1, 2020 |
TABLE 2. Prohibited Substances for New or Retrofit Refrigeration Equipment
|
End-Use |
Criteria |
Prohibited Substances |
Effective Date |
|
Commercial refrigeration: Retail food refrigeration including chillers (New) |
New refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2025 |
|
Commercial refrigeration: Retail food refrigeration including chillers (Retrofit) |
Retrofit refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2029 |
|
Commercial refrigeration: Cold storage warehouses (New) |
New refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2025 |
|
Commercial refrigeration: Cold storage warehouses (Retrofit) |
Retrofit refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2029 |
|
Industrial process refrigeration excluding chillers (New) |
New refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2025 |
|
Industrial process refrigeration excluding chillers (Retrofit) |
Retrofit refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2029 |
|
Chillers used for industrial process refrigeration (New) |
New refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 750 |
January 1, 2025 |
|
Chillers used for industrial process refrigeration (Retrofit) |
Retrofit refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 750 |
January 1, 2029 |
|
Ice rinks including chillers (New) |
New refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 150 |
January 1, 2024 |
|
Ice rinks including chillers (Retrofit) |
Retrofit refrigeration equipment with a full charge of more than 50 pounds of refrigerant |
Refrigerants with a GWP greater than 750 |
January 1, 2024 |
TABLE 3. Prohibited Substances for New or Retrofit Air Conditioning Equipment
|
End-Use |
Criteria |
Prohibited Substances |
Effective Date |
|
Room air conditioners and residential dehumidifiers (New) |
New air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2024 |
|
Room air conditioners and residential dehumidifiers (Retrofit) |
Retrofit air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2029 |
|
Other types of air conditioning equipment used in residential and nonresidential applications (New) |
New air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2026, if UL 60335-2-40 Edition 4 is adopted by the Washington state building code council by December 31, 2023; otherwise 24 months following adoption of the updated code |
|
Other types of air conditioning equipment used in residential and nonresidential applications (Retrofit) |
Retrofit air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2029 |
|
Variable refrigerant flow (VRF) or volume system (New) |
New air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2026 |
|
Variable refrigerant flow (VRF) or volume system (Retrofit) |
Retrofit air conditioning equipment |
Refrigerants with a GWP greater than 750 |
January 1, 2029 |
TABLE 4. Prohibited Substances for Small Containers of Refrigerant and Nonessential Consumer Products
|
End-Use |
Prohibited Substances |
Effective Date |
|
Small containers of refrigerant |
Substitutes with a GWP greater than 150 |
July 25, 2021 |
|
Nonessential consumer products |
Substitutes with a GWP greater than 150 |
July 25, 2021 |
Notes